6.1.  Connecting the transmission cables

(1)  Turn off the power of the connecting unit.
(2)  Insert the driver, etc. into the hole (For open case) and open the top 

cover.

Push

Open

(3)  Connect the transmission cable to accessory KNX connector to con-

nect to KNX network.

(4)  Connect the KNX cables to (+) and (-) according to the polarity of the 

master unit.

(5)  Connect the connector cable for indoor unit to the speci

fi

 ed connector 

fi

 rmly.

(6)  Securely tighten the cable tie and then con

fi

 rm that the cable will not 

come out.

(7)  Use the 3 screws (M4 × 16 mm) provided to mount this product to the 

behind ceiling, wall, 

fl

 oor or other suitable location.

(8)  Once the wiring of the cables has been completed, 

fi

 t the 2 hooks of 

top cover and close the cover.

2 hooks

* The hole for a cable can be widened as necessary. When passing the 

thick cable through the hole, widen it.

Connector cable
to Indoor unit

KNX cable

KNX 
connector

Cable tie

Tightening strength

Cable tie 

0.3 to 0.5 N

(2.7 to 4.4 lbf)

(3 to 5 kgf)

Fix the connector cable even outside the main unit as necessary. Fix the 
cable with cable tie using 3 

fi

 xing holes.

Cable tie
(Accessories) 

Holes for 

fi

 xing cable tie (3 places)

6.2. Installation method

Do not install the main unit with the cables downward.

7.  CIRCUIT BOARD SETTING

Set this product Prog Button.

(1)  Programming Button (Prog Button)

Used for communication with the ETS.

Push to toggle between the modes.
Runtime mode (Default)  

  Programming mode 

[PROG LED off] 

[PROG LED on]

9374707171-02_IM.indb   Sec1:4

9374707171-02_IM.indb   Sec1:4

28/4/2017   AM 11:14:48

28/4/2017   AM 11:14:48

Summary of Contents for UTY-VKSX

Page 1: ...autorizado MANUALE DI INSTALLAZIONE CONVERTITORE KNX PER UNITÀ INTERNE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΜΕΤΑΤΡΟΠΕΑΣ KNX ΓΙΑ ΕΣΩΤΕΡΙΚΉ ΜΟΝΆΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO CONVERSOR KNX PARA UNIDADE INTERIOR Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ КОНВЕРТОР KNX ДЛЯ ВНУТРЕННЕГО МОДУЛЯ Только для авторизованн...

Page 2: ...e quality of the preserved or stored objects Install the unit in a well ventilated place avoiding rains and direct sun light Do not operate this unit when your hands are wet Touching the unit with wet hands will cause an electric shock If children may approach the unit take preventive measures so that they cannot reach the unit CAUTION This mark indicates procedures which if improp erly performed ...

Page 3: ...and outdoor units It may cause erroneous operation When performing wiring work be careful not to damage the cable or injure yourself Also connect the connectors securely Loose connec tors will cause trouble heating fire or electric shock Install the indoor and outdoor units power supply cable transmission cable and remote control cable 1 m 40 in away from television and ra dio to avoid distorted i...

Page 4: ...dent or trouble Use an insulated screwdriver to set the DIP switches Before opening the cover of this unit completely discharge static electricity charged on your body Otherwise failure or malfunction could result Do not touch the circuit board and circuit board parts directly with your hands Otherwise injury or electric shock could result Tightening the mounting screws too tight will damage the b...

Page 5: ...ted fit the 2 hooks of top cover and close the cover 2 hooks The hole for a cable can be widened as necessary When passing the thick cable through the hole widen it Connector cable to Indoor unit KNX cable KNX connector Cable tie Tightening strength Cable tie 0 3 to 0 5 N 2 7 to 4 4 lbf 3 to 5 kgf Fix the connector cable even outside the main unit as necessary Fix the cable with cable tie using 3 ...

Page 6: ...ng initialization If an error occurs the LED5 LED6 LED7 Prog LED lights or flashes Please refer to the Error code below 9 LED DISPLAY 9 1 Normal code Normal indications Normal contents LED5 green LED6 orange LED7 red Prog LED red Normal starting Flashes alternately Start sequence or address rewriting Programming mode display Display mode On Off 1 0s ON 1 0s OFF State unconcerned 9 2 Error code For...

Reviews: