Tr
o
ub
le
S
h
o
o
ti
n
g
These pages cover the current Inverter product range.
They also cover the ARY60U, ARY54U Single and AOY19/24F/U Multi Systems.
Models with Wireless Controllers Trouble Shooting from the Indoor Unit
Fujitsu Trouble Shooting Guide
Current Models
Wall Mounted Single Systems ASY, ASYA & ASYB
Includes AWYZ Nokria Models
Red Light
Operation
Green Light
Timer
Current Models
Off
2 Flashes
Reverse Comms Fail at Startup
Off
3 Flashes
Reverse Comms Fail In Use
Off
4 Flashes
Forward Comms Fail at Startup
Off
5 Flashes
Forward Comms Fail In Use
Off
8 Flashes
Wired Remote Control Failure
2 Flashes
2 Flashes
Indoor Air Sensor Fail
2 Flashes
3 Flashes
Indoor Pipe Sensor Fail
2 Flashes
4 Flashes
Indoor heat exchanger sensor error
2 Flashes
6 Flashes
Float switch operated
3 Flashes
2 Flashes
OD Disch Sensor Fail
3 Flashes
3 Flashes
OD Pipe Sensor Fail
3 Flashes
4 Flashes
OD Air Sensor Fail
3 Flashes
7 Flashes
Heatsink Sensor Error
3 Flashes
8 Flashes
Compressor Temp Sensor Fail
4 Flashes
2 Flashes
Forced Auto Switch Welded
4 Flashes
3 Flashes
Main Relay Welded
4 Flashes
4 Flashes
Power Failure
4 Flashes
7 Flashes
VDD Permament Stop Protection
4 Flashes
8 Flashes
Reverse VDD Permament Stop
5 Flashes
2 Flashes
IPM Protection
5 Flashes
3 Flashes
CT Abnormal
5 Flashes
5 Flashes
Compressor Failure
5 Flashes
6 Flashes
Outdoor Fan Failure
6 Flashes
2 Flashes
ID Fan Motor Locked
6 Flashes
3 Flashes
ID Fan Motor Rotation Error
7 Flashes
2 Flashes
High Discharge Temperature
7 Flashes
3 Flashes
High Pressure
7 Flashes
4 Flashes
4-Way valve abnormal
7 Flashes
5 Flashes
Pressure Switch Fail
7 Flashes
6 Flashes
Compressor Temperature error
8 Flashes
2 Flashes
Active Filter AFM Fail 1st Time
8 Flashes
3 Flashes
Active Filter AFM Fail 2nd Time
8 Flashes
4 Flashes
PFC Circuit Error
Blinking
Blinking
PCB Failure
Wall Mounted Multi Models
Initial Display
Further Interrogation by Pressing Test Button on Infra Red RC
Red
Green
Meaning
Red
Green
Meaning
2 Flashes
Blinks
ID Sensor Failure
Blinks
2 Flashes
ID Air Sensor
2 Flashes
Blinks
ID Sensor Failure
Blinks
3 Flashes
ID Pipe Sensor
4 Flashes
Blinks
ID Control Error
Blinks
2 Flashes
Manual Auto Button Error
4 Flashes
Blinks
ID Control Error
Blinks
4 Flashes
Power Source Failure
5 Flashes
Blinks
Comms Failure
Blinks
2 Flashes
Reverse Comms Failure
5 Flashes
Blinks
Comms Failure
Blinks
3 Flashes
Forward Comms Failure
6 Flashes
Blinks
ID Fan Failure
Blinks
2 Flashes
Motor locked
6 Flashes
Blinks
ID Fan Failure
Blinks
3 Flashes
Motor RPM Incorrect
Blinks
2 Flashes
OD Thermistor Fail
2 Flashes
Blinks
OD Discharge Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
4 Flashes
Blinks
OD Pipe Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
6 Flashes
Blinks
OD Air Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
8 Flashes
Blinks
Compressor Temp Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
9 Flashes
Blinks
2 Way Valve Sensor Fail
Blinks
2 Flashes
OD Thermistor Fail
10 Flashes
Blinks
3 Way Valve Sensor Fail
Blinks
3 Flashes
Pressure Switch
2 Flashes
Blinks
Pressure Switch
Blinks
4 Flashes
ID Units Incorrect
2 Flashes
Blinks
Incorrect Indoor Unit Index
Blinks
5 Flashes
Inverter Failure
2 Flashes
Blinks
IPM Failure
Blinks
5 Flashes
Inverter Failure
5 Flashes
Blinks
Compressor Failure
All Other Wireless Indoor Units AUY, ABY & AWY
Models. Including Multi Systems (Not J Series or VRF)
Red Light
Operation
Green
Light Timer
Yellow
Light Swing
On
Normal
On
Slow Blink Slow Blink Test
Blinks
Blinks
Off
ID PCB Fail
Blinks
Blinks
Blinks
OD PCB Fail
Blinks
2 Pulses
Off
OD Power Connection Failure
Blinks
3 Pulses
Off
OD Unit Pipe Sensor Fail
Blinks
4 Pulses
Off
OD Unit Air Sensor Fail
Blinks
4 Pulses
Blinks
OD Unit Air Sensor Short
Blinks
5 Pulses
Off
OD Unit Disch Sensor Fail
Blinks
5 Pulses
Blinks
OD Unit Disch Sensor Short
Blinks
6 Pulses
Off
High Pressure
Blinks
7 Pulses
Off
High Discharge or Compressor Temp
Blinks
9 Pulses
Off
OD Unit Compressor Temp Sensor
Blinks
10 Pulses
Off
IPM Error
Blinks
11 Pulses
Off
CT Error
Blinks
12 Pulses
Off
AFM Filter Error
Blinks
13 Pulses
Off
Compressor Error
Blinks
14 Pulses
Off
OD Fan Motor Fail
2 Pulses
Blinks
Off
Air Sensor Open
2 Pulses
Blinks
Blinks
Air Sensor Closed
3 Pulses
Blinks
Off
Pipe Sensor Open
3 Pulses
Blinks
Blinks
Pipe Sensor Closed
4 Pulses
Blinks
Off
Drain Problem
5 Pulses
Blinks
Off
Communication Error
5 Pulses
Blinks
Blinks
OD PCB or Wiring Error
6 Pulses
Blinks
Off
Indoor Fan Failure