background image

En-14

Error display

Error code*

Description

LED1  

(green)

LED2 

(orange)

LED3 

(green)

(10)

(1)

A1

Discharge temp. error

(10)

(3)

A3

Compressor temp. error

(10)

(4)

A4

High pressure error

(10)

(5)

A5

Low pressure error

(10)

(11)

AC

Heat sink temp error

(13)

(2)

J2

Branch boxes error  
[flexible multi-split type]

Display mode 

 : 0.5s ON / 0.5s OFF

 : 0.1s ON / 0.1s OFF

( ) : Number of flashing

 

Error code on the wired remote controller (option)

Check the error

1. 

 

If an error occurs, an error icon appears on the “Monitor mode screen”.

Touch the [Status] on the “Monitor mode screen”. The “Status” screen is dis-

played.

2. 

  Touch the [Error Information] on the “Status” screen. The “Error Information” 

screen is displayed. (If there are no errors, the [Error Information] will not be 

displayed.)

3. 

  2-digit numbers correspond to the error code in the table.

Touch the [Next page] (or [Previous page]) to switch to other connected indoor 

units.

1. 

 

2. 

 

3. 

 

Set Temp.

Mode

Menu

Status

Fan

Fri 10:00AM

Unoccupied

Status

Air Flow Direction

VT

Off

1

3

Off

HZ

Economy

Individual

Anti Freeze

Page  1/  4

Monitor

Next

Page

Error

Information

02-01

14,15, 41, 44

Error Information

Page  1/ 5

Address

Error Code

Back

Next

Page

 

How to check the error memory

When an error occurs, the operation lamp (Green) and the timer lamp (Orange) indicate the 

error content by blinking. To check the error memory, follow the procedures below.
1. Stop the operation of the air conditioner, and then disconnect the power supply.

2. Reconnect the power supply.

3.  In one of the following two methods, the memorized error is only displayed during the  

“3 minutes ST”* state period.

•  Start the operation and then press hold [

] on the remote controller for 5 seconds 

or more.

or
•  Press hold [MANUAL AUTO] on the indoor unit for 10 seconds or more.

2 minutes 20 seconds

In case of “No memorized error display”,  

TEST RUN display will be shown.

[The operation lamp (Green) and the timer 

lamp (Orange) blink at the same time.]

Starting operation and then; 
- Press hold 

[

]

 on the remote controller for 5 seconds or more.

or

- Press hold [MANUAL AUTO] on the indoor unit for 10 seconds or more.

Turning on the power supply

Error memory display

*: The “3 minutes ST” period lasts 2 minutes and 20 seconds after turning on the power 

supply.

 

How to erase the error memory

   Manual erase: Pressing [MANUAL AUTO] on the indoor unit while the “Error memory 

display” is being shown. (Short beep emits for about 3 seconds.)

9387082593-01_IM.indb   14

9387082593-01_IM.indb   14

28-Oct-21   13:52:58

28-Oct-21   13:52:58

Summary of Contents for ASUH36LPAS

Page 1: ...nnect all wiring tightly Loose wiring may cause overheating at connection points and a possible fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make su...

Page 2: ... malfunction of your property 2 PRODUCT SPECIFICATION 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models some of the piping and installation and service tools are spe...

Page 3: ...be removed Correct initial installation location is important because it is difficult to move unit after it is installed WARNING Install the air conditioner in a location which can withstand a load of at least 3 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall and cause injuries Withstandable ...

Page 4: ...Top hooks 3 places Top holes 3 places Indoor unit Middle hooks 5 places Middle hooks 5 places 3 Attach the 10 screws 4 Attach the wire cover 2 screws 5 Attach the 4 caps 6 Attach the intake grille CAUTION Take caution when removing or installing the front panel If the front panel falls there is a risk of injury 3 3 Pipe installation 3 3 1 Indoor unit piping direction The piping can be connected in...

Page 5: ... the drain hose so that it is at the bottom of the piping Install the piping so that the drain hose is at the bottom Connection cable GOOD PROHIBITED Vinyl tape Connection pipe Drain hose Connection pipe Saddle Drain hose Lifted up For Left rear piping Drain hose Left piping Drain hose Left bottom piping Drain hose Interchange the drain cap and the drain hose Installing the drain cap Use a hexagon...

Page 6: ... pipe with a sharp cutter as shown on the right and bend it after exposing the pipe After bending the pipe as you want be sure to put the heat insu lating pipe back on the pipe and secure it with tape Pipe Insulating pipe Cutter Cut line Flare connection CAUTION Be sure to install the pipe against the port on the indoor unit correctly If the center ing is improper the flare nut cannot be tightened...

Page 7: ...ightened 5 Do not tighten the terminal screws too much otherwise the screws may break Screw with special washer Wire Ring terminal Terminal blocks Wire Screw with special washer Ring terminal 6 Refer to the following table for the terminal screw tightening torques Tightening torque lbf in N m M3 5 screw 7 0 to 8 8 0 8 to 1 0 M4 screw 10 6 to 15 9 1 2 to 1 8 M5 screw 17 7 to 26 5 2 0 to 3 0 To conn...

Page 8: ...oller turn off 2 Press down MODE for more than 5 seconds The current custom code will be displayed initially set to 3 Press TEMP SELECT to change the custom code between A B C D Match the custom code on the display to the air conditioner custom code 4 Press MODE again The custom code will be set The display will return to the original display To change the air conditioner custom code contact an au...

Page 9: ...ble Use crimp type insulated butt connector to join field cable and wire kit wire Connect the wire with connecting wire with solder IMPORTANT Be sure to insulate the connection between the wires Locally purchased External connect kit option Solder and insulate the connected parts 4 1 3 Installing the External input output PCB 1 Remove the Intake grille front panel and control cover Refer to 3 2 Re...

Page 10: ... code The custom code that is set through this process are applicable only to the custom in the function setting 1 Press TEMP SELECT to change the custom code between A B C D Match the code on the display to the air conditioner custom code initially set to If the custom code does not need to be selected press MODE and proceed to STEP 2 2 Press MODE to accept the custom code and proceed to STEP 2 T...

Page 11: ...tory setting Function number Setting value Setting description 61 00 Auxiliary heater control 1 01 Auxiliary heater control 2 02 Heat pump prohibition control 03 Heater selection control using outdoor temperature 1 04 Heater selection control using outdoor temperature 2 05 Auxiliary heater control by outdoor temperature 3 06 Auxiliary heat pump control 07 Auxiliary heat pump control by outdoor tem...

Page 12: ... 1 Is operation of each button on the remote control unit normal 2 Does each lamp light normally 3 Do air flow direction louvers operate normally 4 Is the drain normal 5 Do not have an abnormal noise and vibration during operation 6 Is there an error left in the error memory After installation check that the display is 00 normal For checking whether the display shows 00 refer to Service check in t...

Page 13: ...ting error 2 7 27 Primary unit secondary unit setup error simultaneous multi split type 2 9 29 Connection unit number error in wired remote controller system 3 1 31 Power supply interruption error 3 2 32 Indoor unit PCB model information error Error display Error code Description LED1 green LED2 orange LED3 green 3 3 33 Indoor unit motor electricity consumption detection error 3 5 35 Manual auto s...

Page 14: ...or Information Page 1 5 Address Error Code Back Next Page How to check the error memory When an error occurs the operation lamp Green and the timer lamp Orange indicate the error content by blinking To check the error memory follow the procedures below 1 Stop the operation of the air conditioner and then disconnect the power supply 2 Reconnect the power supply 3 In one of the following two methods...