Fujitsu UTY-RNNUM Installation Manual Download Page 5

En-5

5.3. Connection of remote controller cable

CAUTION

When connecting the remote controller cable to the wall 

• 

mounted type indoor unit, do not connect it to the outdoor 
unit or the indoor unit power terminal block. It may cause 
a failure.

There are 2 methods to connect the remote controller cable 
to the indoor unit. One is the connection using contained 
connecting cable and the other is the connection the remote 
controller cable is connected to the exclusive terminal block of 
the indoor unit.
Exclusive terminal block for remote controller connection 
method is different depending on each model. Modify the 
remote controller cable as per below description and connect it.
(For the details, refer to the installation manual of the indoor 
unit to be used.)

5.3.1.  When connecting to the wall mounted type 

connector

Connect the remote controller cable to the connecting cable 
and insert it to the connector.

PCB

Connecting cable

Remote controller 
cable

Indoor unit

Outdoor 
unit / 
power 
supply 
terminal 
block

Connector

Modify the cable as per below methods.

(1) Use a tool to cut off the terminal on the end of the remote 

controller cable and then remove the insulation from the cut 
end of the cable as shown in Fig. 1.

(2) Connect the remote controller cable and connecting cable 

as shown in Fig. 2.

(3) Be sure to insulate the connection between the cables.

Connecting 
cable

Connector

Fig. 1

Fig. 2

White

Red

White

Red

Black

Black

Insulated
connection

Remote
controller cable

Remote
controller cable

20 mm 

(13/16 in.)

5.3.2.  When connecting to the exclusive terminal 

block

Connect the end of remote controller cable directly to the 
exclusive terminal block.

Terminal block

M4 screw

PCB

Indoor unit

Outdoor unit /
power supply
terminal block

Remote controller
terminal block

Remote controller 
cable

   It may be failed if it is connected to the outdoor unit or 

the terminal block for power supply.

d

6. INSTALLATION METHODS

6.1. Group control

A number of indoor units can be operated at the same time 

• 

using a single remote controller.
Depending on the model, some indoor units cannot be 

• 

connected for group control. (Option is not available for 
U.S.A. wall mounted type indoor unit.)
Some functions may become unusable, depending on the 

• 

combination of the indoor units that are connected in a 
group.

(1) Wiring method (indoor unit to remote controller)
 

EXAMPLE: Single Type

Remote controller

Remote controller
cable

Indoor unit 0

Indoor unit 1

Indoor unit 2

Indoor unit 3

1 2 3

1 2 3

1 2 3

1 2 3

1 2 3

(2) Indoor unit address setting
 

Set each indoor unit address using the DIP switch of each 
indoor unit. 

 

(Refer to the installation manual for the indoor unit.)

9373328148-02_IM_EN_FR_SP.indb   5

9373328148-02_IM_EN_FR_SP.indb   5

9/14/2010   1:15:27 PM

9/14/2010   1:15:27 PM

Summary of Contents for UTY-RNNUM

Page 1: ...ons 3 4 2 Name of parts 3 5 INSTALLING THE REMOTE CONTROLLER 4 5 1 Installation 4 5 2 Setting the DIP switch 4 5 3 Connection of remote controller cable 5 6 INSTALLATION METHODS 5 6 1 Group control 5 6 2 Dual remote control 6 7 TURNING ON THE POWER 6 8 SETTING THE ROOM TEMPERATURE DETECTION LOCATION 6 9 FUNCTION SETTING 7 10 TEST OPERATION 9 11 ERROR CODES 9 For authorized service personnel only E...

Page 2: ... with your hands Do not wire the remote controller cable together with or parallel to the connection cables and power supply cables of the indoor unit and outdoor unit It may cause erroneous operation When installing cable near a source of electromagnetic waves use shielded wire Do not set the DIP switches either on the air conditioner or the remote controller in any way other than indicated in th...

Page 3: ...ection and swing Button C Economy Thermo Sen sor Button D Maintenance Filter Reset Button E Operation Lamp F Day Display G Operation Lock Display H Temperature Display I Fan Speed Display J Timer Mode Display K Operation Mode Display L Timer and Clock Display M Filter Display N Economy Display O Thermo Sensor Display P Vertical Swing Display Q Horizontal Swing Display R Defrost Display 4 SELECTING...

Page 4: ...NSTALLING THE REMOTE CONTROLLER 5 1 Installation 5 1 1 Installing the remote controller Open the operation panel on the front of the remote controller remove the 2 screws indicated in the following figure and then remove the front case of the remote controller When installing the remote controller remove the connector from the front case The wires may break if the connector is not removed and the ...

Page 5: ...1 2 Connect the remote controller cable and connecting cable as shown in Fig 2 3 Be sure to insulate the connection between the cables Connecting cable Connector Fig 1 Fig 2 White Red White Red Black Black Insulated connection Remote controller cable Remote controller cable 20 mm 13 16 in 5 3 2 When connecting to the exclusive terminal block Connect the end of remote controller cable directly to t...

Page 6: ...ting factory setting The room temperature is detected by the indoor unit temperature sensor 1 When the button is pressed the lock display flashes because the function is locked at the factory A Indoor unit B Indoor unit remote controller setting room temperature sensor selection The temperature sensor of the indoor unit or the remote controller can be used to detect the room temperature When use t...

Page 7: ...oor unit SU MO TU WE TH FR SA 6 Repeat steps 2 to 5 to perform additional settings Press the button button and simultaneously again for more than 5 seconds to cancel the function setting mode In addition the function setting mode will be automatically canceled after 1 minute if no operation is performed 7 After completing the FUNCTION SETTING be sure to turn off the power and turn it on again Func...

Page 8: ...tandard 31 00 Lower control 01 Slightly warmer control 02 Warmer control 03 7 Auto restart Enable or disable automatic system restart after a power outage Factory setting Setting Description Function Number Setting Value Yes 40 00 No 01 Auto restart is an emergency function such as for power fail ure etc Do not start and stop the indoor unit by this function in nor mal operation Be sure to operate...

Page 9: ...lamp will light up and 1 will be displayed on the set temperature display Perform the test operation for 60 minutes Pressing the START STOP button will stop the test operation Test operation display 11 ERROR CODES If you use a wired type remote control error codes will appear on the remote control display If you use a wireless remote control the lamp on the IR receiver unit will output error codes...

Page 10: ...oor unit Active filter error Outdoor unit 6 5 IPM error Outdoor unit 6 10 Display panel error Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit Outdoor unit 9 4 Trip detection Outdoor unit Outdoor unit Outdoor unit 9 9 10 1 4 way valve error Outdoor unit Discharge temperature 1 error Refriger ant system Display mode 0 ...