5.2 Setting
C141-E235
5-3
5.2 Setting
5.2.1
Loop ID setting
When setting the fibre channel loop ID, use SEL0 to SEL6 of interface connector CN1. IN bit
weighting, SEL6 corresponds to the MSB, SEL0 to the LSB, and 126 types of X'00' to X'7D' can be
specified as loop IDs.
5.2.2
Mode settings
(1)
Motor start mode
The method for start control of the HDD spindle motor can be set in accordance with Table 5.1.
Table 5.1
Motor start mode
Setting
Signal name
Start_2/Mated Start_1/Mated
Start
mode
Connector pin
CN1-10 pin
CN1-09 pin
Open
Open
The drive is not connected to the system. The drive does not start the
spindle motor.
Open
GND
The drive is connected to the system. After recognizing the
connection, the drive starts the spindle motor upon receipt of a
START/STOP UNIT command.
GND
Open
The drive is connected to the system. After recognizing the
connection, the drive starts the spindle motor after a prescribed delay
time has elapsed.
GND
GND
The drive is connected to the system. The drive starts the spindle
motor immediately after recognizing the connection.
Set the loop ID so that there are no duplicates between devices on the
same loop.
Summary of Contents for HARD DISK DRIVES MAW3073FC
Page 1: ...C141 E235 01EN MAW3300FC MAW3147FC MAW3073FC HARD DISK DRIVES PRODUCT MAINTENANCE MANUAL ...
Page 4: ...This page is intentionally left blank ...
Page 10: ...This page is intentionally left blank ...
Page 14: ...This page is intentionally left blank ...
Page 16: ...This page is intentionally left blank ...
Page 22: ...This page is intentionally left blank ...
Page 30: ...This page is intentionally left blank ...
Page 38: ...This page is intentionally left blank ...
Page 94: ...This page is intentionally left blank ...
Page 108: ...This page is intentionally left blank ...
Page 110: ...This page is intentionally left blank ...
Page 111: ......
Page 112: ......