Fujitsu ASYA12LGC Installation Manual Download Page 2

FINISHING

(1) Insulate between pipes.

For rear, right, and bottom piping, overlap the connection pipe insulation and indoor
unit pipe insulation and bind them with vinyl tape so that there is no gap.

For left and left rear piping, butt the connection pipe insulation and indoor unit pipe
insulation together and bind them with and vinyl tape so that there is no gap.

For left and left rear piping, wrap the area which accommodates the rear piping storage
section with cloth tape.

For left and left rear piping, bind the connection cord to the top of the pipe with vinyl
tape.

For left and left rear piping, bundle the piping and drain hose together by wrapping
them with cloth tape over within the range of which they fit into the rear piping storage
section.

(2) Temporarily fasten the connection cord along the connection pipe with vinyl tape. (Wrap

to about 1/3 the width of the tape from the bottom of the pipe with tape so that water
does not enter.)

(3) Fasten the connection pipe to the outside wall with saddles, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with sealant so that rain

water and wind cannot blow in.

(5) Fasten the drain hose to the outside wall, etc.

Fig. 16

Fig. 15

Pipe

(Saddle)

(Outside wall cap)

(Sealant)

(Outdoors)

Pipe

Drain hose

Cloth tape

Wrap with cloth tape

Left piping

Connection cord

Pipe

Drain hose

For connection from the left rear

Connection cord

Wall pipe

Connection
pipe

Check the following:

GOOD

Lifted up

Wave

End in water

Overlap the insulation

Bind the pipes together so
that there is no gap.

Connection pipe
(insulation)

Vinyl tape

Wall

Indoor unit pipe
(insullation)

Drain hose

BAD

BAD

BAD

1.

Check if the piping connections are secure.

2.

Check that the stems of 2-way valve and 3-way valve are closed
fully.

3.

Connect the gauge manifold charge hose to the charging port
of the 3-way valve (side with the projection for pushing in the
valve core).

4.

Open the low pressure side valve of the gauge manifold fully.

5.

Operate the vacuum pump and start pump down.

6.

Slowly loosen the flare nut of the 3-way valve and check if air
enters, then retighten the flare nut.
(When the flare nut is loosened the operating sound of the
vacuum pump changes and the reading of the compound
pressure gauge goes from minus to zero.)

OUTDOOR UNIT

OUTDOOR UNIT INSTALLATION

AIR PURGE

Always use a vacuum pump to purge the air.
Refrigerant for purging the air is not charged in the
outdoor unit at the factory.

Close the high pressure side valve of the gauge manifold fully and do
not operate it during the following work.

Set the unit on a strong stand such as thing made of concrete blocks
to minimize shock and vibration.

Do not set the unit directly on the ground because it will cause trou-
ble.

Connector cover removal

Remove the tapping screws.

Installing the connector cover

(1) After inserting the four hooks, then push upward.
(2) Tighten the tapping screws.

7.

Pump down the system for at least 15 minutes, then check if the
compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).

8.

At the end of pump down, close the low pressure side gauge of
the gauge manifold fully and stop the vacuum pump.

9.

Slowly loosen the valve stem of the 3-way valve. When the
compound pressure gauge reading reaches 0.1-0.2 MPa,
retighten the valve stem and disconnect the charge hose
from the 3-way valve charging port.
(If the stem of the 3-way valve is opened fully before the
charge hose is disconnected, it may be difficult to disconnect
the charge hose.)

10. Fully open the valve stems of the 2-way valve and 3-way valve

using a hexagon wrench. (After the valve stem begins to turn,
turn it with a torque of less than 2.9 N

 • 

m (30 kgf

 • 

cm) until it

stops turning.)

11. Firmly tighten the 2-way valve and 3-way valve blank cap and

the charging port cap.

Fig. 11

 

CAUTION

(1) R e f r i g e r a n t   m u s t   n o t   b e   d i s c h a r g e d   i n t o

atmosphere.

(2) After connecting the piping , check the joints for

gas leakage with gas leak detector.

OUTDOOR UNIT WIRING

(1) Remove the outdoor unit connector cover.
(2) Bend the end of the cord as shown in the figure.
(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the sheath with a cord clamp.
(5) Install the connector cover.

(1) Match the terminal block numbers and connection

cord colors with those of the indoor unit.
Erroneous wiring may cause burning of the electric
parts.

(2)

Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.

(3) Always fasten the outside covering of the connec-

tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)

(4) Securely earth the power cord plug.

(5)

Do not use the earth screw for an external connector.
Only use for interconnection between two units.

 

CAUTION

35mm

12mm

5mm

5mm

12mm

25mm

Fig. 13

Sheath

Cord clamp

Earth screw

Outdoor unit terminal block

Indoor unit terminal block

Connection cord

Earth screw

Earth screw

Table 4

Tightening torque

Blank cap

19.6 to 24.5 N

 • 

m (200 to 250 kgf

 • 

cm)

Charging port cap

12.3 to 15.7 N

 • 

m (125 to 160 kgf

 • 

cm)

TEST RUNNING

Perform test operation and check items 1 and 2 below.

