5. Thermistor resistance values
5-1. Indoor unit
¢
Room temperature thermistor
Temperature (°C)
Resistance (kΩ)
Voltage (V)
-10.0
58.25
0.73
-5.0
44.03
0.93
0.0
33.62
1.15
5.0
25.92
1.39
10.0
20.17
1.66
15.0
15.84
1.94
20.0
12.54
2.22
25.0
10.00
2.50
30.0
8.04
2.77
35.0
6.51
3.03
40.0
5.30
3.27
45.0
4.35
3.49
¢
Heat exchanger temperature thermistor
Temperature (°C)
Resistance (kΩ)
Voltage (V)
-30.0
1,013.09
0.24
-25.0
729.08
0.32
-20.0
531.55
0.43
-15.0
382.31
0.56
-10.0
312.27
0.69
-5.0
292.90
0.73
0.0
168.60
1.14
5.0
129.84
1.39
10.0
100.91
1.65
15.0
79.12
1.93
20.0
62.55
2.22
25.0
49.84
2.50
30.0
40.01
2.78
35.0
32.35
3.03
40.0
26.34
3.27
45.0
21.58
3.49
50.0
17.79
3.69
55.0
14.75
3.86
60.0
12.30
4.01
65.0
10.32
4.14
5-1. Indoor unit
- (03-62) -
5. Thermistor resistance values
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...