8-8. High temperature and high pressure release control
The compressor is controlled as follows.
¢
Models: AOYG36KQTA, AOYG45KQTA, and AOYG54KQTA
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB:
63°C
BC:
55°C
CD:
53°C
DE:
50°C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
-15 rps/120 sec.
Zone C
-2 rps/120 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-8. High temperature and high pressure release control
- (04-36) -
8. Various protections