For the test operation method, refer to the operating manual.

The outdoor unit, may not operate, depending on the room temperature. In this case, press the TEST RUN button on the remote control unit
while the air conditioner is running. (Point the transmitter section of the remote control unit toward the air conditioner and press the test run
button with the tip of a ball-point pen, etc.)

To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously
flash slowly.)

1. INDOOR UNIT

(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do the airflowdirection louver operate normally?
(4) Is the drain normal?

2. OUTDOOR UNIT

(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?

 

WARNING

(1) Install the unit where it will not be tilted by more

than 5°.

(2) When installing the outdoor unit where it may ex-

posed to strong wind, fasten it securely.

Connector cord

Cord clamp

Control box

Fig. 14

Connector cord

Connection cord wiring

Run the connection cord to the rear of the outdoor unit within the 

A

range of the arrows shown in the figure.
(The connector cover becomes difficult to install.)

Fig. 12

Additional charge

Refrigerant suitable for a piping length of 15 m is charged in the outdoor
unit at the factory.
When the piping is longer than 15 m, additional charging is necessary.
For the additional amount, see the table below.

Pipe length

Additional refrigerant

Table 5

15 m

None

20 m

100 g

Tapping screw

Rear hooks

Connector cover

 

CAUTION

(1) When adding refrigerant, add the refrigerant from

the charging port at the completion of work.

(2) The maximum length of the piping is 20 m. If

the units are further apart than this, correct
operation can not be guaranteed.

Between 15 m and 20 m, when using a connection pipe other than
that in the table, charge additional refrigerant with 20g/1 m as the
criteria.

Control box cover

Transmitter section

Test run button

Fig. 17

P/N 9317265003-01

L    N

3

Drain hose
Saddle

INDOOR UNIT

CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING

(1) Cut a 65 mm diameter hole in the wall at the position shown in (Fig.

5).

(2) When cutting the wall hole at the inside of the installation frame, cut

the hole within the range of the left and right center marks of the
installation frame.
When cutting the wall hole at the outside of the installation frame,
cut the hole at least 10 mm lower.

(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the

inside end.

(4) Always align the center of the wall hole. If misaligned, water leakage

will occur.

(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap,

fasten the cap with vinyl tape, and stick the pipe through the hole.
(The connection pipe is supplied in the installation set.) (Fig. 5)

(6) For left piping and right piping, cut the hole a little lower so that drain

water will flow freely. (Fig. 5)

Fig. 5

Fasten with
vinyl tape

(Wall cap)

(Wall pipe)

(Inside)

Wall

(Outside)

(1) Remove the cord clamp.
(2) Bend the end of the connection cord as shown in the figure.

(1) Match the terminal block numbers and connection

cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the elec-
tric parts.

(2)

Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.

(3) Always fasten the outside covering of the connec-

tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.)

(4) Securely earth the power cord plug.

(5)

Do not use the earth screw for an external connector.
Only use for interconnection between two units.

Fig. 10

 CAUTION

(3) Connect the end of the connection cord fully into the terminal block.
(4) Fasten the connection cord with a cord clamp.

INDOOR UNIT WIRING

Connection cord

40 m

m

12 m

m

60 m

m

12 m

m

5 m

m

5 m

m

Wire cover

Cord clamp

Screw

Connection cord

Insert the tab into the square hole of the
indoor unit and fasten with a screw.

INSTALLING THE WALL HOOK BRACKET

(1) Install the wall hook bracket so that it is correctly positioned horizon-

tally and vertically. If the wall hook bracket is tiled, water will drip to

the floor.

(2) Install the wall hook bracket so that it is strong enough to withstand

the weight of an adult.

Fasten the wall hook bracket to the wall with 6 or more screws through

the holes near the outer edge of the bracket.

Check that there is no rattle at the wall hook bracket.

FORMING THE DRAIN HOSE AND PIPE

 

WARNING

If the wall pipe is not used, the cord interconnecting
the indoor and outdoor units may touch metal and
cause electric leakage.

[Rear piping, Right piping, Bottom piping]

Install the indoor unit piping in the direction of the wall hole and bind
the drain hose and pipe together with vinyl tape. (Fig. 7)

Install the piping so that the drain hose is at the bottom.

Wrap the pipe of the indoor unit that visible from the outside with
decorative tape.

[For Left rear piping, Left piping]

Interchange the drain cap and the drain hose.

Fig. 6

Fig. 7

 

CAUTION

●  

In order to align the drain hose and drain cap, be
sure to insert securely and vertically. ncline insertion
will cause water leakage.

●  

When inserting, be sure not to attach any material
besides water. If any other material is attached, it
will cause deterioration and water leakage.

