background image

En-9

 Cable preparation

Keep the earth (ground) wire longer than the other wires.

NOTES:  

When using a sealed cable

2-1/8 in (60 mm)

Power supply cable 
or connection cable

 Earth wire

2-15/16 in (75 mm) 

or more

 Wiring procedure

(1)

 

Remove the outdoor unit switch cover.(Refer to “3.5.1. Switch cover removal”.)

(2)

 

Remove the outdoor unit conduit cover. (Refer to “3.10.1. Conduit installation”.)

(3)

 

Connect the power supply cable and the connection cable to terminal.

(4)

 

Fasten the power supply cable and connection cable with cable tie (accessories).

(5)

 

Install the conduit cover.(Refer to “3.10.1. Conduit installation”.)

L2

L1

Cut off the 

excess

Thread the cable tie through 

the hole and tighten securely

Cable tie (accessories)

4. TEST RUN

Make a test run in accordance with the installation manual for the indoor unit.

5. FINISHING

5.1. Installing insulation

• Install insulation material after conducting “3.7. Sealing test”.
• To prevent condensation and water droplets, install insulation material on the refrigerant 

pipe. 

• Use insulation with heat resistance above 248 °F (120 °C).
• Refer to the table to determine the thickness of the insulation material.

  Selection of insulation

(Use an insulation material with equal heat transmission rate or below 0.040 
W/(m·k))

Insulation material minimum thickness [in (mm)]

Relative humidity

 70%

 75%

 80%

 85%

Pipe diameter 

[in (mm)]

1/4 (6.35)

5/16 (8)

3/8 (10)

1/2 (13)

11/16 (17)

3/8 (9.52)

3/8 (9)

7/16 (11)

9/16 (14)

11/16 (18)

1/2 (12.70)

3/8 (10)

1/2 (12)

9/16 (15)

3/4 (19)

5/8 (15.88)

3/8 (10)

1/2 (12)

5/8 (16)

13/16 (20)

3/4 (19.05)

3/8 (10)

1/2 (13)

5/8 (16)

13/16 (21)

*  When the ambient temperature and relative humidity exceed 89.6 °F (32 °C) (DB) and 

85% respectively, please strengthen the heat insulation of refrigerant pipe.

6. PUMP DOWN

 Pump down operation (forced cooling operation)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, 
recover refrigerant by doing the forced cooling operation according to the following proce-
dure. 
(1)  Conduct preliminary operation for 5 to 10 minutes using the forced cooling opera-

tion. Start the forced cooling operation. Keep on pressing the [MANUAL AUTO] of the 
indoor unit for more than 10 seconds. The operation indicator lamp and timer indicator 
lamp will begin to flash simultaneously during test run. (The forced cooling operation 
cannot start if the [MANUAL AUTO] is not kept on pressing for more than 10 seconds.)

(2)  Close the valve stem of 2-way valve completely.
(3)  Continue the forced cooling operation for 2 to 3 minutes, then close all the valve stems 

on the 3-way valves

(4)  Stop the operation.

• Press the [START/STOP] of the remote controller to stop the operation.
•  Press the [MANUAL AUTO] when stopping the operation from the indoor unit side. 

(It is not necessary to press down for more than 10 seconds.)

 CAUTION

Please check the refrigerant circuit for any leaks before starting the pump down 
operation.
Do not proceed with the pump down operation if there is no refrigerant left in the 
circuit due to bent or broken piping.
During the pump down operation, be sure to turn off the compressor before removing 
the refrigerant piping.

9319205403_IM_3L.indb   9

9319205403_IM_3L.indb   9

11/19/2019   9:02:48 AM

11/19/2019   9:02:48 AM

Summary of Contents for LM 12

Page 1: ...uct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In Moist or Uneven Locations Use a raised concrete pad or concrete blocks to provide a solid level foundation for the outdoor unit This prevents water damage and abnormal vibration In an Area with High W...

Page 2: ... earth ground the unit correctly and use the power cable combined with an Earth Leakage Circuit Breaker ELCB The units are not explosion proof and therefore should not be installed in explosive atmosphere This unit contains no user serviceable parts Always consult experienced service technicians for repairing When moving or relocating the air conditioner consult experienced service technicians for...

Page 3: ...t Location Working period Protection method Outdoor 1 month or more Pinch pipes Less than 1 month Pinch or tape pipes Indoor Pinch or tape pipes 2 3 2 Refrigerant pipe size and allowable piping length CAUTION Keep the piping length between the indoor unit and outdoor unit within the allowable tolerance The maximum lengths of this product are shown in the table If the units are further apart than t...

Page 4: ...ignal conditions If children under 10 years old may approach the unit take preventive measures so that they cannot reach the unit Keep the length of the piping of the indoor and outdoor units within the allowable range For maintenance purposes do not bury the piping Decide the mounting position with the customer as follows 1 Install the outdoor unit in a location which can withstand the weight of ...

Page 5: ...9 15 16 252 15 11 16 399 3 2 3 Outdoor units installation multi row Unit in mm 1 Single parallel unit arrangement 4 100 or more 8 200 or more 20 500 or more 40 1 000 or more 2 Multiple parallel unit arrangement 8 200 or more 16 400 or more 40 1 000 or more 10 250 or more 80 2 000 or more 10 250 or more 40 1 000 or more 8 200 or more 8 200 or more 10 250 or more CAUTION Do not install the outdoor u...

Page 6: ...before connecting the connection pipe 2 Centering the pipe against port on the outdoor unit turn the flare nut with your hand To prevent gas leakage coat the flare surface with alkylbenzene oil HAB Do not use mineral oil 3 Tighten the flare nut of the connection pipe at the outdoor unit valve connector Connection pipe liquid Connection pipe gas Flare nuts 2 way valve liquid 3 way valve gas 4 When ...

Page 7: ...Gauge manifold Flare nuts Blank caps Vacuum pump Charging port Service valve gas Use a 3 16 in 4 mm hexagon wrench Charging port cap 3 9 Additional charging WARNING When moving and installing the air conditioner do not mix gas other than the specified refrigerant R410A inside the refrigerant cycle If air or other gas enters the refrigerant cycle the pressure inside the cycle will rise to an abnorm...

Page 8: ...eaker itself Do not use crossover power supply wiring for the outdoor unit If the temperature surrounding the breaker is too high the amperage at which the breaker cuts out may decrease When the electrical switchboard is installed outdoors place it under lock and key so that it is not easily accessible Start wiring work after closing branch switch and over current breaker Connection cable between ...

Page 9: ... 16 20 3 4 19 05 3 8 10 1 2 13 5 8 16 13 16 21 When the ambient temperature and relative humidity exceed 89 6 F 32 C DB and 85 respectively please strengthen the heat insulation of refrigerant pipe 6 PUMP DOWN Pump down operation forced cooling operation To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal recover refrigerant by doing the forced cooling operat...

Reviews: