En-10

7.4. Connection of wiring

7.4.1. Terminal Explanation and Cable Holes

•  Only one cable can be passed through each cable hole. To pass multiple cables 

through a single cable hole, use a (

fi

 eld supply) multi-conductor cable with more wires, 

and bundle multiple cables into one.

•  Maximum length of cable is 10 m. (recommended value, Except "P1" and "TR1")

TH1 TH2

TH3 TH4

EV1

EV2

EX1 EX2 EX3 EX4

EX6 EX7

EX5

EX8 EX9

EX10

P1

D1

TR1

R1

·Power supply terminal
·Drain pump signal terminal

·Transmission terminal
·Remote controller terminal

·External interface terminal

Cable holes with mounted cable glands (accessories)

Hole No.

Cable gland 

type

Diameter 

(mm)

Insertable cable 

dimensions (mm)

H2

Large

Φ

20.0

Φ

6 to 12

H5, H6, H7, H9, H10

Medium

Φ

16.2

Φ

4 to 8

H1, H3, H4, H8

Small

Φ

10.2

Φ

3 to 6

H1

H2

H3

H5

H4

H8

H9

H10

H6

H7

Terminal 

No.

Terminal Name

Hole No.

Connection

Recommended 

cable size

(mm

2

)

Cable type

Speci

fi

 cations

P1

POWER SUPPLY

H2

Power supply

2.5 (AWG14)

Type245 IEC57 or 
equivalent

1ø 50 Hz 198 to 264 V 
2 Cable + earth (ground)

TR1

TRANSMISSION

H3

Transmission line

0.33 (AWG22)

LONWORKS compatible 
cable

22 AWG LEVEL 4 (NEMA) 
non-polar 2 core, twisted 
pair solid core diameter 
0.65 mm

R1

REMOTE CONTROLLER

H4

2-wire type remote controller

0.33 to 1.25
(AWG22 to 16)

Sheathed PVC cable

Non polar 2 core

3-wire type remote controller

0.33 (AWG22)

Sheathed PVC cable

Polar 3 core

D1

DRAIN PUMP

H1

Drain pump

0.5 (AWG20)

Type245 IEC57 or 
equivalent

T1

THERMISTOR (GAS)

H5

Thermistor mounted to the gas 
pipe

0.33 (AWG22)

Sheathed PVC cable

Relay the multi-conductor 
cable, and pass it through 
the designated hole.

T2

THERMISTOR (LIQUID)

Thermistor mounted to the liquid 
pipe

T3

THERMISTOR (INLET AIR)

Thermistor mounted to the inlet

T4

THERMISTOR (OUTLET AIR)

Thermistor mounted to the outlet

EV1

EEV1

1 - Red
2 - Brown
3 - Black
4 - Green
5 - Yellow
6 - White

H9

Electronic expansion valve 1

0.33 (AWG22)

Sheathed PVC cable

EV2

EEV2

H10

Electronic expansion valve 2

0.33 (AWG22)

Sheathed PVC cable

Use the electronic 
expansion valves only 
when two units are 
connected

EX1

ON/OFF SIGNAL 
(OUTPUT)

External output 
/ Digital

H6

External controller

0.33 (AWG22)

Sheathed PVC cable

EX2

ERROR SIGNAL 
(OUTPUT)

External output 
/ Digital

EX3

FAN SIGNAL

External output 
/ Digital

EX4

DEFROST SIGNAL

External output 
/ Digital

EX5

THERMOSTAT ON/OFF 
SIGNAL

External output 
/ Digital

EX6

ON/OFF SIGNAL (INPUT)

External input 
/ Digital

H7

External controller

0.33 (AWG22)

Sheathed PVC cable

ERROR SIGNAL
 OFF(Open)= 

Error

 ON(Short)= 

Normal

EX7*

ERROR SIGNAL *
(INPUT)

External input 
/ Digital

The factory default is shorted between the 
terminals by the cables.

EX8

COOL/HEAT SIGNAL

External input 
/ Digital

EX9

ANALOG SIGNAL

External input 
/ Analog

EX10

FLOAT SW SIGNAL

External input 
/ Digital

H8

Float switch mounted to the heat 
exchanger

0.33 (AWG22)

Sheathed PVC cable

EX7*: The factory default is shorted between the terminals by the cables. If there is a malfunction with an external device, using this external input is recommended in order to protect the 

refrigerant system.

9381279005_IM.indb   10

9381279005_IM.indb   10

6/30/2014   11:31:18 AM

6/30/2014   11:31:18 AM

Summary of Contents for UTP-VX30A

Page 1: ...PART NO 9381279005 Original instructions INSTALLATION MANUAL DX kit For authorized service personnel only UTY VDGX UTP VX30A UTP VX60A UTP VX90A TM ...

Page 2: ...his unit contains no user serviceable parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THIS PRODUCT 2 1 Precautions for using R410A refrigerant WARNING Do not introduce any substance other than the prescribed refrigerant into the refrigeration cycle If air enters the refrigeration cy...

Page 3: ...or Inlet air and Outlet air 2 For measuring the room temperature Thermistor Label GAS 1 For measuring the gas pipe temperature For gas pipes Thermistor Label LIQ 1 For measuring the liquid pipe temperature For liquid pipes Thermistor holder pipe Small 1 For mounting the thermistor Thermistor holder pipe Large 1 For mounting the thermistor Name and Shape Q ty Application Thermistor spring For small...

Page 4: ... temperature Refer to the Design Technical manual Condensation temperature Refer to the Design Technical manual Capacity Class kW 14 0 20 0 25 0 40 0 50 0 EEV unit model No 60 90 90 90 90 90 90 Cooling capacity kW 14 22 4 25 40 50 4 Heating capacity kW 16 25 28 45 56 5 Heat exchanger capacity Refer to the Design Technical manual Airflow rate Reference m3 h 2 240 3 560 4 000 6 400 8 000 Capacity ra...

Page 5: ...n below System Configuration Diagram Fujitsu general approved devices Outdoor unit Indoor unit Control unit Liquid pipe Gas pipe Control line Thermistor 4 Wired remote controller Piping Wiring EEV unit 3 2 3 Pipe Conditions EEV unit Heat Exchanger R Straight pipe 200 mm or more Liquid pipe Gas pipe 4 INSTALLATION WORK Correct initial installation location is important because it is difficult to mo...

Page 6: ...nly Cannot be installed outdoors EEV unit inclination limits 10 or less 10 or less 4 3 1 Installing the Control unit If installing outdoors make sure to orient A upwards Using a template accessory is recommended when positioning the holes for mounting the control unit 5 or less Inclination limits Sealing washers 3 Accessories M8 Nuts 3 Accessories A A Contorl unit 200 mm or more Service space 200 ...

Page 7: ...tion location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 to 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 use heat insulation that is 20 mm or thicker If heat insulation is used that is not as thick as specified condensation may form on the surface of the ins...

Page 8: ...round cable Improper earthing grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the DX kit can be operated safely and positively Connect the connection cable firmly to the terminal board Imperfect installation may cause a fire If the supply cable is damaged it must be ...

Page 9: ...ent breaker requirements Model MCA MFA UTY VDGX 0 096 A 20 A MCA Minimum Circuit Ampacity MFA Main Fuse Ampacity When the power crossover wiring is done make it so that the total of the MCA of the connected DX kits RB units and indoor units does not exceed the 15 A For indoor unit MCA and RB unit MCA refer to the indoor unit and RB unit installation manual If the capacity of connected DX kits RB u...

Page 10: ...therwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the table for the terminal screw tightening torques 7 Please do not fix 2 power supply cables with 1 screw Sleeve Strip 10 mm Screw with special washer Screw with special washer Ring terminal Cable Terminal block Cable Ring ...

Page 11: ...G20 Type245 IEC57 or equivalent T1 THERMISTOR GAS H5 Thermistor mounted to the gas pipe 0 33 AWG22 Sheathed PVC cable Relay the multi conductor cable and pass it through the designated hole T2 THERMISTOR LIQUID Thermistor mounted to the liquid pipe T3 THERMISTOR INLET AIR Thermistor mounted to the inlet T4 THERMISTOR OUTLET AIR Thermistor mounted to the outlet EV1 EEV1 1 Red 2 Brown 3 Black 4 Gree...

Page 12: ...le gland recommended value A B For M10 0 5 N m 0 5 N m For M16 1 0 N m 1 5 N m For M20 1 0 N m 2 0 N m Outdoor cable connections 1 Thermistor cable connections Connect the thermistor cables to the relay multi conductor cables as shown in the diagram before passing through the hole Make sure to use only weatherproof relay cables Terminal block Thermistor Relay cable Cable connector 2 Electronic exp...

Page 13: ...R SIGNAL INPUT CNA06 CNA07 COOL HEAT SIGNAL CNA03 CNA04 FLOAT SW SIGNAL Incompatible CNA05 External input terminal Dry contact terminal External input terminal Apply voltage terminal External output terminal CNA01 CNA04 CNA02 CNA07 CNB01 Controller PCB CNA03 CNA06 Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed The wire c...

Page 14: ...e Pulse input method Terminal block Input signal Command ON OFF SIGNAL INPUT Pin1 to Pin2 OFF ON Operation Pin1 to Pin3 OFF ON Stop The last command has priority The indoor units within the same remote controller group operates in the same mode 2 ERROR SIGNAL INPUT If an error signal is input perform protection operation Thermostat OFF mode Make sure to install so that the input signals during nor...

Page 15: ...her than the DX kit Connected unit etc 1 2 3 4 5 6 Power supply Terminal Relay PC board Control unit DX kit Connected unit Connected device 1 Connected device 2 Connected device 3 Connected device 4 Connected device 5 Drain pump PC board Power supply for drain pump AC 220 to 240 V 1A max DC 30 V max 1A max When using a drain pump connect relay that is compatible with AC power supply field supply P...

Page 16: ...t where the wireless remote controller can be used the addresses can also be set using the remote controller If setting the addresses using the wireless remote controller set the indoor unit address and refrigerant circuit address to 00 For information on setting using the wireless remote controller Table A Address Rotary Address Rotary Switch Setting Switch Setting Refrigerant circuit REF AD SW I...

Page 17: ...FF ON ON Precautions if using the DX kit as the administrative indoor unit If the Administrative indoor unit setting is ON for another indoor unit connected to the same refrigerant system or RB unit make sure to turn OFF that setting For details see the wired remote controller installation manual When connecting the wired remote controller to the DX kit set this switch to OFF Set the Administrativ...

Page 18: ...R CODES When an error occurs the LED on the PC board LED name LED1 flashes Error code can be viewed by connecting the optional wired remote controller group remote controller and IR receiver unit etc If you use a wired type remote controller Optional parts error codes will appear on the remote controller display If you use a wireless remote controller IR receiver unit of optional parts the lamp on...

Page 19: ...he operation temperature using analog external inputs Connected unit Connected device Control unit DX kit Analog signal The operation temperature is set by changing the voltage of the input signals If using this function set the DIP switch SET3 2 to OFF Formula Operation temperature T C 2 5 Ain 7 5 Ain Input voltage 1 0 to 9 0V See the following diagram for the advanced input conditions a Using th...

Reviews: