6-2. Model: AOHG36KMTA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
20
30
40
50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30
—
—
—
—
0.902
0.882
0.862
20
—
—
—
0.938
0.917
0.897
0.876
10
—
—
0.973
0.953
0.933
0.912
0.891
7.5
—
0.988
0.977
0.957
0.936
0.916
0.895
5
0.992
0.992
0.981
0.961
0.940
0.919
0.898
0
1.000
1.000
0.989
0.968
0.947
0.926
0.905
Indoor unit is lower than
outdoor unit *2
-5
1.000
1.000
0.989
0.968
0.947
0.926
0.905
-7.5
—
1.000
0.989
0.968
0.947
0.926
0.905
-10
—
—
0.989
0.968
0.947
0.926
0.905
-20
—
—
—
0.968
0.947
0.926
0.905
-30
—
—
—
—
0.947
0.926
0.905
HEATING
Pipe length (m)
5
7.5
10
20
30
40
50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30
—
—
—
—
0.978
0.968
0.958
20
—
—
—
0.988
0.978
0.968
0.958
10
—
—
0.998
0.988
0.978
0.968
0.958
7.5
—
1.000
0.998
0.988
0.978
0.968
0.958
5
1.000
1.000
0.998
0.988
0.978
0.968
0.958
0
1.000
1.000
0.998
0.988
0.978
0.968
0.958
Indoor unit is lower than
outdoor unit *2
-5
0.995
0.995
0.993
0.983
0.973
0.963
0.953
-7.5
—
0.993
0.991
0.981
0.971
0.961
0.951
-10
—
—
0.988
0.978
0.968
0.958
0.948
-20
—
—
—
0.968
0.958
0.949
0.939
-30
—
—
—
—
0.949
0.939
0.929
- 44 -
6-2. Model: AOHG36KMTA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG30-36KMTA
OUTDOOR UNIT
AOHG30-36KMTA