2) Filter sign
Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated
amount of dust in the air of the room.
If the indication is not required, select "No indication" (03).
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er’s recommended value).
Function number
Setting value
Setting description
Factory setting
11
00
Standard (400 hours)
01
Long interval (1,000 hours)
02
Short interval (200 hours)
03
No indication
♦
Function number
Setting value
Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00
Standard setting
♦
01
No correction 0.0 °C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...