Confirming the operation of indoor unit

88

 

88

 

Run the unit in a normal way, and confirm its operation. (Please end the test run first 

before confirmation)

(1) Cold air (or warm air) must be discharged from the indoor unit.

(2) The indoor unit operates normally when air direction or air volume adjustment button 

is pressed.

PUMP DOWN

98

 

PUMP DOWN OPERATION

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, 

recover refrigerant by doing the cooling operation or forced cooling operation according 

to the following procedure. (When the cooling operation cannot start in winter, and so on, 

start the forced cooling operation.)

(1) Do the air purging of the charge hose by connecting the charging hose of gauge 

manifold to the charging port of 3 way valve (At lease one unit of connected units) and 

opening the low pressure valve slightly.

(2) Close the valve stem of 2 way valve (All connected units) completely.

(3) Start the cooling operation or following forced cooling operation. (All connected 

units) When using the remote control unit Press the TEST RUN button after starting 

the cooling operation by the remote control unit. The operation indicator lamp and 

timer indicator lamp will begin to flash simultaneously during test run. When using 

the MANUAL AUTO button of the indoor unit (The remote control unit is lost, and so 

on.) Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 

seconds. (The forced cooling operation cannot start if the MANUAL AUTO button is not 

kept on pressing for more than 10 seconds.)

(4) Close the valve stem of 3 way valve (All connected units) when the reading on the 

compound pressure gauge becomes 0.05

0 MPa (7.3

0 psi).

(5) Stop the operation. (All connected units) Press the START/STOP button of the remote 

control unit to stop the operation. Press the MANUAL AUTO button when stopping the 

operation from indoor unit side. (It is not necessary to press on keeping for more than 

10 seconds.)

 

CAUTION

During the pump-down operation, make sure that compressor is off before you remove 

the refrigerant piping. Do not remove the connection pipe while the compressor is 

in operation with 2 or 3 way valve open. This may cause abnormal pressure in the 

refrigeration cycle that breakage and injury.

CUSTOMER GUIDANCE

118

 

Explain the following to the customer in accordance with the operating manual:

(1) Starting and stopping method, operation switching, temperature adjustment, timer, air 

flow adjustment, and other remote control unit operations.

(2) Air filter removal and cleaning.

(3) Give the operating manual and installation instruction sheet to the customer.

TEST RUN

88

 

The test run method may be different for each indoor unit that is connected. Refer to the 

installation instruction sheet included with each indoor unit.

 

CAUTION

Always turn on the power 12 hours prior to the start of the operation in order to ensure 

compressor protection.

 Make a test run in accordance with the installation Manual  

88

 

18

 

for the indoor unit

(1) Indoor unit

1

 Is operation of each button on the remote control unit normal?

2

 Does each lamp light normally?

3

 Do the air flow-direction louver operate normally?

4

 Is the drain normal?

5

 Is there any abnormal noise and vibration during operation?

(2) Outdoor unit

1

 Is there any abnormal noise and vibration during operation?

2

 Will noise, wind, or drain water from the unit disturb the neighbors?

3

 Is there any gas leakage?

• Do not operate the air conditioner in the test running state for a long time.

• For the operation method, refer to the operating manual and perform operation check

Outdoor unit LED

88

 

88

 

When a malfunction occurs in the outdoor unit, the LED on the circuit board lights to 

indicate the error. Refer to the following table for the description of each error according 

to the LED.

Error contents

LED1

LED2

LED3

LED4

Serial Communication error 

 

(Outdoor unit to Indoor unit A)

● 1 time

Serial Communication error 

 

(Outdoor unit to Indoor unit B)

● 1 time

Serial Communication error 

 

(Outdoor unit to Indoor unit C)

● 1 time

Serial Communication error 

 

(Outdoor unit to Indoor unit D)

● 1 time

Discharge temp. sensor error

● 2 times

Outdoor unit Heat Ex. middle temp. 

sensor error

● 3 times

Outdoor temp. sensor error

● 4 times

2-way valve temp. sensor error 

 

(for Indoor unit A)

● 5 times

2-way valve temp. sensor error 

 

(for Indoor unit B)

● 5 times

2-way valve temp. sensor error 

 

(for Indoor unit C)

● 5 times

2-way valve temp. sensor error 

 

(for Indoor unit D)

● 5 times

3-way valve temp. sensor error 

 

(for Indoor unit A)

● 6 times

3-way valve temp. sensor error 

 

(for Indoor unit B)

● 6 times

3-way valve temp. sensor error 

 

(for Indoor unit C)

● 6 times

3-way valve temp. sensor error 

 

(for Indoor unit D)

● 6 times

Compressor temp. sensor error

● 7 times

Heat sink temp. sensor error

● 8 times

High pressure switch 1 error

● 9 times

High pressure switch 2 error

● 10 times

Indoor unit capacity error

● 11 times

Trip detection

● 12 times

Compressor rotor position detection 

error

● 13 times

Trip terminal L error

● 14 times

Outdoor unit fan motor error

● 15 times

Outdoor unit PCB microcomputer 

communication error

● 17 times

Discharge temperature error

● 18 times

Compressor temperature error

● 19 times

4-way valve error

● 20 times

Outdoor unit PCB model information 

error

● 21 times

Active filter error, PFC circuit error

● 22 times

● : flashing         – : Off

9374747115_IM_En.indd   11

20/12/2553   13:13:13

Summary of Contents for R410A

Page 1: ...TIONER OUTDOOR UNIT PART NO 9374747115 INSTALLATION MANUAL For authorized personnel only MANUEL D INSTALLATION Pour le personnel agréé uniquement MANUAL DE INSTALACIÓN Solo para personal autorizado 9374747115_IM_En indd 1 20 12 2553 8 58 37 ...

Page 2: ...ply refrigeration compressor oil or equivalent used for the outdoor unit to the matching surfaces of the flare and union tubes before connecting them then tighten the nut with a torque wrench for a leak free connection Check carefully for leaks before starting the test run NOTE Depending on the system type liquid and gas lines may be either narrow or wide Therefore to avoid confusion the refrigera...

Page 3: ...g than with refrigerant models Also when storing the piping securely seal the openings by pinching taping etc When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose composition is stable Special tools for R410A 222222 Tool name Contents of change Gauge manifold Pressure is high and cannot ...

Page 4: ...of this product are shown in the table If the units are further apart than this correct operation cannot be guaranteed Total max length a b c d 70 m 230 ft 1 Max length for each indoor unit a b c or d 25 m 82 ft Max height difference between outdoor unit and each indoor unit H1 15 m 49 ft Max height difference between indoor units H2 10 m 33 ft Min length for each indoor unit a b c or d 5 m 16 ft ...

Page 5: ...the like to prevent their access Install the outdoor unit in a location that would not inconvenience your neighbors as they could be affected by the airflow coming out from the outlet noise or vibration If it must be installed in proximity to your neighbors be sure to obtain their approval If the outdoor unit is installed in a cold region that is affected by snow accumulation snow fall or freezing...

Page 6: ...ere it is very dusty 7 Do not install the unit where people pass 8 Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible 9 Install the unit where connection to the indoor unit is easy Single outdoor unit installation 333333333 When the upward area is open When there are obstacles at the back side 100 m m 4 in or m ore When there are o...

Page 7: ... a pipe cutter 2 Hold the pipe downward so that the cuttings will not enter the pipe and remove any burrs 3 Insert the flare nut always use the flare nut attached to the indoor and outdoor units respectively onto the pipe and perform the flare processing with a flare tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dus...

Page 8: ...of the specified capacity When selecting breaker please comply with the laws and the regulations of each country One breaker must be installed on the power supply of the outdoor unit Wrong selection and setup of the breaker will cause electric shock or fire Do not connect AC power supply to the transmission line terminal board Improper wiring can damage the entire system Connect the connector cord...

Page 9: ...the specified wires connect them securely and fasten them so that there is no stress placed on the terminals 4 Use an appropriate screwdriver to tighten the terminal screws Do not use a screwdriver that is too small otherwise the screw heads may be damaged and prevent the screws from being properly tightened 5 Do not tighten the terminal screws too much otherwise the screws may break 6 See the tab...

Page 10: ...p to the specified pressure all at once but do so gradually 1 Increase the pressure up to 0 5 MPa 73 psi let it sit for about 5 minutes and then check for any decrease in pressure 2 Increase the pressure up to 1 5 MPa 218 psi let it sit for about 5 minutes and then check for any decrease in pressure 3 Increase the pressure up to the specified pressure the pressure designed for the product and then...

Page 11: ...e air conditioner do not mix gas other than the specified refrigerant R410A inside the refrigerant cycle When charging the refrigerant R410A always use an electronic balance for refrigerant charging to measure the refrigerant by weight When charging the refrigerant take into account the slight change in the composition of the gas and liquid phases and always charge from the liquid phase side whose...

Page 12: ...val and cleaning 3 Give the operating manual and installation instruction sheet to the customer TEST RUN 888 The test run method may be different for each indoor unit that is connected Refer to the installation instruction sheet included with each indoor unit CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection Make a test run in ac...

Page 13: ...9374747115_IM_En indd 12 20 12 2553 8 59 06 ...

Reviews: