FUJITSU Storage ETERNUS LT40 S2/LT60 S2 LTO Library Installing, Starting Up and Maintaining
Copyright 2018 FUJITSU LIMITED
P3AM-5392-07ENZ0
20
Chapter 2
Installing the Tape Library
2.1
Location Requirements
Choose a location that meets the following criteria:
Table 2.1 Location criteria
Criteria
Definition
Rack requirements
Standard 19-inch rack with 2U 4U of clearance
Room temperature
10-35
C
(50-95
F
)
Power source
AC power voltage
100-127 VAC
200-240 VAC
Line frequency
50-60 Hz
Place the library near an AC outlet. The AC power cord is the product's main AC
disconnect device and must be easily accessible at all times.
Weight without media
ETERNUS LT40 S2 with two HH drives: 16.5 kg
ETERNUS LT60 S2
with four HH drives: 27 kg
Weight with media
ETERNUS LT40 S2 with 24 cartridges: 24.2 kg
ETERNUS LT60 S2 with 48 cartridges: 42.4 kg
Air quality
The library should be placed in an area with minimal sources of particulate
contamination.
Avoid areas near frequently used doors and walkways, stacks of supplies that collect
dust, printers, and smoke-filled rooms.
Excessive dust and debris can damage tapes and tape drive.
Humidity
20-80 percent RH non-condensing
Clearance
Back
Minimum of 15.4 cm (6 inches)
Front
Minimum of 30.8 cm (12 inches)-for mailslot
Minimum of 60 cm to remove magazines
Sides
Minimum of 5.08 cm (2 inches)