2-18. E: 84. Current sensor error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 84
Detective actuator
Outdoor unit
main PCB
When input current sensor has detected 0 A, while
inverter compressor is operating at higher than 50 rps,
after 1 minute upon starting the compressor. (Except
during the defrost operation)
Forecast of cause
Defective connection of electric components
External cause
Main PCB failure
Check point 1. Reset power supply and operate
Does error indication show again?
↓
Check point 2. Check connections of outdoor
unit electrical components
Upon correcting the removed connector or mis-
wiring, reset the power.
•
Check if the terminal connection is loose.
•
Check if connector is removed.
•
Check erroneous connection.
•
Check if cable is open.
↓
Check point 3. Replace the main PCB
If Check point 1, 2 do not improve the symptom,
replace the main PCB.
↓
End
Check point 1-2. Check external cause at Indoor and Outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
End
2-18. E: 84. Current sensor error (Outdoor unit)
- (03-24) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for General AOHG45KRTA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Page 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Page 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Page 36: ......
Page 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Page 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...