2-34. E: A5. Low pressure error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: A5
Detective actuator
Outdoor unit main PCB
Protection stop by suction pressure ≥ 0.02 MPaG
continued 5 minutes repeats 5 times within 24 hours.
Suction pressure sensor
Forecast of cause
3-way valve not opened
Outdoor unit ambient temperature too low
Outdoor unit operation failure, foreign matter on heat
exchanger
EEV defective, strainer clogged
Solenoid valve defective
Low pressure sensor characteristics defective
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
↓
Check point 2. Check the outdoor unit ambient temperature (Only when heating operation)
Outdoor unit ambient temperature lower than operating range?
↓
Check point 3. Check the outdoor unit fan and heat exchanger (Only when heating operation)
•
No foreign object in air passage?
•
Heat exchanger fins clogged?
•
Fan rotes?
•
Check the motor. (Refer to outdoor unit fan motor in
↓
Check point 4. Check the electronic expansion valve (EEV) and strainer
•
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check the strainer clogging.
↓
Check point 5. Check the suction pressure sensor
Check the suction pressure sensor characteristics.
NOTE:
For the characteristics of the thermistor, refer to suction pressure sensor in
↓
2-34. E: A5. Low pressure error (Outdoor unit)
- (03-42) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AUXG36KRLB
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2020 11 16 SR_CH01_AU015EF_02 ...
Page 16: ...2 2 Outdoor unit 01 10 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 17: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AU015EF_02 ...
Page 47: ...3 TROUBLESHOOTING 2020 06 04 SR_CH03_AU015EF_01 ...
Page 50: ......
Page 116: ...5 2 Outdoor unit 03 66 5 Thermistor resistance values TROUBLESHOOTING TROUBLESHOOTING ...
Page 117: ...4 CONTROL AND FUNCTIONS 2020 06 04 SR_CH04_AU015EF_01 ...
Page 120: ......
Page 157: ...5 FILED WORKING 2020 06 04 SR_CH05_AU015EF_01 ...