![Fujitsu AOYG07KPCA Design & Technical Manual Download Page 25](http://html.mh-extra.com/html/fujitsu/aoyg07kpca/aoyg07kpca_design-and-technical-manual_2344221025.webp)
3) Auto restart
Enables or disables automatic restart after a power interruption.
Function number
Setting value
Setting description
Factory setting
40
00
Enable
♦
01
Disable
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-
nal device.
4) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
5) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number
Setting value
Setting description
Factory setting
49
00
Disable
01
Enable
♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
- 21 -
9-1. Function settings by using remote controller
9. Function settings
WALL MOUNTED
ASYG07-12KPCA
WALL MOUNTED