If you use a wired type remote control, error

codes will appear on the remote control display.

If you use a wireless remote control, the lamps

on the IR receiver unit will output error codes

by way of blinking patterns.

See the lamp blinking patterns and error codes

in the table. An error display is displayed only

during running.

For more details, refer to the installation

manual of the remote control.

ERROR DETECTION

: 0.5s on / 0.5s off
: 0.1s on / 0.1s off

(   ) : Number of flashing

2016.02.18

8

Error display

Wired 

remote 

controller 

Error code

Description

OPERATION 

lamp (green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(1)

(1)

Serial communication error

(1)

(2)

Wired remote controller  
communication error

(1)

(5)

(1)

(6)

Peripheral unit transmission PCB 
connection error

(1)

(8)

External communication error

(2)

(1)

Unit number or Refrigerant circuit 
address setting error  
[Simultaneous Multi]

(2)

(2)

Indoor unit capacity error

(2)

(3)

Combination error

(2)

(4)

 Connection unit number  

error (indoor secondary unit) 
[Simultaneous Multi]

 Connection unit number error 

(indoor unit or branch unit) 
[Flexible Multi]

(2)

(6)

Indoor unit address setting error

(2)

(7)

Primary unit, secondary unit setup 
error [Simultaneous Multi]

(2)

(9)

Connection unit number error in 
wired remote controller system

(3)

(1)

Power supply interruption error

(3)

(2)

Indoor unit PCB model  
information error

(3)

(3)

Indoor unit motor electricity 
consumption detection error

(3)

(5)

Manual auto switch error

(3)

(9)

Indoor unit power supply error for 
fan motor 

(3)

(10)

Indoor unit communication circuit 
(wired remote controller) error

(4)

(1)

Room temp. sensor error 

(4)

(2)

Indoor unit heat ex. middle temp. 
sensor error

(4)

(4)

Human sensor error

Error display

Wired 

remote 

controller 

Error code

Description

OPERATION 

lamp (green)

TIMER 

lamp 

(orange)

ECONOMY 

lamp 

(green)

(5)

(1)

Indoor unit fan motor error

(5)

(3)

Drain pump error

(5)

(7)

Damper error 

(5)

(15)

Indoor unit error

(6)

(1)

Outdoor unit reverse/missing 
phase and wiring error

(6)

(2)

Outdoor unit main PCB 
model information error or 
communication error

(6)

(3)

Inverter error 

(6)

(4)

(6)

(5)

Trip terminal L error

(6)

(8)

Outdoor unit rush current limiting 
resister temp. rise error

(6)

(10)

Display PCB microcomputers 
communication error

(7)

(1)

Discharge temp. sensor error

(7)

(2)

Compressor temp. sensor error

(7)

(3)

Outdoor unit Heat Ex. liquid temp. 
sensor error

(7)

(4)

Outdoor temp. sensor error

(7)

(5)

Suction Gas temp. sensor error

(7)

(6)

 2-way valve temp. sensor error

 3-way valve temp. sensor error

(7)

(7)

Heat sink temp. sensor error

(8)

(2)

 Sub-cool Heat Ex. gas inlet 

temp. sensor error

 Sub-cool Heat Ex. gas outlet 

temp. sensor error

(8)

(3)

Liquid pipe temp. sensor error

(8)

(4)

Current sensor error

(8)

(6)

 Discharge pressure sensor error

 Suction pressure sensor error

 High pressure switch error

(9)

(4)

Trip detection

(9)

(5)

Compressor rotor position 
detection error (permanent stop) 

(9)

(7)

Outdoor unit fan motor 1 error

(9)

(8)

Outdoor unit fan motor 2 error

(9)

(9)

4-way valve error

(9)

(10)

Coil (expansion valve) error

(10)

(1)

Discharge temp. error

(10)

(3)

Compressor temp. error

(10)

(4)

High pressure error

(10)

(5)

Low pressure error

(13)

(2)

Branch boxes error  
[Flexible Multi]

Summary of Contents for AOYG12LBLAAOYG14LBLA

Page 1: ...r unit Outdoor unit ARYG12LHTBP ARYG14LHTBP AOYG12LBLA AOYG14LBLA CONTENTS SPECIFICATIONS 1 DIMENSIONS 2 REFRIGERANT SYSTEM DIAGRAM 4 ERROR DETECTION 6 CIRCUIT DIAGRAM 5 PCB CIRCUIT DIAGRAM 8 PARTS INDOOR UNIT 9 PARTS OUTDOOR UNIT 13 ACCESSORIES 16 ...

