Chapter 13
Fan Unit Replacement
13-5
13.3
Mounting a Fan Unit
Caution –
Do not forcibly mount a fan unit in a slot. Forcibly pushing a fan unit in
a slot may damage the fan unit or the server.
1. Adjust the position of the fan unit so that its latch is on the right when you are
facing the front of the server.
2. Insert the fan unit in the slot.
3. Complete the
replacefru
command which has been executed in the XSCF
command prompt. For details, see
Section 4.4.1, “FRU Removal and
Replacement (Power supply unit/Fan unit)” on page 4-8
13.4
Reassembling the Server
1. Attach the fan cover.
For details, see
Section 5.4.2, “Attaching the Fan Cover” on page 5-8
.
2. If the equipment rack is supplied with a Quake-Resistant Options Kit or
stabilizer, return to its original position.
For details, see
Section 5.1.2, “Sliding the Server into the Equipment Rack” on
3. From the XSCF Shell prompt, use the
showhardconf
command to verify that
the new fan unit has been installed.
For details, see
Section 4.4.2, “Verifying the Hardware Operation (Power supply
XSCF>
showhardconf
Summary of Contents for SPARC Enterprise M3000
Page 4: ......
Page 91: ...Chapter 5 Internal Components Access 5 5 FIGURE 5 3 Removing the Air Duct ...
Page 114: ...7 10 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 120: ...8 6 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 128: ...9 8 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 146: ...12 6 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 152: ...13 6 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 160: ...14 8 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 166: ...15 6 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 170: ...A 4 SPARC Enterprise M3000 Server Service Manual March 2012 ...
Page 178: ...B 8 SPARC Enterprise M3000 Server Service Manual March 2012 ...