ASYG30, 36LMTA
1-3. Details of server room control
By activating server room control using function setting 96, this product maintains a room at constant
temperature.
Available operations
When server room control is activated by changing the setting on function setting 96, this product
maintains the room temperature constant by performing 3 types of operations automatically accord-
ing to the room temperature conditions.
While this function is activated, contents of operation is fixed as follows:
*: Set temperature correction (±4 °C) is possible by switching the setting value on function setting
30. For the setting details, refer to
“Room temperature control for indoor unit sensor”
•
Alternative operation
Controls the units operations by using the weekly timer of the primary unit.
When the weekly timer is activated and the primary unit operation is turned off, the secondary unit
starts operation simultaneously.
Also, when the weekly timer is activated and the primary unit operation is turned on, the second-
ary unit stops operation simultaneously.
•
Backup operation
Regardless of the primary-secondary relation of the unit, if an error occurred on one unit, opera-
tion start indication is issued to another unit and the unit starts backup operation.
Operation mode
Set temperature
Airflow mode
COOL
24 °C*
HIGH
On
Primary unit
Secondary unit
Off
On
Off
Off timer expired
On timer expired
On
Indoor unit A
Indoor unit B
Off
On
Off
Error occurred
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...