background image

Tr

o

ub

le

 S

h

o

o

ti

n

g

These pages cover the current Inverter product range. 
They also cover the ARY60U, ARY54U Single and AOY19/24F/U Multi Systems. 

Models with Wireless Controllers Trouble Shooting from the Indoor Unit

Fujitsu Trouble Shooting Guide

Current Models

Wall Mounted Single Systems ASY, ASYA & ASYB
Includes AWYZ Nokria Models

Red Light 
Operation

Green Light 
Timer

Current Models

Off

2 Flashes

Reverse Comms Fail at Startup

Off

3 Flashes

Reverse Comms Fail In Use

Off

4 Flashes

Forward Comms Fail at Startup

Off

5 Flashes

Forward Comms Fail In Use

Off

8 Flashes

Wired Remote Control Failure

2 Flashes

2 Flashes

Indoor Air Sensor Fail

2 Flashes

3 Flashes

Indoor Pipe Sensor Fail

2 Flashes

4 Flashes

Indoor heat exchanger sensor error

2 Flashes

6 Flashes

Float switch operated

3 Flashes

2 Flashes

OD Disch Sensor Fail

3 Flashes

3 Flashes

OD Pipe Sensor Fail

3 Flashes

4 Flashes

OD Air Sensor Fail

3 Flashes

7 Flashes

Heatsink Sensor Error

3 Flashes

8 Flashes

Compressor Temp Sensor Fail

4 Flashes

2 Flashes

Forced Auto Switch Welded

4 Flashes

3 Flashes

Main Relay Welded

4 Flashes

4 Flashes

Power Failure

4 Flashes

7 Flashes

VDD Permament Stop Protection

4 Flashes

8 Flashes

Reverse VDD Permament Stop

5 Flashes

2 Flashes

IPM Protection

5 Flashes

3 Flashes

CT Abnormal

5 Flashes

5 Flashes

Compressor Failure

5 Flashes

6 Flashes

Outdoor Fan Failure

6 Flashes

2 Flashes

ID Fan Motor Locked

6 Flashes

3 Flashes

ID Fan Motor Rotation Error

7 Flashes

2 Flashes

High Discharge Temperature

7 Flashes

3 Flashes

High Pressure

7 Flashes

4 Flashes

4-Way valve abnormal

7 Flashes

5 Flashes

Pressure Switch Fail

7 Flashes

6 Flashes

Compressor Temperature error

8 Flashes

2 Flashes

Active Filter AFM Fail 1st Time

8 Flashes

3 Flashes

Active Filter AFM Fail 2nd Time

8 Flashes

4 Flashes

PFC Circuit Error

Blinking

Blinking

PCB Failure

Wall Mounted Multi Models

Initial Display

Further Interrogation by Pressing Test Button on Infra Red RC

Red

Green

Meaning

Red

Green

Meaning

2 Flashes

Blinks

ID Sensor Failure

Blinks

2 Flashes

ID Air Sensor

2 Flashes

Blinks

ID Sensor Failure

Blinks

3 Flashes

ID Pipe Sensor

4 Flashes

Blinks

ID Control Error

Blinks

2 Flashes

Manual Auto Button Error

4 Flashes

Blinks

ID Control Error

Blinks

4 Flashes

Power Source Failure

5 Flashes

Blinks

Comms Failure

Blinks

2 Flashes

Reverse Comms Failure

5 Flashes

Blinks

Comms Failure

Blinks

3 Flashes

Forward Comms Failure

6 Flashes

Blinks

ID Fan Failure

Blinks

2 Flashes

Motor locked

6 Flashes

Blinks

ID Fan Failure

Blinks

3 Flashes

Motor RPM Incorrect

Blinks

2 Flashes

OD Thermistor Fail

2 Flashes

Blinks

OD Discharge Sensor Fail

Blinks

2 Flashes

OD Thermistor Fail

4 Flashes

Blinks

OD Pipe Sensor Fail 

Blinks

2 Flashes

OD Thermistor Fail

6 Flashes

Blinks

OD Air Sensor Fail

Blinks

2 Flashes

OD Thermistor Fail

8 Flashes

Blinks

Compressor Temp Sensor Fail

Blinks

2 Flashes

OD Thermistor Fail

9 Flashes

Blinks

2 Way Valve Sensor Fail

Blinks

2 Flashes

OD Thermistor Fail

10 Flashes

Blinks

3 Way Valve Sensor Fail

Blinks

3 Flashes

Pressure Switch

2 Flashes

Blinks

Pressure Switch

Blinks

4 Flashes

ID Units Incorrect

2 Flashes

Blinks

Incorrect Indoor Unit Index

Blinks

5 Flashes

Inverter Failure

2 Flashes

Blinks

IPM Failure

Blinks

5 Flashes

Inverter Failure

5 Flashes

Blinks

Compressor Failure

All Other Wireless Indoor Units AUY, ABY & AWY 
Models. Including Multi Systems (Not J Series or VRF)

Red Light 
Operation

Green  
Light Timer

Yellow  
Light Swing

On

Normal

On

Slow Blink Slow Blink Test

Blinks

Blinks

Off

ID PCB Fail

Blinks

Blinks

Blinks

OD PCB Fail

Blinks

2 Pulses

Off

OD Power Connection Failure

Blinks

3 Pulses

Off

OD Unit Pipe Sensor Fail

Blinks

4 Pulses

Off

OD Unit Air Sensor Fail

Blinks

4 Pulses

Blinks

OD Unit Air Sensor Short

Blinks

5 Pulses

Off

OD Unit Disch Sensor Fail

Blinks

5 Pulses

Blinks

OD Unit Disch Sensor Short

Blinks

6 Pulses

Off

High Pressure

Blinks

7 Pulses

Off

High Discharge or Compressor Temp

Blinks

9 Pulses

Off

OD Unit Compressor Temp Sensor

Blinks

10 Pulses

Off

IPM Error

Blinks

11 Pulses

Off

CT Error

Blinks

12 Pulses

Off

AFM Filter Error

Blinks

13 Pulses

Off

Compressor Error

Blinks

14 Pulses

Off

OD Fan Motor Fail

2 Pulses

Blinks

Off

Air Sensor Open

2 Pulses

Blinks

Blinks

Air Sensor Closed

3 Pulses

Blinks

Off

Pipe Sensor Open

3 Pulses

Blinks

Blinks

Pipe Sensor Closed

4 Pulses

Blinks

Off

Drain Problem

5 Pulses

Blinks

Off

Communication Error

5 Pulses

Blinks

Blinks

OD PCB or Wiring Error

6 Pulses

Blinks

Off

Indoor Fan Failure

Summary of Contents for ASY7-12A

Page 1: ...s ID Control Error Blinks 2 Flashes Manual Auto Button Error 4 Flashes Blinks ID Control Error Blinks 4 Flashes Power Source Failure 5 Flashes Blinks Comms Failure Blinks 2 Flashes Reverse Comms Failure 5 Flashes Blinks Comms Failure Blinks 3 Flashes Forward Comms Failure 6 Flashes Blinks ID Fan Failure Blinks 2 Flashes Motor locked 6 Flashes Blinks ID Fan Failure Blinks 3 Flashes Motor RPM Incorr...

Page 2: ...pressor Temp Abnormal 10 Current Trip 10 Pulses Lit Compressor Temp Sensor Fail 11 CT Fail 12 Compressor Position Fail IPM Error 13 Compressor Start Fail Compressor Position Fail 14 Timer Failure Compressor Start Fail 15 OD Upper Fan Fail 16 OD Lower Fan Fail Slow Blink Protect Operation Inverter Multi AOY30 This has 4 LEDs A B C D to denote which circuit has the fault Up to 8 flashes faults are i...

Page 3: ...ed In cooling mode both pipes should be between 0 and 10 C the suction line should sweat but not freeze In heating moded both pipes should be between 30 and 60 C Pipework should be refrigeration quality Refrigerant should be R22 unless stated on the outdoor unit Look for restrictions They could cause compressor failures Indoor Unit Is it level Have we adequate drainage Smells are always due to sit...

Page 4: ...d Pulse Off F 3ph Reversal Rapid Pulse 2 Short Pulses Off C Pipe Sensor Fault Long Pulse 3 Short Pulses Off F OD Pipe Sensor Open Rapid Pulse 3 Short Pulses Off F OD Pipe Sensor Short Rapid Pulse 3 Short Pulses Rapid Pulse F OD Temp Sensor Open Rapid Pulse 4 Short Pulses Off F OD Temp Sensor Short Rapid Pulse 4 Short Pulses Rapid Pulse F Discharge Sensor Open Rapid Pulse 5 Short Pulses Off F Disch...

Reviews: