3-2. Outdoor unit—No power
Forecast of cause
Power supply failure
External cause
Electrical components defective
Check point 1. Check installation condition
•
Is the circuit breaker on or off?
•
Check loose or removed connection cable.
→ If abnormal condition is found, correct it by referring to the installation manual or the “DESIGN &
TECHNICAL MANUAL”.
↓
Check point 2. Check external cause at indoor and outdoor (voltage drop or noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 3. Check electrical components
Check the voltage of power supply.
Check if AC 198 to 264 V appears at outdoor unit terminal L—N
→ If no, go to
and
.
+
-
↓
•
Check fuse in main PCB.
If fuse is open, check if the wiring between terminal and main PCB is loose, and replace fuse.
↓
Check point 4. Replace the main PCB
If check point 1 to 3 do not improve the symptom, replace the main PCB.
↓
End
3-2. Outdoor unit—No power
- (03-35) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHH30KMTB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 07 19 SR_CH01_AS073EG_02 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 07 19 SR_CH02_AS073EG_01 ...
Page 33: ...3 TROUBLESHOOTING 2022 08 22 SR_CH03_AS073EG_01 ...
Page 36: ......
Page 90: ...5 2 Outdoor unit 03 54 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 91: ...4 CONTROL AND FUNCTIONS 2022 08 22 SR_CH04_AS073EG_01 ...
Page 94: ......
Page 129: ...5 FILED WORKING 2022 08 22 SR_CH05_AS073EG_01 ...