output. This is useful for production environment to turn off the EM output once a luminaire has completed  

press and hold the test switch for 10 seconds.

ON/2.5s OFF stands for Disabled.

Disabled status. The indicator would blink for current status for 3 cycles. 2.5s ON/0.5s OFF stands for Enabled. 0.5s

press the test button two times, then release and press and hold the test button for two seconds. When properly 
executed the indicator on the test button will display the appropriate color for the Enable/Disable status. A  
flashing of 2.5s ON/0.5s OFF means "Enabled", while a flashing of 0.5s ON/2.5s off means "Disabled". Once Enable
/ Disable is set the status color on the test button will remain the same throughout normal operation (refer to 
Indicator Status Table).

 

is funcNoning by illuminaNng the light source. Conduct a ninety (90) minutes discharge test one (1) Nme per
year; LED light source should be illuminated for a minimum of ninety (90) minutes .
7. Replace battery only with corresponding part number.

TEST SWITCH INDICATOR STATUS:

System OK / EM Mode

Solid RED ON

System OK/AC OK (Self-diagnostic Enabled or Disabled).

EM Driver Status/Mode

LED Indicators Status

Flashing RED, 0.1s on/3s off

condition and will be turning ON when there is power (AC) failure.

 internal components other than recommended by manufacturer. failure to follow this may cause an unsafe
 condition. Servicing should only be performed by qualified service personnel or unit to be sent back for servicing.

 

It is recommended and required by applicable code to test emergency ballast to ensure proper funcNon of

 

the system; push the test switch for thirty (30) seconds every thirty (30) days to ensure the emergency driver

4. Do not let power supply cords touch hot surfaces.

Slow Flashing Red, 4s on/1s off

Self-Diagnostic test underway.

Abnormal driver performance, replace driver.

Flashing Red, 1s on/1s off

Battery not detected, check battery switch or connection.

Over temperature.

Fulham extends a limited warranty only to the original purchaser or to the first user from the date of manufacture when properly installed 

and operated under normal conditions of use. For complete terms and conditions, please reference the Fulham Product Catalog 

(www.fulham.com). Due to a program of continuous improvement, Fulham reserves the right to make modifications or variations in 

design or construction to the equipment described. © Fulham Company Limited, All Rights Reserved.

Page 2 of 3

2022-02 Rev. 00

PM-FR-004 Rev. 00

1. EM Test: Press and hold test button (>1s)to enter EM mode for testing in normal AC powered .
2. Manual Self-Diagnostic: After charging twelve (12) hours or battery fully charged, quickly press the test button

3. Enable/Disable Auto Self-Diagnostic: Press and hold the test button for one second, then release and quickly 

4. Enable / Disable Self-Diagnostic Status: Fast click 2 times within 2s to query the Self-Diagnostic Enabled /  

5. Exit Output Short Circuit/No Load/Over Voltage Protection: When the test button flashes red for 4s on/4s off, 

6. Turn off EM output: Press and hold the test switch for 10 seconds during EM output condition to turn off EM 

Very Slow Flashing Red, 1s on/7s off

 three times within two seconds to force the controller to enter a Self-Diagnostic cycle. To quit the self-diagnostic 
cycle after engaged press and hold the test button for ten seconds.

functionality testing. This applies to products with Serial Number starting with Date code: S12016 or higher.

  FHS2-20WFL-20W  EMERGENCY FLOOD LIGHT

Important and Safety Instructions

TEST SWITCH OPERATIONS:

Very Slow Flashing Red, 4s on/4s off

Flashing Red, 2s on/2s off

Fast Flashing Red, 0.1s on/0.1s off

PLEASE READ CAREFULLY AND FOLLOW ALL INSTRUCTIONS FOR YOUR OWN SAFETY
1. An un-switched AC power source of 100VAC to 277VAC is required for Charging the Battery.
2. Fixture will be operating in Non Maintained mode, i.e. In Presence of AC supply Fixture will be in OFF 

3. Make sure all electrical connections conform to the National Electrical Code and all applicable local regulations.

LED output load is Short/Over Current/Over Voltage/Open Circuit in EM 
Mode.

5. Battery is rechargeable LiFePO4 type and must be recycled or disposed of properly. Do not use Replace the

 

6. Indicator (LED light) illuminated indicates baPery in charge mode when AC power is applied.

Replace battery.