Page 2: ...EFRIGERANT NOISE LEVEL 10 5 A OUTDOOR UNIT heat 48 dB Pipe length 15 m 1 150 g FULL CHARGE COMPRESSOR TYPE DISCRIMINATION WEIGHT with oil REFRIGERANT TYPE 20 m 1 250 g ADDITIONAL CHARGE MAXIMUM PIPING HEIGHT PRECHARGED DA130A1F 25NA 25 m 1 350 g 20 g m 15 m 1 000 rpm 820 rpm 740 rpm 640 rpm 0 9 L h Inverter cooling heating ARYG14LHTBP AOYG14LBLA 5 4 A 5 7 A 1 18 kW 4 30 kW 1 25 kW 4 10 kW 5 00 kW ...

Page 3: ...INDOOR UNIT ARYG12LHTBP ARYG14LHTBP unit mm 740 255 300 650 700 700 22 631 184 462 217 25 DIMENSIONS 2016 02 29 2 ...

Page 4: ...OUTDOOR UNIT AOYG12LBLA AOYG14LBLA unit mm 347 540 300 66 790 578 320 10 2016 02 18 3 ...

Page 5: ...ompressor Accumulator Heat exchanger Heat exchanger Cooling Refrigerant flow Heating Compressor thermistor Pipe thermistor Room thermistor Discharge pipe thermistor Heat exchanger thermistor Middle Heat exchanger thermistor Out Outdoor thermistor Refrigerant pipe diameter 12 Liquid 1 4 6 35 mm Gas 3 8 9 52 mm 14 Liquid 1 4 6 35 mm Gas 1 2 12 70 mm 4 ...

Page 6: ... White Black 11 10 9 8 7 6 5 4 3 2 1 1 2 1 2 12 11 10 9 8 7 6 5 4 3 2 1 12 11 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 3 2 1 4 3 2 1 4 3 2 1 3 2 1 3 2 1 4 3 2 1 4 3 2 1 1 2 3 1 2 3 1 2 3 1 2 3 3 2 1 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 5 4 3 2 1 5 4 3 2...

Page 7: ...ACK BLACK UL1007 AWG22 ORANGE UL1007 AWG22 BLUE UL1007 AWG22 BLACK UL1007 AWG22 WHITE UL1007 AWG22 RED UL1430 AWG28 x 9 SQMM 0 3 x 9 UL1430 AWG28 x 9 EMI FILTER ZCAT2132 1130 2 TURNS W300 L W301 N W302 Si F300 5A AC250V E300 TERMINAL 3 2 1 Y1 Y2 Y3 W100 Y1 Y2 Y3 1 2 TERMINAL DC FAN MOTOR FLOAT SWITCH DC DRAIN MOTOR THERMISTOR PIPE TEMP THERMISTOR ROOM TEMP M POWER SOURCE AC230V 50Hz OUTDOOR UNIT F...

Page 8: ...ive Condition Unipolar Drive 1 2 Phase Excitation Coil resistance CN40 Expansion Valve Coil DC12V DC FAN MOTOR BLUE YELLOW WHITE BLACK RED 1 2 3 4 5 6 7 FM REACTOR 17mH 14A DC Resistance 233 24m 25 EMI FILTER GTFC 25 15 12 2 TURNS EMI FILTER GTFC 25 15 12 1 TURN CN800 DC Fan Motor 1 3 4 5 6 Pin No Terminal code Vm GND Vcc Vsp FG Function of terminal Revolution pulse output Speed control voltage in...

Page 9: ... 9 Indoor unit power supply error for fan motor 3 10 Indoor unit communication circuit wired remote controller error 4 1 Room temp sensor error 4 2 Indoor unit heat ex middle temp sensor error 4 4 Human sensor error Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 5 1 Indoor unit fan motor error 5 3 Drain pump error 5 7 Damper e...

Page 10: ...ub Assy 9378450196 1 Remote Control no brand 9709335055 3 4 3 Room Thermistor 9703299278 Control box cover sub assy Hook metal 2016 02 17 PARTS INDOOR UNIT ARYG12LHTBP ARYG14LHTBP 9 2 Top panel sub assy FUJI 用のリモコンですが 欧州の在庫を減らすために FUJITSU GENERAL も ブランドロゴの無いリモコンで供給します ...

Page 11: ...9710032028 9900921019 11 Main PCB 12LHTBP 16 Terminal Remote 17 Terminal Power 9900896003 9900568009 9710016288 11 Main PCB 14LHTBP 9710016295 12 Holder 0600063023 13 Communication PCB 9710019005 2016 02 17 INDOOR UNIT ARYG12LHTBP ARYG14LHTBP 10 15 17 16 14 13 12 11 ...

Page 12: ...sy 24 Float Switch Window panel sub assy 22 Drain Pan Sub Assy 9381752034 Pipe panel sub assy 23 Drain Pump Sub Assy 9381766017 9900465070 25 Pump Assy 9900890018 26 Drain Hose 9381576005 21 Evaporator Total Assy 12 9374517428 21 Evaporator Total Assy 14 9374517411 2016 02 17 INDOOR UNIT ARYG12LHTBP ARYG14LHTBP 11 23 22 21 24 25 27 26 28 ...

Page 13: ...scription Part number 31 33 Fan Motor 31 Casing B Sub Assy 9381829002 32 Sirocco Fan Assy 9381302000 34 Casing A 9381587001 Service panel 9603514006 2016 02 17 INDOOR UNIT ARYG12LHTBP ARYG14LHTBP 12 33 32 34 ...

Page 14: ...sy 6 Switch Cover Assy Parts number Description Ref 9309230057 9900820008 9315319036 9309236059 9309237032 2 8 Fan Motor 9601725015 9 Propeller Fan 9309909014 5 Cabinet Assy 9312799404 10 Nut with Washer 9304902003 11 Drain Assy 9303029015 4 Fan Guard Cover 9378110014 Adaptor D 12 only 12 9370244007 3 11 1 2 7 6 9 4 5 10 8 12 ...

Page 15: ...r Description Ref 2016 02 18 25 Heat Sink B Main PCB Service unit 14 22 PCB Holder 23 Terminal Sealed panel Terminal bracket 24 Heat Sink A 9314090011 9709681206 9313074029 9703874031 9314410017 21 Main PCB Service unit 12 9709681190 21 25 21 22 23 24 ...

Page 16: ...3763039 31 Reactor Assy 9900641016 42 3 way Valve Assy 9970092015 34 Expansion Valve Coil 36 Thermistor Assy 9900818005 38 Solenoid 9970033018 Condenser Total Assy 37 4 way Valve Assy 2016 02 18 9315311030 40 Compressor Thermistor 9900819002 9311641018 9311381068 35 Heat Exchanger Thermistor 9900821005 9970095030 32 34 41 35 42 33 31 40 39 37 38 36 ...

Page 17: ...upler heat insulation large 1 For indoor side pipe joint gas pipe For fixing the remote control cable For fixing the remote control cable Coupler heat insulation small 1 For indoor side pipe joint liquid pipe For fixing the heat insulation Cable tie large 4 Cable tie medium 1 Cable tie small 1 Remote control WEC type 1 For air conditioner operation Remote control accessories 1 set See installation...

Page 18: ...1602G4485 ...

Reviews: