2-35. E: AC. Heat sink temperature error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: AC
Detective actuator
Outdoor unit inverter PCB
Protection stop by heat sink temperature ≥ 80 °C during
heat sink operation generated 2 times within 24 hours.
Heat sink temperature thermistor
Forecast of cause
Foreign matter on heat sink, heat sink dirty
Foreign matter on heat exchanger, excessive ambient
temperature rise
Heat sink temp. thermistor defective
Check point 1. Check the heat sink state
Heat sink foreign matter, soiling check
↓
Check point 2. Check the foreign matter and ambient temperature of heat exchanger
•
Heat exchange foreign matter check
•
Ambient temperature not raised by effect of other heat sources?
•
Discharged air not sucked in?
↓
Check point 3. Check the heat sink temperature thermistor
The heat sink temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
↓
Check point 4. Replace inverter PCB
Replace inverter PCB
↓
End
2-35. E: AC. Heat sink temperature error (Outdoor unit)
- (03-44) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...