4. Capacity table
Capacity tables show each of following values calculated based on the outdoor temperature and the
indoor temperature, under given Airflow Rate (AFR):
For cooling capacity:
Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP)
For heating capacity:
Total Capacity (TC) and Input Power (IP)
4-1. Cooling capacity
¢
ARXG45KHTA
AFR
m
3
/h
3,350
Indoor temperature
°CDB
18
21
23
25
27
29
32
°CWB
12
15
16
18
19
21
23
Outdoor temperature
°CDB
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
kW
kW
kW
kW
kW
kW
kW
-15
8.48
7.52
1.67
9.20
7.90
1.71
9.68
8.15
1.74
10.16
8.49
1.76
10.64
8.83
1.78
11.08
9.00
1.78
11.75
9.24
1.78
-10
8.56
7.56
1.70
9.29
7.94
1.74
9.77
8.19
1.76
10.26
8.53
1.79
10.74
8.88
1.81
11.19
9.04
1.81
11.86
9.29
1.81
0
8.73
7.63
1.75
9.47
8.02
1.79
9.96
8.27
1.82
10.46
8.62
1.84
10.95
8.96
1.87
11.41
9.13
1.87
12.09
9.38
1.87
5
8.57
7.56
1.80
9.30
7.94
1.84
9.78
8.19
1.86
10.27
8.54
1.89
10.76
8.88
1.92
11.20
9.05
1.92
11.88
9.29
1.92
10
8.42
7.49
1.84
9.13
7.87
1.88
9.61
8.12
1.91
10.08
8.46
1.94
10.56
8.80
1.96
11.00
8.96
1.96
11.66
9.21
1.96
15
8.27
7.37
1.89
8.98
7.74
1.94
9.45
7.99
1.96
9.91
8.32
1.99
10.38
8.66
2.02
10.82
8.82
2.02
11.47
9.05
2.02
20
11.05
9.41
3.54
11.99
9.88
3.62
12.61
10.20
3.67
13.24
10.62
3.72
13.86
11.05
3.78
14.44
11.25
3.78
15.31
11.56
3.78
25
10.58
9.17
3.66
11.48
9.63
3.74
12.08
9.94
3.80
12.68
10.36
3.85
13.28
10.77
3.90
13.83
10.97
3.90
14.66
11.27
3.90
30
10.11
8.94
3.78
10.97
9.39
3.86
11.54
9.68
3.92
12.12
10.09
3.98
12.69
10.49
4.03
13.22
10.69
4.03
14.01
10.98
4.03
35
9.64
8.70
3.90
10.46
9.14
3.99
11.01
9.43
4.04
11.55
9.82
4.10
12.10
10.22
4.16
12.61
10.40
4.16
13.36
10.69
4.16
40
8.22
7.68
3.51
8.92
8.06
3.59
9.38
8.32
3.64
9.85
8.67
3.70
10.32
9.02
3.75
10.75
9.18
3.75
11.39
9.43
3.75
46
6.51
6.45
3.05
7.07
6.78
3.12
7.44
6.99
3.16
7.80
7.28
3.21
8.17
7.58
3.25
8.51
7.72
3.25
9.03
7.93
3.25
¢
ARXG54KHTA
AFR
m
3
/h
3,350
Indoor temperature
°CDB
18
21
23
25
27
29
32
°CWB
12
15
16
18
19
21
23
Outdoor temperature
°CDB
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
kW
kW
kW
kW
kW
kW
kW
-15
9.58
8.34
1.89
10.39
8.76
1.93
10.94
9.04
1.96
11.48
9.42
1.99
12.02
9.80
2.02
12.52
9.98
2.02
13.28
10.25
2.02
-10
9.61
8.34
1.91
10.42
8.76
1.95
10.97
9.04
1.98
11.51
9.42
2.01
12.06
9.80
2.03
12.56
9.99
2.03
13.32
10.26
2.03
0
9.66
8.35
1.94
10.48
8.77
1.98
11.03
9.05
2.01
11.58
9.43
2.04
12.13
9.81
2.07
12.63
10.00
2.07
13.39
10.27
2.07
5
9.49
8.23
1.99
10.30
8.65
2.03
10.84
8.93
2.06
11.37
9.30
2.09
11.91
9.68
2.12
12.41
9.86
2.12
13.15
10.13
2.12
10
9.32
8.12
2.04
10.11
8.53
2.08
10.64
8.80
2.11
11.17
9.17
2.14
11.70
9.54
2.17
12.18
9.72
2.17
12.92
9.98
2.17
15
9.16
7.98
2.10
9.94
8.39
2.14
10.46
8.66
2.17
10.98
9.02
2.21
11.50
9.38
2.24
11.98
9.56
2.24
12.70
9.82
2.24
20
12.24
10.29
4.06
13.27
10.81
4.15
13.97
11.16
4.21
14.66
11.63
4.27
15.35
12.10
4.33
16.00
12.32
4.33
16.96
12.66
4.33
25
11.72
10.03
4.20
12.71
10.54
4.29
13.38
10.88
4.35
14.04
11.33
4.41
14.70
11.79
4.48
15.32
12.01
4.48
16.24
12.34
4.48
30
11.20
9.77
4.33
12.15
10.27
4.43
12.78
10.60
4.49
13.42
11.04
4.56
14.05
11.49
4.62
14.64
11.70
4.62
15.52
12.02
4.62
35
10.68
9.51
4.47
11.59
9.99
4.57
12.19
10.32
4.64
12.80
10.75
4.70
13.40
11.18
4.77
13.96
11.39
4.77
14.80
11.70
4.77
40
9.10
8.41
4.03
9.88
8.84
4.12
10.39
9.12
4.18
10.91
9.50
4.24
11.42
9.89
4.30
11.90
10.07
4.30
12.62
10.35
4.30
46
7.21
7.09
3.50
7.83
7.45
3.57
8.23
7.69
3.63
8.64
8.01
3.68
9.05
8.34
3.73
9.43
8.49
3.73
10.00
8.72
3.73
- 7 -
4-1. Cooling capacity
4. Capacity table
DUCT TYPE
ARXG45, 54KHTA
DUCT TYPE
ARXG45, 54KHTA