5.3. Outdoor unit wiring

(1)  Remove the outdoor unit Switch cover A, B.
(2)  Remove the outdoor unit cable clamp and Nylon clamp.
(3)  Bend the end of the cable as shown in the 

fi

 gure.

(4)  Connect the end of the connection cable fully into the terminal block.
(5)  Fasten the sheath with a cable clamp.
(6)  Fasten the sheath with a nylon clamp.
(7)  Install the Switch cover A, B.

Cable clamp

Screw

Screw

Nylon clamp

N

L

3

2

1

Outdoor unit terminal block

Indoor unit terminal block

Connection cable

Power supply cable

Earth

(Ground) 

screw

Earth

(Ground) 

screw

25mm

12mm

5mm

5mm

12mm

20mm

20mm

12mm

5mm

5mm

12mm

20mm

Connection cable

Power supply cable

Cable clamp

Earth

(Ground) 

screw

Connection cable wiring

A

Connection and 

Power supply cable
Nylon clamp

Screw

HOLE

HOLE

Run the connection cable to the 
rear of the outdoor unit  within 
the A range of the arrows shown 
in the figure.
(The switch cover becomes 
difficult to install.)

5.4. HOW TO CONNECT THE WIRE TO THE TERMINALS

(1)   Use crimp-type terminals with insulating sleeves as shown in the 

fi

 gure below to con-

nect to the terminal block.

(2)   Securely crimp the crimp-type terminals to the wires using an appropriate tool so that 

the wires do not come loose.

(3)   Use the speci

fi

 ed wires, connect them securely, and fasten them so that there is no 

stress placed on the terminals.

(4)   Use an appropriate screwdriver to tighten the terminal screws. Do not use a screw-

driver that is too small, otherwise, the screw heads may be damaged and prevent the 
screws from being properly tightened.

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.
(6)  See the table below for the terminal screw tightening torques.

Tightening torque

M3.5 screw

0.8 to 1.0 N • m ( 8 to 10 kgf • cm )

M4 screw

1.2 to 1.8 N • m (12 to 18 kgf • cm)

M5 screw

2.0 to 3.0 N • m (20 to 30 kgf • cm)

Strip 
10 mm

Crimp-type terminal

Sleeve

Wire

Wire

Screw with special washer

Terminal board

Terminal block

Screw with special washer

Crimp-type terminal

Crimp-type terminal

4. INSTALLATION DIAGRAM

10 cm or over

60 cm or over

10 cm or over

20 cm or over

25 cm or 
over

5 cm or over

INDOOR UNIT

[OUTDOOR UNIT]

•  Do not directly install it on the 

ground, otherwise it will cause 
failure.

•  To obtain better operation ef-

ficiency, when the outdoor unit 
is installed, be sure to open the 
front and left side.

Drain pipe

Outdoor unit 
bottom

Drain hose

54 cm

32 cm

 CAUTION

When the outdoor temperature is 0 

˚

C or less, do not use the accessory drain pipe 

and drain cap. If the drain pipe and drain cap are used, the drain water in the pipe may 
freeze in extreme cold weather. (Reverse cycle model only)

In the area with heavy snowfall, if the intake and outlet of outdoor unit is blocked with 
snow, it might become dif

fi

 cult to get warm and it is likely to cause of the breakdown. 

Please construct a canopy and a pedestal or place the unit on a high stand (local 
con

fi

 gured).

5. INSTALLATION 

5.1. Outdoor unit installation

  Set the unit on a strong stand such as thing made of concrete blocks to minimize shock and vibration.

  Do not set the unit directly on the ground because it will cause trouble.

 WARNING

Install the unit where it will not be tilted by more than 5°.

When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

5.2. Switch cover remove

Hook

Hooks

Hooks

Switch cover A

Switch cover B

Screw

Switch cover A, B removal

(1) Remove the three tapping screws.
(2) Push downward the Switch cover B.
(3) Push upward the Switch cover A.

Installing the Switch cover A, B

(1)  After inserting the three hooks of Switch cover A, 

then push upward, and then tighten the two tap-
ping screws.

(2)  After inserting the three hooks of Switch cover B, 

then push upward, and then tighten the one tap-
ping screw.

 

9332983012_IM.indb   3

9332983012_IM.indb   3

4/8/2013   11:22:32 AM

4/8/2013   11:22:32 AM

Summary of Contents for AOYG14LMCA

Page 1: ...vicio autorizado MANUALE DI INSTALLAZIONE UNITÀ ESTERNA A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΕΞΩΤΕΡΙΚΗ ΜΟΝΑΔΑ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO UNIDADE EXTERIOR Apenas para pessoal de assistência autorizado РУКОВОДСТВО ПО УСТАНОВКЕ ВНЕШНИЙ МОДУЛЬ Только для авторизованного обслуживающего персонала MONTAJ KILAVUZU DIŞ ÜNİTE Yalnızca...

Page 2: ...ulation and laws in use on installation place The installation must be carried out in compliance with regulations in force in the place of installation and the installation instructions of the manufacturer This unit is part of a set constituting an air conditioner It must not be installed alone or with non authorized by the manufacturer The unit must be correctly earthed grounded and the supply li...

Page 3: ... unit Install all electrical works in accordance to the national standard Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units Both indoor unit and outdoor unit Install the circuit breaker nearby the units 2 5 Additional charge Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory When the piping is longer than 15 ...

Page 4: ...o 18 kgf cm M5 screw 2 0 to 3 0 N m 20 to 30 kgf cm Strip 10 mm Crimp type terminal Sleeve Wire Wire Screw with special washer Terminal board Terminal block Screw with special washer Crimp type terminal Crimp type terminal 4 INSTALLATION DIAGRAM 10 cm or over 60 cm or over 10 cm or over 20 cm or over 25 cm or over 5 cm or over INDOOR UNIT OUTDOOR UNIT Do not directly install it on the ground other...

Page 5: ...to zero 7 Pump down the system for at least 15 minutes then check if the compound pressure gauge reads 0 1 MPa 76 cmHg 1 bar 8 At the end of pump down close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump 9 Slowly loosen the valve stem of the 3 way valve When the compound pressure gauge reading reaches 0 1 0 2 MPa retighten the valve stem and disconnect the charge ...

Reviews: