2-3. Duct type
Model name
ARXG22KMLA
ARXG24KMLA
Power supply
3N 400 V ~50 Hz
Power supply intake
Outdoor unit
Available voltage range
342—457 V
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,100
MED
910
LOW
750
QUIET
580
Heating
HIGH
1,100
MED
910
LOW
750
QUIET
580
Type × Q'ty
Sirocco fan × 2
Motor output
W
106
Recommended static pressure
Pa
30 to 150
Sound pressure level*
1
Cooling
HIGH
dB (A)
31
MED
29
LOW
27
QUIET
25
Heating
HIGH
31
MED
29
LOW
27
QUIET
25
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 1,000 × 39.9
Fin pitch
mm
1.40
Rows × Stages
3 × 14
Pipe type
Copper
Fin type
Aluminum
Enclosure
Material
Steel sheet
Color
—
Dimensions
(H × W × D)
Net
mm
270 × 1,135 × 700
Gross
300 × 1,320 × 790
Weight
Net
kg
35
Gross
43
Connection
pipe
Size
Liquid
mm (in)
Ø 6.35 (1/4)
Gas
Ø 12.70 (1/2)
Method
Flare
Operation range
Cooling
°C
18 to 32
%RH
80 or less
Heating
°C
16 to 30
Drain port
Material
Steel
Size
mm
Ø 35.7 (I.D.), Ø 38.1 (O.D.)
Remote controller type (option)
Wired remote controller, Wireless remote controller, Mobile app*
2
(FGLair
™
)
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 35 Pa
• The protective function might work when using it outside the operation range.
• *1: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• *2: Available on Google Play
™
store or on App Store
®
. Optional WLAN adapter is also required. For details, refer to the setting manual.
2-3. Duct type
- (01-4) -
2. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION
Summary of Contents for AUXG18KVLA
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2021 05 19 SR_CH01_SM001EG_02 ...
Page 22: ...3 4 Outdoor unit 01 16 3 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Page 23: ...2 TECHNICAL DATA AND PARTS LIST 2021 06 15 SR_CH02_SM001EG_04 ...
Page 69: ...3 TROUBLESHOOTING 2021 06 15 SR_CH03_SM001EG_03 ...
Page 72: ......
Page 143: ...4 CONTROL AND FUNCTIONS 2021 05 19 SR_CH04_SM001EG_02 ...
Page 146: ......
Page 185: ...5 FILED WORKING 2021 06 15 SR_CH05_SM001EG_03 ...