Mode
Function
setting
Rotary
SW
External output
Indoor unit
External input and output PCB
CN47
1
CN310
2
CN311
3
CN312
0-1
60-00
1
Operation/Stop
Operation/Stop
Error status
Indoor unit fan
operation status
0-2
60-00
2
Operation/Stop
Error status
Indoor unit fan
operation status
External heater
output
1
60-01
3
Cooling
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
2
60-02
4
Cooling
thermostat On
Error status
Remote
controller output
External heater
output
3
60-03
5
Cooling
thermostat On
Cooling high/low
output
Remote
controller output
External heater
output
4
60-04
6
Cooling
thermostat On
Error status
Remote
controller output
Cooling high/low
output
5
60-05
7
Heating
thermostat On
Error status
Indoor unit fan
operation status
External heater
output
6
60-06
8
Operation/Stop
Error status
Indoor unit fan
operation status
Heating
thermostat On
7
60-07
9
Cooling
thermostat On
Error status
Heating
thermostat On
External heater
output
8
60-08
A
Cooling
thermostat On
Heating
thermostat On
Remote
controller output
External heater
output
9
60-09
B
Error status
Operation/Stop
Indoor unit fan
operation status
External heater
output
10
60-10
C
Indoor unit fan
operation status Operation/Stop
Error status
External heater
output
11
60-11
D
External heater
output
Operation/Stop
Indoor unit fan
operation status
Error status
12
60-12
D
Set point
attainment status Operation/Stop
Indoor unit fan
operation status
Error status
¢
Input signal type
External input and output PCB:
The input signal type can be selected.
Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and out-
put PCB.
Pulse
The width of pulse must be
longer than 200 msec.
Edge
- 25 -
8-3. Combination of external input and output
8. External input and output
W
A
LL
MO
U
N
TED
A
SU
H
18
-2
4L
MA
S
W
A
LL
MO
U
N
TED
A
SU
H
18
-2
4L
MA
S