- 25 -
W
A
LL
MOU
N
TED
ASYG30, 36LMTA
10. External input and output
10-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
PCB
External input
External output
Connector
Input select
Input
signal
Indoor unit
Operation/Stop
-
CN2
Dry contact
Edge
Forced stop
-
Operation status
CN3
-
-
Error status
Indoor unit fan
operation status
Set point
attainment status
External input
and output
(UTY-XCSXZ1)
Operation/Stop
-
CN313/
CN314
Dry contact/
Apply voltage
Edge/Pulse
Forced stop
Forced thermostat off
CN313
Edge
-
Operation status
CN310
-
-
Error status
CN311
Indoor unit fan
operation status
CN312
Rotary switch
SW302
CN308
SW301
CN2 (Ext. in)
CN3 (Ext. out)
CN6
(Ext. in/out PCB)
External input and output PCB
Indoor unit PCB
CN314
CN313
CN312
CN311
CN310
1
2
3
Connector
(CN2)
PCB
Connected unit
Summary of Contents for AOYG30LMTA
Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG30LMTA ASYG36LMTA ...
Page 20: ... 16 WALL MOUNTED ASYG30 36LMTA 5 Wiring diagram ...
Page 27: ... 23 WALL MOUNTED ASYG30 36LMTA 8 2 Sound level check point 0 8 m 1 m Microphone Microphone ...
Page 52: ... 48 WALL MOUNTED ASYG30 36LMTA ...
Page 53: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG30LMTA AOYG36LMTA ...
Page 59: ... 55 OUTDOOR UNIT AOYG30 36LMTA 3 Refrigerant circuit ...
Page 60: ... 56 OUTDOOR UNIT AOYG30 36LMTA 4 Wiring diagram ...