background image

En-3

 CAUTION

9-Charging procedures

•  In addition to conventional charging procedures, the following requirements shall be 

followed.

-  Ensure that contamination of different refrigerants does not occur when using 

charging equipment.

-  Hoses or lines shall be as short as possible to minimize the amount of refrigerant 

contained in them.

-  Cylinders shall be kept upright.
-  Ensure that the refrigeration system is earthed prior to charging the system with 

refrigerant.

-  Label the system when charging is complete (if not already).
-  Extreme care shall be taken not to over

fi

 ll the refrigeration system.

•  Prior to recharging the system it shall be pressure tested with OFN. 
•  The system shall be leak tested on completion of charging but prior to commission-

ing. 

•  A follow up leak test shall be carried out prior to leaving the site.

10-Decommissioning

•  Before carrying out this procedure, it is essential that the technician is completely 

familiar with the equipment and all its details.

•  It is recommended good practice that all refrigerants are recovered safely.
•  Prior to the task being carried out, an oil and refrigerant sample shall be taken in 

case analysis is required prior to re-use of reclaimed refrigerant.

•  It is essential that electrical power is available before the task is commenced.

a)  Become familiar with the equipment and its operation.
b)  Isolate system electrically.
c)  Before attempting the procedure ensure that:

•  mechanical handling equipment is available, if required, for handling refriger-

ant cylinders;

•  all personal protective equipment is available and being used correctly; 
•  the recovery process is supervised at all times by a competent person; 
•  recovery equipment and cylinders conform to the appropriate standards.

d)  Pump down refrigerant system, if possible.
e)  If a vacuum is not possible, make a manifold so that refrigerant can be removed 

from various parts of the system.

f)   Make sure that cylinder is situated on the scales before recovery takes place.
g)  Start the recovery machine and operate in accordance with manufacturer’s 

instructions.

h)  Do not over

fi

 ll cylinders. (No more than 80 % volume liquid charge).

i)   Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)   When the cylinders have been 

fi

 lled correctly and the process completed, make 

sure that the cylinders and the equipment are removed from site promptly and all 
isolation valves on the equipment are closed off.

k)  Recovered refrigerant shall not be charged into another refrigeration system un-

less it has been cleaned and checked.

11-Labelling

•  Equipment shall be labelled stating that it has been de-commissioned and emptied 

of refrigerant. 

•  The label shall be dated and signed. 
•  Ensure that there are labels on the equipment stating the equipment contains 

fl

 am-

mable refrigerant.

12-Recovery

•  When removing refrigerant from a system, either for servicing or decommissioning, it 

is recommended good practice that all refrigerants are removed safely.

•  When transferring refrigerant into cylinders, ensure that only appropriate refrigerant 

recovery cylinders are employed.

•  Ensure that the correct number of cylinders for holding the total system charge are 

available. 

•  All cylinders to be used are designated for the recovered refrigerant and labelled for 

that refrigerant (i.e. special cylinders for the recovery of refrigerant). 

•  Cylinders shall be complete with pressure relief valve and associated shut-off valves 

in good working order.

•  Empty recovery cylinders are evacuated and, if possible, cooled before recovery 

occurs.

•  The recovery equipment shall be in good working order with a set of instructions 

concerning the equipment that is at hand and shall be suitable for the recovery of 

fl

 ammable refrigerants.

•  In addition, a set of calibrated weighing scales shall be available and in good working 

order.

•  Hoses shall be complete with leak-free disconnect couplings and in good condition.
•  Before using the recovery machine, check that it is in satisfactory working order, has 

been properly maintained and that any associated electrical components are sealed 
to prevent ignition in the event of a refrigerant release. 
Consult manufacturer if in doubt.

•  The recovered refrigerant shall be returned to the refrigerant supplier in the correct 

recovery cylinder, and the relevant Waste Transfer Note arranged. 

•  Do not mix refrigerants in recovery units and especially not in cylinders.
•  If compressors or compressor oils are to be removed, ensure that they have been 

evacuated to an acceptable level to make certain that 

fl

 ammable refrigerant does not 

remain within the lubricant. 

•  The evacuation process shall be carried out prior to returning the compressor to the 

suppliers. 

•  Only electric heating to the compressor body shall be employed to accelerate this 

process. 

•  When oil is drained from a system, it shall be carried out safely.

Explanation of symbols displayed on the indoor unit or outdoor unit.

WARNING

This symbol shows that this appliance uses a 

fl

 ammable 

refrigerant. 
If the refrigerant is leaked and exposed to an external igni-
tion source, there is a risk of 

fi

 re.

CAUTION

This symbol shows that the operation manual should be 
read carefully.

CAUTION

This symbol shows that a service personnel should be 
handling this equipment with reference to the installation 
manual.

CAUTION

This symbol shows that information is available such as 
the operating manual or installation manual.

2.  ABOUT THIS PRODUCT

2.1. Special tools for R32 (R410A)

Tool name

Change from R22 to R32 (R410A)

Gauge manifold

Pressure is high and cannot be measured with a R22 
gauge. To prevent erroneous mixing of other refrigerants, 
the diameter of each port has been changed.
It is recommended to use gauge with seals -0.1 to 5.3 MPa 
(-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure.

Charge hose

To increase pressure resistance, the hose material and base 
size were changed. (R32/R410A)

Vacuum pump

A conventional vacuum pump can be used by installing a 
vacuum pump adapter. 
(Use of a vacuum pump with a series motor is prohibited.)

Gas leakage detector

Special gas leakage detector for HFC refrigerant R410A or 
R32.

Copper pipes

It is necessary to use seamless copper pipes and it is desirable that the amount of residual 
oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or 
discolored portion (especially on the interior surface). Otherwise, the expansion value or 
capillary tube may become blocked with contaminants.
As an air conditioner using R32 (R410A) incurs pressure higher than when using R22, it is 
necessary to choose adequate materials. 

 WARNING

•  Do not use the existing (for R22) piping and 

fl

 are nuts.

If the existing materials are used, the pressure inside the refrigerant cycle will rise and 
cause failure, injury, etc. (Use the special R32/R410A materials.)

•  Use (re

fi

 ll or replace with) speci

fi

 ed refrigerant (R32) only.  Use of unspeci

fi

 ed refriger-

ant can cause product malfunction, burst, or injury.

•  Do not mix any gas or impurities except speci

fi

 ed refrigerant (R32).  In

fl

 ow of air or ap-

plication of unspeci

fi

 ed material makes the internal pressure of the refrigerant cycle too 

high, and may cause product malfunction, burst of piping, or injury.

 WARNING

•  For appropriate working of the air conditioner, install it as written in this manual.
•  To connect indoor unit and outdoor unit, use air conditioner piping and cables available 

through your local distributor. This manual describes proper connections using such 
installation set.

•  Do not turn on the power until all work has been completed.

 CAUTION

This manual describes how to install the indoor unit only. To install the outdoor unit, refer 
to the installation manual included in each product.

•  Be careful not to scratch the air conditioner when handling it.
•  After installation, explain correct operation to the customer, using the operating manual.

9333005201_IM_En_ASTG09KMCA.indd   3

9333005201_IM_En_ASTG09KMCA.indd   3

2017/1/20   11:43:03

2017/1/20   11:43:03

Summary of Contents for ASTG12CMCB

Page 1: ...ult experienced service technicians for disconnection and reinstallation of the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit Condensation dripping from the unit might get them wet and may cause damage or malfunction of your property Be careful not to scratch the air conditioner when handling it After installation explain correct operatio...

Page 2: ...onents During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servic ing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation P...

Page 3: ...hall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supp...

Page 4: ...t piping 4 ELECTRICAL REQUIREMENT The indoor unit is powered from the outdoor unit Do not power indoor unit from separate power source WARNING Standard for electrical wiring and equipment differs in each country or region Before you start electrical working confirm related regulations codes or standards Cable Conductor size mm2 Type Remarks Connection cable 1 5 Type 60245 IEC 57 3 cable Earth Grou...

Page 5: ... an electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to the floor 2 Install the wall hook bracket so that it is strong enough to support the weight of the unit Fasten the wall hook ...

Page 6: ...r water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicat...

Page 7: ...lastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the earth ground wire Improper earthing grounding work can cause electric shocks Do not use the earth ground screw for the indoor unit to the outdoor unit unless it is specified 7 ELECTRICAL WIRING CAUTION Be careful not to generate a spark as follows for using a flammable re...

Page 8: ...val 2 Remove 3 caps 3 Remove wire cover 4 Remove 7 screws Screws Wire cover Screws 6 position Caps 3 position Wire cover 5 The front panel is pulled to the front raising the upper surface and a front panel is removed Front panel 9 2 Front panel installation 1 First fit the lower part of the front panel and insert top and bottom hooks 3 top sides 2 center Indoor unit Front panel Latches 2 position ...

Page 9: ...l kit confirm whether the air conditioner receives the signal from the remote controller Do not connect the wired remote controller to the terminal for power supply When connecting the wired remote controller with the indoor unit use the connecting cable that is supplied with wired remote controller or simple remote controller Recommended cable length of wired remote controller is 10 m When you ex...

Page 10: ...nd pull off the lock at the side of the connector insertion part CAUTION Be careful not to damage the parts on the board Otherwise it will cause malfunction Connector number CN 5 Connector number CN 4 Connector number CN 10 Connector number CN 7 Symbol indicating the location printed on the board 4 Remove the wires from the three fixtures See the figure below Leave the thick green wire in fixture ...

Page 11: ... in the oval circles below Then connect the connectors in the squares to the terminals respectively Each terminal should form a pair with a connector CAUTION Ensure that the connector is properly inserted Otherwise it may result in erroneous operation Be careful not to damage the parts on the board Otherwise it will cause malfunction 4 Wired remote controller cable External connect kit cable sold ...

Page 12: ...ress the RESET button to enter the function setting mode Selecting the Function Number and Setting Value Reverse cycle model 1 Press the TEMP buttons to select the func tion number Press the 10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP ...

Page 13: ... converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the remote controller has this function refer to the operating manual of each remote controller Setting record Record any changes to the settings in the following table Setting Description Setting Value Filter sign Auto restart Room temperature sensor switching Remote controller custom code External ...

Page 14: ...peration Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 1 1 Serial communication error 1 2 Wired remote controller communication error 1 5 Check run unfinished 1 6 Peripheral unit transmission PCB connection error 1 8 External communication error 2 1 Unit number or Refrigerant circuit address setting error Simultaneous Multi 2...

Page 15: ...rror 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator green TIMER indicator orange ECONOMY indicator green Troubleshooting ...

Page 16: ......

Reviews: