8-2. External output

With using external output function, operating status of this product can be transmitted to the ex-
ternal device, and also, this product can be inter-connected with the external device.

¢

Operation status output

Air conditioner operation status signal can be output.

Circuit diagram example:

Locally purchased

Optional parts

Example: Display

Indoor unit 

control PCB

Communication kit

Connected unit

Example: Relay unit

1

2

Signal

Relay 
power supply

V

Connector

10 m*

DC 24 V

– *: Make the distance from the PCB to the connected unit within 10 m.
– Relay spec: Max. DC 24 V, 10 mA to less than 500 mA.

On

Off

Operation

Stop

Indoor unit

Output signal

Optional part:

Part name

Model name

Exterior

External connect kit

UTY-XWZXZ5

External output wire

Communication kit

UTY-TWBXF2

* For operating the external function, the wall mounted type requires the communication kit in
addition to the wire (UTY-XWZXZ5).

- 23 -

WALL MOUNTED

ASYG07-14KMTA

Summary of Contents for AOYG07KMTA

Page 1: ...AIR CONDITIONER Wall mounted type DESIGN TECHNICAL MANUAL INDOOR ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA OUTDOOR AOYG07KMTA AOYG09KMTA AOYG12KMTA AOYG14KMTA DR_AS066EF_01 2018 02 20 ...

Page 2: ...please check with our authorized dealer Trademarks FGLair is trademark of Fujitsu General Limited in the United States other countries or both Google Play is trademark of Google Inc App Store is a service mark of Apple Inc registered in the U S and other countries Copyright 2018 Fujitsu General Limited All rights reserved ...

Page 3: ...ound level check point 18 7 Safety devices 19 8 External input and output 20 8 1 External input 20 8 2 External output 23 9 Group connection 25 9 1 Precautions on creating a group connection 25 9 2 Remote controller address setting procedure for wireless remote controllers 26 10 Remote controller 27 10 1 Wireless remote controller 27 11 Function settings 29 11 1 Function settings by using remote c...

Page 4: ...ensation rate for pipe length and height difference 49 6 1 Models AOYG07KMTA and AOYG09KMTA 49 6 2 Model AOYG12KMTA 50 6 3 Model AOYG14KMTA 50 7 Additional charge calculation 51 7 1 Models AOYG07KMTA and AOYG09KMTA 51 7 2 Model AOYG12KMTA 51 7 3 Model AOYG14KMTA 51 8 Airflow 52 8 1 Model AOYG07KMTA 52 8 2 Model AOYG09KMTA 52 8 3 Model AOYG12KMTA 52 8 4 Model AOYG14KMTA 53 9 Operation noise sound p...

Page 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG07KMTA ASYG09KMTA ASYG12KMTA ASYG14KMTA ...

Page 6: ... 35 36 LOW 29 29 30 30 QUIET 20 20 20 20 Heating HIGH 41 42 42 44 MED 35 36 38 39 LOW 31 31 33 33 QUIET 22 22 22 24 Heat exchanger type Dimensions H W D mm Main1 210 670 26 6 Main2 112 670 20 Main1 210 670 26 6 Main2 112 670 20 Sub 84 670 13 3 Fin pitch Man1 1 2 Main2 1 1 Man1 1 2 Main2 1 1 Sub 1 4 Rows Stages Main1 2 10 Main2 2 7 Main1 2 10 Main2 2 7 Sub 1 4 Pipe type Copper tube Fin type Aluminu...

Page 7: ...ing kW 2 0 35 C 2 5 35 C 3 4 35 C 4 2 35 C Heating Average 2 3 10 C 2 4 10 C 2 5 10 C 4 0 10 C SEER Cooling kWh kWh 7 4 7 4 7 3 6 9 SCOP Heating Average 4 1 4 1 4 4 4 1 Annual energy consumption QCE kWh a 95 118 163 213 QHE Average 785 819 795 1 367 Sound power level Cooling HIGH dB A 54 55 55 57 Heating 56 57 58 59 3 WALL MOUNTED ASYG07 14KMTA ...

Page 8: ...ASYG07KMTA ASYG09KMTA ASYG12KMTA and ASYG14KMTA Unit mm 834 Outline of indoor unit 327 273 273 54 270 43 43 9 5 220 for pipe inlet Ø65 for pipe inlet Ø65 182 182 356 346 48 84 63 63 834 270 222 3 0 4 WALL MOUNTED ASYG07 14KMTA ...

Page 9: ...ion space for product safety Unit mm Wall hook bracket Outline of the indoor unit 50 or more 67 or more The flare connection part should be installed outdoors 40 or more 70 or more 107 or more 1 500 or more 1 800 or more 183 or more 5 WALL MOUNTED ASYG07 14KMTA ...

Page 10: ...3 Wiring diagrams 3 1 Models ASYG07KMTA ASYG09KMTA ASYG12KMTA and ASYG14KMTA 6 WALL MOUNTED ASYG07 14KMTA ...

Page 11: ... 2 54 0 53 2 94 2 60 0 52 3 09 2 66 0 52 3 16 2 74 0 52 3 39 2 78 0 51 3 61 2 88 0 51 10 2 64 2 42 0 50 2 87 2 51 0 50 3 02 2 57 0 49 3 18 2 63 0 49 3 25 2 71 0 49 3 48 2 76 0 48 3 71 2 85 0 48 15 2 58 2 43 0 50 2 81 2 52 0 49 2 96 2 58 0 49 3 11 2 65 0 49 3 18 2 72 0 49 3 41 2 77 0 48 3 63 2 86 0 47 20 2 51 2 42 0 51 2 73 2 51 0 50 2 88 2 58 0 50 3 02 2 64 0 50 3 09 2 71 0 50 3 31 2 76 0 49 3 53 ...

Page 12: ... 4 48 3 29 0 42 4 79 3 40 0 41 15 3 38 2 85 0 53 3 68 2 95 0 53 3 89 3 02 0 53 4 10 3 09 0 52 4 35 3 15 0 52 4 51 3 23 0 52 4 81 3 33 0 51 20 3 35 2 78 0 63 3 66 2 88 0 62 3 86 2 95 0 62 4 06 3 01 0 62 4 31 3 07 0 61 4 47 3 15 0 61 4 78 3 25 0 61 25 3 28 2 69 0 71 3 58 2 79 0 71 3 78 2 86 0 71 3 98 2 92 0 70 4 22 2 97 0 69 4 38 3 05 0 69 4 68 3 15 0 69 30 3 17 2 60 0 79 3 46 2 69 0 78 3 65 2 75 0 ...

Page 13: ...1 30 4 39 1 35 4 37 1 38 20 15 4 85 1 27 4 83 1 30 4 80 1 31 4 80 1 36 4 78 1 39 24 18 5 18 1 28 5 16 1 31 5 13 1 32 5 13 1 37 5 11 1 40 Model ASYG12KMTA AFR m3 h 770 Indoor temperature 16 18 20 22 24 Outdoor temperature CDB CWB TC IP TC IP TC IP TC IP TC IP kW kW kW kW kW 15 16 2 88 1 19 2 86 1 22 2 82 1 23 2 81 1 28 2 78 1 31 10 11 3 46 1 25 3 43 1 28 3 38 1 30 3 37 1 35 3 34 1 38 5 7 4 04 1 32 ...

Page 14: ...10 Top view Vertical airflow direction louver Up Horizontal airflow direction louver Left Right 2 0 2 0 1 0 1 0 0 5 0 5 Unit m s m m 3 2 1 0 1 2 3 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center m m 3 2 1 0 0 1 2 3 4 5 6 7 8 9 10 Unit m s 2 0 0 5 1 0 Side view Vertical airflow direction louver Down Horizontal airflow direction louver...

Page 15: ...n louver Up Horizontal airflow direction louver Left Right 1 0 1 0 0 5 0 5 2 0 2 0 Unit m s m m 3 2 1 0 1 2 3 0 1 2 3 4 5 6 7 8 9 10 Side view Vertical airflow direction louver Up Horizontal airflow direction louver Center 2 0 0 5 1 0 m m 3 2 1 0 0 1 2 3 4 5 6 7 8 9 10 Unit m s Side view Vertical airflow direction louver Down Horizontal airflow direction louver Center 0 5 0 5 2 0 1 0 m m 3 2 1 0 0...

Page 16: ... 181 CFM 383 MED m3 h 540 l s 150 CFM 318 LOW m3 h 430 l s 119 CFM 253 QUIET m3 h 270 l s 75 CFM 159 Heating Fan speed Airflow HIGH m3 h 720 l s 200 CFM 424 MED m3 h 580 l s 161 CFM 341 LOW m3 h 460 l s 128 CFM 271 QUIET m3 h 330 l s 92 CFM 194 12 WALL MOUNTED ASYG07 14KMTA ...

Page 17: ...FM 412 MED m3 h 560 l s 156 CFM 330 LOW m3 h 430 l s 119 CFM 253 QUIET m3 h 270 l s 75 CFM 159 Heating Fan speed Airflow HIGH m3 h 750 l s 208 CFM 441 MED m3 h 610 l s 169 CFM 359 LOW m3 h 470 l s 131 CFM 277 QUIET m3 h 330 l s 92 CFM 194 13 WALL MOUNTED ASYG07 14KMTA ...

Page 18: ...FM 412 MED m3 h 560 l s 156 CFM 330 LOW m3 h 430 l s 119 CFM 253 QUIET m3 h 270 l s 75 CFM 159 Heating Fan speed Airflow HIGH m3 h 770 l s 214 CFM 453 MED m3 h 640 l s 178 CFM 377 LOW m3 h 520 l s 144 CFM 306 QUIET m3 h 330 l s 92 CFM 194 14 WALL MOUNTED ASYG07 14KMTA ...

Page 19: ...FM 453 MED m3 h 600 l s 167 CFM 353 LOW m3 h 450 l s 125 CFM 265 QUIET m3 h 280 l s 78 CFM 165 Heating Fan speed Airflow HIGH m3 h 800 l s 222 CFM 471 MED m3 h 660 l s 183 CFM 388 LOW m3 h 520 l s 144 CFM 306 QUIET m3 h 340 l s 94 CFM 200 15 WALL MOUNTED ASYG07 14KMTA ...

Page 20: ... 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model ASYG09KMTA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 QUIET HIGH Heating Octave band sound pressure...

Page 21: ...000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Model ASYG14KMTA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 HIGH QUIET Heating Octave band sound pressure level dB 0 dB 0 0002 µbar ...

Page 22: ...6 2 Sound level check point 0 8 m 1 m Microphone Microphone NOTE Detailed shape of the actual indoor unit might be slightly different from the one illustrated above 18 WALL MOUNTED ASYG07 14KMTA ...

Page 23: ...ection Activate More than 85 C Fan motor speed down Reset 85 C or less Fan motor speed recover Type of protection Protection form Model ASYG14KMTA Circuit protection Current fuse PCB 250 V 3 15 A Fan motor protection Power IC thermal shutdown protection Activate 125 25 C Fan motor stop Reset 110 25 20 C Fan motor restart PCB Printed Circuit Board 19 WALL MOUNTED ASYG07 14KMTA ...

Page 24: ... Maximum length of cable is 150 m The wire connection should be separate from the power cable line Control input Operation Stop or Forced stop The air conditioner can be remotely operated by means of the following on site work Unit operation is started at the following contents by adding the contact input of a commercial on off switch to a connector on the external control PCB and turning it on Un...

Page 25: ...p mode Operation Stop On Off Input signal Indoor unit When function setting is Forced stop mode Remote controller On On On Input signal Indoor unit Command Remote control operation invalidity On Off Operation Stop Forced stop Normal When function setting is Operation Stop mode 2 On Input Off Operation Indoor unit Stop R C disabled Remote controller On On Off NOTE When Operation Stop mode 2 functio...

Page 26: ...erior External connect kit UTY XWZXZ5 External input wire Communication kit UTY TWBXF2 For operating the external function the wall mounted type requires the communication kit in addition to the wire UTY XWZXZ5 22 WALL MOUNTED ASYG07 14KMTA ...

Page 27: ...it control PCB Communication kit Connected unit Example Relay unit 1 2 Signal Relay power supply V Connector 10 m DC 24 V Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA On Off Operation Stop Indoor unit Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit U...

Page 28: ...ctor 10 m DC 24 V Make the distance from the PCB to the connected unit within 10 m Relay spec Max DC 24 V 10 mA to less than 500 mA On Off Error Normal Error status Output signal Optional part Part name Model name Exterior External connect kit UTY XWZXZ5 External output wire Communication kit UTY TWBXF2 For operating the external function the wall mounted type requires the communication kit in add...

Page 29: ...trolled by using one wired remote controller 9 1 Precautions on creating a group connection Take precautions on items described in this section when creating a group connection Maximum wiring length of the remote controller cable 300 m Even if the maximum wiring length of the product itself is specified as longer than 300 m the maximum length of the remote controller cable will be 300 m if the sys...

Page 30: ...unted type store the crimping terminals in side the Communication kit In the wireless remote controllers for the group connection its remote controller address can be set by its own For the details refer to following section Remote controller address setting procedure for wireless remote controllers An error is displayed immediately just turning on the power to effect the settings of the group con...

Page 31: ... TIMER button TIMER CANCEL button NOTE Functions may differ by type of the indoor unit For details refer to the operation manual Display panel Mode indicator Clock and Timer indicator LOW NOISE mode indicator Transmit indicator Temperature indicator Fan speed indicator Swing indicator To facilitate explanation the accompanying illustration has been drawn to show all possible indica tors in actual ...

Page 32: ...iew Side view 205 17 61 Size H W D mm 205 61 17 Weight g 122 without batteries Holder Unit mm 48 5 5 5 26 2 69 3 6 5 Front View Side View Bottom View Ø 3 5 Hole 150 106 8 Hole 3 5 2 R Size H W D mm 150 69 3 26 2 Weight g 27 28 WALL MOUNTED ASYG07 14KMTA ...

Page 33: ... unit Entering function setting mode While pressing the POWERFUL button and TEMP button simultaneously press the RESET button to enter the function setting mode STEP 1 Setting the remote controller custom code Use the following steps to select the custom code of the remote controller Note that the air con ditioner cannot receive a custom code if the air conditioner has not been set for the custom ...

Page 34: ...HEAT button 2 Press the POWERFUL button to proceed the setting value To re turn the function number selection press the POWERFUL button again 3 Press the TEMP buttons to select the setting value To switch between the left and right digits press the 10 C HEAT but ton 4 Press the MODE button and START STOP button in the order listed to confirm the settings 5 Press the RESET button to cancel the func...

Page 35: ...ss setting NOTE This setting is configurable only by wireless remote controller but not configurable by Polar 3 wired remote controller Multiple indoor units can be operated by using one wired remote controller Set the unit number of each indoor unit Function number Setting value Setting description Factory setting 00 00 Unit no 0 01 Unit no 1 02 Unit no 2 03 Unit no 3 04 Unit no 4 05 Unit no 5 06...

Page 36: ... the installed environment correction of the room temperature sensor may be re quired Select the appropriate control setting according to the installed environment The temperature correction values show the difference from the Standard setting 00 manufac turer s recommended value Function number Setting value Setting description Factory setting 30 For cooling 31 For heating 00 Standard setting 01 ...

Page 37: ...C 14 2 5 C 15 3 0 C 16 3 5 C 17 4 0 C 5 Auto restart Enables or disables automatic restart after a power interruption Function number Setting value Setting description Factory setting 40 00 Enable 01 Disable NOTE Auto restart is an emergency function such as for power outage etc Do not attempt to use this function in normal operation Be sure to operate the unit by remote controller or external dev...

Page 38: ...ion number Setting value Setting description Factory setting 48 00 Both 01 Wired remote controller 10 Indoor unit fan control for energy saving for cooling Enables or disables the power saving function by controlling the indoor unit fan rotation when the outdoor unit is stopped during cooling operation Function number Setting value Setting description Factory setting 49 00 Disable 01 Enable 02 Rem...

Page 39: ...to operate for the air conditioner 1 Press the START STOP button until only the clock is displayed on the remote controller display 2 Press the MODE button for at least 5 seconds to display the cur rent custom code Initially set to 3 Press the TEMP buttons to change the custom code be tween Match the code on the display to the air conditioner custom code Initially set to 4 Press the MODE button ag...

Page 40: ...14KMTA Part name Exterior Q ty Part name Exterior Q ty Operating manual 1 Cloth tape 1 Installation manual 1 Screw Large 5 Operating manual CD ROM 1 Screw Small 2 Remote controller 1 Wall hook bracket 1 Battery 2 Remote controller holder 1 36 WALL MOUNTED ASYG07 14KMTA ...

Page 41: ...mpact remote controller concentrates on the basic functions such as Start Stop fan control temperature setting and operation mode Wire type Polar 3 wire Optional communication kit is necessary for installation NOTE Available functions may differ by the remote controller For details refer to the operation manual 13 2 Others Exterior Part name Model name Summary External connect kit UTY XWZXZ5 Requi...

Page 42: ... 38 WALL MOUNTED ASYG07 14KMTA ...

Page 43: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG07KMTA AOYG09KMTA AOYG12KMTA AOYG14KMTA ...

Page 44: ...ial Steel sheet Color Beige Approximate color of Munsell 10YR 7 5 1 0 Dimensions H W D Net mm 541 663 290 542 799 290 Gross 602 804 375 602 940 375 Weight Net kg 23 25 31 Gross 26 29 35 Connection pipe Size Liquid mm in Ø 6 35 Ø 1 4 Gas Ø 9 52 Ø 3 8 Method Flare Pre charge length m 15 Max length 20 Max height difference 15 Operation range Cooling C 10 to 46 Heating 15 to 24 Drain hose Material PP ...

Page 45: ...290 16 20 42 450 Pitch of bolts for installation 330 Pitch of bolts for installation 106 37 331 Drain port Ø42 Top view Side view 663 68 19 541 20 Front view Side view Airflow 184 120 37 179 331 Bottom view Side view Bulb part Drain port Ø42 41 OUTDOOR UNIT AOYG07 14KMTA ...

Page 46: ... 37 179 399 Bottom view Side view Bulb part 580 109 799 68 290 16 33 30 19 330 542 20 Pitch of bolts for installation Pitch of bolts for installation Top view Side view Side view Front view Drain port Ø42 4 M10 hole 42 OUTDOOR UNIT AOYG07 14KMTA ...

Page 47: ...k of operating performance Single outdoor unit installation When the upper space is open Unit mm Obstacles at rear only Obstacles at rear and sides 100 or more 250 or more 100 or more 100 or more Obstacles at front Obstacles at front and rear 600 or more 600 or more 100 or more When there is an obstruction in the upper space Unit mm Obstacles at rear and above Obstacles at rear sides and above 100...

Page 48: ... arranged in a line provide the space as shown in the following example When an obstruction in the upper space When the upper space is open Unit mm Obstacles at rear only Obstacles at front only 200 or more 250 or more 1 000 or more 250 or more Obstacles at front and rear 200 or more 1 000 or more 250 or more When an obstruction in the upper space Unit mm Obstacles at rear and above 1 500 or more ...

Page 49: ...AUTION Do not install the outdoor unit in two stage where the drain water could freeze Otherwise the drainage from the upper unit may form ice and cause a malfunction of the lower unit When the outdoor temperature is 0 C or less do not use the accessory drain pipe and drain cap If the drain pipe and drain cap are used the drain water in the pipe may freeze in ex tremely cold climate For reverse cy...

Page 50: ...ansion valve Heat exchanger Heat exchanger INDOOR OUTDOOR Compressor Cooling Heating ThD ThR ThPI ThO ThHO Thermistor Discharge temperature Thermistor Outdoor temperature Thermistor Heat exchanger out temperature ThD ThO ThHO Thermistor Room temperature Thermistor Pipe temperature ThR ThPI Muffler 46 OUTDOOR UNIT AOYG07 14KMTA ...

Page 51: ...changer Heat exchanger INDOOR OUTDOOR Compressor Cooling Heating ThD ThR ThPI ThO ThHO Thermistor Discharge temperature Thermistor Outdoor temperature Thermistor Heat exchanger out temperature ThD ThO ThHO Thermistor Room temperature Thermistor Pipe temperature ThR ThPI Muffler 47 OUTDOOR UNIT AOYG07 14KMTA ...

Page 52: ...5 Wiring diagrams 5 1 Models AOYG07KMTA AOYG09KMTA AOYG12KMTA and AOYG14KMTA 48 OUTDOOR UNIT AOYG07 14KMTA ...

Page 53: ... unit 1 15 0 872 0 910 10 0 961 0 886 0 925 7 5 0 979 0 965 0 890 0 929 5 0 992 0 983 0 969 0 893 0 933 0 1 000 0 991 0 976 0 901 0 940 Indoor unit is lower than outdoor unit 2 5 1 000 0 991 0 976 0 901 0 940 7 5 0 991 0 976 0 901 0 940 10 0 976 0 901 0 940 15 0 901 0 940 HEATING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 832 0 822 10 0 917 0 ...

Page 54: ...989 0 963 0 891 0 875 7 5 0 987 0 961 0 889 0 873 10 0 959 0 887 0 871 15 0 878 0 862 6 3 Model AOYG14KMTA NOTE Values mentioned in the table are calculated based on the maximum capacity COOLING Pipe length m 5 7 5 10 15 20 Height difference H m Indoor unit is higher than outdoor unit 1 15 0 893 0 909 10 0 955 0 908 0 924 7 5 0 975 0 959 0 912 0 928 5 0 992 0 979 0 963 0 916 0 931 0 1 000 0 987 0 ...

Page 55: ...0 g m Additional charge g 0 100 7 2 Model AOYG12KMTA Refrigerant type R32 Refrigerant amount g 700 Refrigerant charge Total pipe length m 15 or less 20 Max 20 g m Additional charge g 0 100 7 3 Model AOYG14KMTA Refrigerant type R32 Refrigerant amount g 850 Refrigerant charge Total pipe length m 15 or less 20 Max 20 g m Additional charge g 0 100 51 OUTDOOR UNIT AOYG07 14KMTA ...

Page 56: ...8 CFM 971 Heating m3 h 1 450 l s 403 CFM 853 8 2 Model AOYG09KMTA Cooling m3 h 1 650 l s 458 CFM 971 Heating m3 h 1 450 l s 403 CFM 853 8 3 Model AOYG12KMTA Cooling m3 h 1 700 l s 472 CFM 1 001 Heating m3 h 1 470 l s 408 CFM 865 52 OUTDOOR UNIT AOYG07 14KMTA ...

Page 57: ...8 4 Model AOYG14KMTA Cooling m3 h 1 680 l s 467 CFM 989 Heating m3 h 1 580 l s 439 CFM 930 53 OUTDOOR UNIT AOYG07 14KMTA ...

Page 58: ... 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model AOYG09KMTA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating Octave band sound pressure level dB 0...

Page 59: ...00 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Model AOYG14KMTA Cooling Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band center frequency Hz 80 70 60 50 40 30 20 10 0 63 125 250 500 1 000 2 000 4 000 8 000 NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30 NC 25 NC 20 NC 15 Heating Octave band sound pressure level dB 0 dB 0 0002 µbar Octave band...

Page 60: ...evel check point 1 m Microphone Microphone Rear Airflow Rear view Side view NOTE Detailed shape of the actual outdoor unit might be slightly different from the one illustrat ed above 56 OUTDOOR UNIT AOYG07 14KMTA ...

Page 61: ...al area mm2 1 5 Limited wiring length m 21 1 Maximum operating current is the total current of the indoor unit and the outdoor unit 2 Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005 As the regulations of wire size and circuit breaker differ in each country or region select appropri ate devices complied to the regional standard 3 Limit voltage drop to less than 2...

Page 62: ...program Discharge temp Activate 110 C Compressor stop Reset After 7 minutes Compressor restart Type of protection Protection form Model AOYG12KMTA AOYG14KMTA Circuit protection Current fuse Main PCB 250 V 20 A 250 V 5 A Fan motor protection Terminal protection program Activate 85 122 C Fan motor stop Reset 77 114 C Fan motor restart Compressor protection Terminal protection program Discharge temp ...

Page 63: ...12 Accessories 12 1 Models AOYG07KMTA AOYG09KMTA AOYG12KMTA and AOYG14KMTA Part name Exterior Q ty Part name Exterior Q ty Installation manual 1 Drain pipe 1 59 OUTDOOR UNIT AOYG07 14KMTA ...