6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Model: AOYG18KATA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
15
—
—
—
0.953
0.950
10
—
—
0.983
0.968
0.966
7.5
—
0.988
0.987
0.972
0.970
5
0.992
0.992
0.991
0.976
0.974
0
1.000
1.000
0.999
0.984
0.982
Indoor unit is lower than
outdoor unit *
2
-5
1.000
1.000
0.999
0.984
0.982
-7.5
—
1.000
0.999
0.984
0.982
-10
—
—
0.999
0.984
0.982
-15
—
—
—
0.984
0.982
HEATING
Pipe length (m)
5
7.5
10
15
20
Height difference H (m)
Indoor unit is higher than
outdoor unit *
1
15
—
—
—
0.920
0.894
10
—
—
0.982
0.920
0.894
7.5
—
1.000
0.982
0.920
0.894
5
1.000
1.000
0.982
0.920
0.894
0
1.000
1.000
0.982
0.920
0.894
Indoor unit is lower than
outdoor unit *
2
-5
0.995
0.995
0.977
0.916
0.889
-7.5
—
0.993
0.975
0.913
0.887
-10
—
—
0.972
0.911
0.885
-15
—
—
—
0.902
0.876
- 56 -
6-1. Model: AOYG18KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG18, 22KATA
OUTDOOR UNIT
AOYG18, 22KATA