●  

After removing drain hose, be sure not to forget

mounting drain cap.

●  

Be sure to fix the drain hose with tape to the bottom

of piping.

 

CAUTION

Install the wall hook bracket horizontally and
perpendicularly.

Removal method of drain
hose

 

Remove the screw at the left of
drain hose and pull out drain
hose.

Installation method of
drain hose

 

Vertically insert the drain hose
toward the inside, so that the
drain fixture can accurately
align with the screw hole
around the drain cock.
After inserting and before
replacing, please reinstall and
fix the removed screws.

Right piping

Bind with vinyl tape

Indoor unit drain hose (bottom)

Pipe (top)
Rear piping

Bottom
piping

●   

Be sure to install around the drain hose connector.

●   

As the screw is inside, be sure to use screwdriver treated with

magnet.

Screw

Drain hose

Drain fixture

Screw hole

Drain hose

Screw

Drain cock

Drain fixture

For left piping and left rear piping, align the marks on the wall hook
bracket and shape the connection pipe.

Bend the connection piping at the bend radius of 70 mm or more and
install no more than 35 mm from the wall.

After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top and bottom of the wall
hook bracket.

[Installing the indoor unit]

Hang the indoor unit from the hooks at the top of the wall hook bracket.

Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.

Fig. 8

After hooking the indoor unit to the top hook, hook the fittings of the
indoor unit to the two bottom hooks while lowering the unit and
pushing it against the wall.

CONNECTION

(1) Install the outdoor unit wall cap (supplied with the optional installation set

or procured at the site) to the wall pipe.

(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the nut hand

tight, tighten the nut to the specified tightening torque with a torque wrench.
(Table 2)

FLARING

(1) Cut the connection pipe to the necessary

length with a pipe cutter.

(2) Hold the pipe downward so that cuttings

will not enter the pipe and remove the
burrs.

(3) Insert the flare nut onto the pipe and flare

the pipe with a flaring tool.

Insert the flare nut (always use the flare nut
attached to the indoor and outdoor units
respectively) onto the pipe and perform the
flare processing with a flare tool.
Use the special R410A  flare tool, or the conv-
entional (for R22) flare tool.
When using the conventional flare tool, always
use an allowance adjustment gauge and secure
the A dimension shown in table 3 .

CONNECTING THE PIPING

Check if [L] is flared uniformly
and is not cracked or scratched.

Fig. 9

Die

A

Pipe

Top hooks

Indoor unit

Bottom hooks

Wall hook bracket

Indoor unit

Wall hook bracket

(Spacer)

Table 2

Flare nut tightening torque

Tighten with two wrenches.

Torque
wrench

Wrench (fixed)

Flare nut

Indoor unit pipe

Connection pipe

To prevent gas leakage, coat the flare
surface with refrigerator oil.

Table 3

Pipe outside diameter

Flare nut

6.35  mm dia.

9.52  mm dia.

Tightening torque

15.7  to 17.6 N

 • 

m

(160 to 180 kgf

 • 

cm)

29.4 to 41.1 N

 • 

m

(300 to 420 kgf

 • 

cm)

A (mm)

Pipe outside

diameter

ø 6.35 mm (1/4”)

ø 9.52 mm (3/8”)

Flare tool for

R410A, clutch type

0 to 0.5

0 to 0.5

Conventional (R22) flare tool

Clutch type

1.0 to 1.5

1.0 to 1.5

Wing nut type

1.5 to 2.0

1.5 to 2.0

 

CAUTION

(1) Fasten a flare nut with a torque wrench as instructed in this manual. If

fastened too tight, the flare nut may be broken after a long period of time
and cause a leakage of refrigerant.

(2) During installation, make sure that the refrigerant pipe is attached firmly

before you run the compressor. Do not operate the compressor under the
condition of refrigerant piping not attached properly with 2-way or 3-way
valve open. This may cause abnormal pressure in the refrigeration cycle
that leads to breakage and even injury.

Installation method of Drain cap

Use a hexagonal wrench (4mm at op-
posite side) to insert the drain cap, till
the drain cap contacts the tip of drain
cock.

No gap

Hexagonal
wrench

Drain cock

Drain cap

Drain cap

Indoor unit
drain hose

Remove the drain cap by pulling
at the projection at the end of
the cap with pliers, etc.

For left outlet piping, cut off the
piping outlet cutting groove
with a hacksaw.

Center mark

at least 10 mm lower

Center mark

65 mm dia. hole

65 mm dia. hole

at least 10 mm lower

5 to 10 mm low

Wall hook bracket

Tapping screw

Connection pipe
(6.35  mm dia.)

Connection
pipe (9.52 mm dia.)

Align the marks.

Bend (R70) with
a pipe bender

Screw

Wire cover

Screw

Screw

Cord clamp

Connection

cord

Reviews: