background image

En-12

Indoor unit fan control for energy saving for cooling

 Enables or disables the power-saving function by controlling the indoor unit fan rotation 
when the outdoor unit is stopped during cooling operation.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting description 

49

00

Disable

01

Enable

02

Remote controller

00: When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for 

cooling function, or when connecting a single split converter, the setting cannot be made 

by using the remote controller. Set to “00” or “01”.

To confirm if the remote controller has this function, refer to the operating manual of each 

remote controller.

Switching functions for external output terminal

 Functions of the external output terminal can be switched. For details, refer to “External 

input and output”.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description 

60

00

Operation status

01-08

Other status  

(refer to Design & Technical 

manual)

09

Error status

10

Indoor unit fan operation status

Server room control switching

Switches between normal control and server room control.

To use this function, address setting of the primary unit and secondary unit needs to be done.

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description 

96

00

Normal control

01

Server room control (Primary 

unit)

02

Server room control (Secondary 

unit)

Setting record

Record any changes to the settings in the following table.

Setting Description

Setting Value

Filter sign

Auto restart

Room temperature sensor switching

Remote controller custom code

External input control

Room temperature sensor switching (Aux.)

Indoor unit fan control for energy saving for cooling

Switching functions for external output terminal

Server room control switching

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on 
again.

14.2. 

Temperature correction 

NOTE:

When changing Function 95, perform this setting before other Room temp. control settings 
(Function 30, 31, 92, 93).
If Function 95 is not set first, Room temperature control settings (Function 30, 31, 92, 93) 
will be reset and you must re-do them again.

Heat Insulation condition (building insulation)

Heat insulation conditions differ according to the installed environment.
“Standard insulation” (00) allows system to rapidly respond to the cooling or heating load 
changes.
“High insulation” (01) is when the heat insulation structure of the building is high and does 
not require system to rapidly respond to cooling or heating load changes.
When “High insulation” (01) is selected;
•  Overheating (overcooling) is prevented at the start-up.
•  All room temp. control settings (Function 30, 31, 92, 93) will reset to “No correction” [0.0°F 

(0.0°C)].

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

95

00

Standard insulation

01

High insulation

Room temperature control for indoor unit sensor

Depending on the installed environment, correction of the room temperature sensor may 
be required.
Select the appropriate control setting according to the installed environment.
The  temperature  correction  values  show  the  difference  from  the  “Standard  setting”  (00)
(manufacturer’s recommended value).
*  When Function 95-01(High insulation) is set, the “Standard setting” (00) will be the same 

as “No correction” (01) [0.0°F (0.0°C)].

(♦...  Factory setting)

Function Number

Setting 

Value

Setting Description

30

(For cooling)

31

(For heating)

00

Standard setting*

01

No correction 0.0°F (0.0°C)

02

-1°F (-0.5°C)

More 

Cooling 

Less 

Heating

03

-2°F (-1.0°C)

04

-3°F (-1.5°C)

05

-4°F (-2.0°C)

06

-5°F (-2.5°C)

07

-6°F (-3.0°C)

08

-7°F (-3.5°C)

09

-8°F (-4.0°C)

10

+1°F (+0.5°C)

Less 

Cooling 

More 

Heating

11

+2°F (+1.0°C)

12

+3°F (+1.5°C)

13

+4°F (+2.0°C)

14

+5°F (+2.5°C)

15

+6°F (+3.0°C)

16

+7°F (+3.5°C)

17

+8°F (+4.0°C)

Room temperature control for wired remote controller sensor

Depending on the installed environment, correction of the wire remote temperature sensor 
may be required.
Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.

(♦...  Factory setting)

Function number

Setting 

value

Setting description

35 

(For cooling)

36 

(For heating)

00

No correction 0.0°F (0.0°C)

01

No correction 0.0°F (0.0°C)

02

-1°F (-0.5°C)

More 

Cooling 

Less 

Heating

03

-2°F (-1.0°C)

04

-3°F (-1.5°C)

05

-4°F (-2.0°C)

06

-5°F (-2.5°C)

07

-6°F (-3.0°C)

08

-7°F (-3.5°C)

09

-8°F (-4.0°C)

10

+1°F (+0.5°C)

Less 

Cooling 

More 

Heating

11

+2°F (+1.0°C)

12

+3°F (+1.5°C)

13

+4°F (+2.0°C)

14

+5°F (+2.5°C)

15

+6°F (+3.0°C)

16

+7°F (+3.5°C)

17

+8°F (+4.0°C)

9387082098-02_IM.indb   12

21/03/2016   10:13:01

Summary of Contents for ASU30RLE

Page 1: ... a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulate any tubing run inside a room to prevent sweating that can cause drip ping and water damage to walls and floors In an Area with High Winds Securely anchor the outdoor unit down with bolts and a met...

Page 2: ... erroneous charging with conventional refrigerant R22 and for safety Therefore check beforehand The charging port thread diameter for R410A is 1 2 20 UNF Be more careful that foreign matter oil water etc does not enter the piping than with refrigerant R22 models Also when storing the piping securely seal the opening by pinching taping etc When charging the refrigerant take into account the slight ...

Page 3: ...nimals may urinate on the unit or ammonia may be generated Do not use the unit for special purposes such as storing food raising animals grow ing plants or preserving precision devices or art objects It can degrade the quality of the preserved or stored objects Do not install where there is the warning of combustible gas leakage Do not install the unit near a source of heat steam or flammable gas ...

Page 4: ...ck Drain cap Removal method of drain hose Remove the screw at the left of drain hose and pull out drain hose Installation method of drain hose Vertically insert the drain hose toward the inside so that the drain fixture white can ac curately align with the screw hole around the drain cock After inserting and before replacing please reinstall and fix the removed screws Please hold around the joint ...

Page 5: ...CAUTION Connect the piping so that the control box cover can easily be removed for servicing when necessary In order to prevent water from leaking into the control box make sure that the piping is well insulated When the flare nut is tightened properly by your hand hold the body side coupling with a wrench then tighten with a torque wrench See the table below for the flare nut tightening torques T...

Page 6: ...e terminal screw tightening torques Tightening torque lbf in N m M4 screw 11 to 16 1 2 to 1 8 CAUTION Attach the cable clamp firmly by holding the connection cable and make sure that the clamp is fixed securely Incomplete attachment of the cable clamp might cause a malfunction of the open panel Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wi...

Page 7: ...ation Vinyl tape Wrap with cloth tape Cloth tape Drain hose Connection cable Pipe Drain hose Drain hose Connection pipe Wall pipe Connection cable Left piping For connection from the left rear Pipe Connection pipe heat insulation Indoor unit pipe heat insulation Bind the pipes together so that there is no gap Seal A is used when the diam eter of gas pipe is Ø12 70 or more Butt connection pipe heat...

Page 8: ...tricted When function setting is Operation Stop mode 2 Input signal Command OFF ON Operation ON OFF Stop R C disabled 10 1 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25 m 82 ft Use an external input and output cable with appropriate external dimension depending on the number of cables to be installed Output voltage Hi DC12V 2V Lo 0V Permissible current 5...

Page 9: ...re to insulate the connecting parts when extending the cable Server room control For server room control connect the communication cable to the terminal block following the same procedure as the remote controller cable For details refer to the service instruction for Server room control Note Wire colors may not match Match the numbers on the terminal block of each indoor unit Tab Cable clamper and...

Page 10: ...ch indoor unit using the Function setting a 3 wire type Function setting RC AD setting Factory setting 00 When connecting multiple indoor units to 1 standard wired remote controller set the address at RC AD setting in sequence from 00 b 2 wire type Function setting RC AD setting Factory setting 00 Since the remote controller address settings are automatically configured you do not need to configur...

Page 11: ... buttons to select the setting value Press the MIN HEAT button to switch between the left and right digits 4 Press the MODE button in the order listed to confirm the settings Please confirm that the beep sounds 5 Next please press START STOP button Please confirm that the beep sounds 6 Press the RESET button to cancel the function set ting mode 7 After completing the FUNCTION SETTING be sure to tu...

Page 12: ...ot set first Room temperature control settings Function 30 31 92 93 will be reset and you must re do them again Heat Insulation condition building insulation Heat insulation conditions differ according to the installed environment Standard insulation 00 allows system to rapidly respond to the cooling or heating load changes High insulation 01 is when the heat insulation structure of the building i...

Page 13: ...g to the customer in accordance with the operating manual 1 Starting and stopping method operation switching temperature adjustment timer air flow switching and other remote controller operations 2 Air filter removal and cleaning and how to use the air louvers 3 Give the operating manual to the customer 18 ERROR CODES If you use a wireless remote controller the lamp on the photo detector unit will...

Page 14: ...sure sensor error Suction pressure sensor error High pressure switch error 9 4 Trip detection 9 5 Compressor rotor position detection error permanent stop 9 7 Outdoor unit fan motor 1 error 9 8 Outdoor unit fan motor 2 error 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes e...

Reviews: