Chapter 5 Installation
5.2 Rack Installation
ETERNUS DX60/DX80/DX90 Disk storage system User Guide
90
Copyright 2011 FUJITSU LIMITED
P3AM-3042-08ENZ0
■
Installation conditions for other rack brands
When installing the ETERNUS DX60/DX80/DX90 in other 19-inch rack brands, make sure that
the following conditions are met.
Note that there is no guarantee that operations will perform properly when other rack brands are
used to install the ETERNUS DX60/DX80/DX90.
•
Pitch for mounting holes
EIA standard universal pitch
•
Size for mounting holes
The correct hole size for M6 screws
•
Load capacity
The maximum load capacity of the rack must be more than the weight of the ETERNUS
DX60/DX80/DX90.
•
Unit installation area
The dimensions of the area shown in
must match the conditions described in
.
Figure 5.1
Unit installation area (when installing other rack brands)
Table 5.4
Conditions of the unit installation area (when installing other rack brands)
Area
Description
Conditions
A
From the fixed part of the ETERNUS DX60/DX80/DX90
on the front side to the inner side of the front door
40mm or more
B
Space between the rack pillars on the front and back
sides (inside dimensions)
630mm to 800mm
C
From the fixed part of the ETERNUS DX60/DX80/DX90
on the back side to the inner side of the rear door
60mm or more
(recommended)
D
From the fixed part of the ETERNUS DX60/DX80/DX90
on the front side to the inner side of the rear door
830mm or more
E
Rack mount kit installation area
482mm or more
(recommended)
ETERNUS
DX60/DX80/DX90
A
B
C
D
E
Rack rear door
Rack front door
Rack pillars
Rack rails