11) Control switching of external heaters
Sets the control method for external heater to be used.
For details, refer to
Function
number
Setting value
Setting description
Factory
setting
61
00
Auxiliary heater control 1
♦
01
Auxiliary heater control 2
02
Heat pump prohibition control
03
Auxiliary heater control by outdoor temperature 1
04
Auxiliary heater control by outdoor temperature 2
12) Operating temperature switching of external heaters
Sets the temperature conditions when the external heater is ON.
For details, refer to
Function
number
Setting value
Setting description
Factory
setting
Heater: On
Heater: Off
62
00
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
♦
01
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
02
-3.6 °F (-2 °C)
-1.8 °F (-1 °C)
03
-5.4 °F (-3 °C)
-1.8 °F (-1 °C)
04
-7.2 °F (-4 °C)
-1.8 °F (-1 °C)
05
-9.0 °F (-5 °C)
-1.8 °F (-1 °C)
13) Outdoor temperature zone boundary temperature A
Setting required if changing of the outdoor temperature setting for heat pump prohibition zone is re-
quired when auxiliary heater control by outdoor temperature 1 and 2 are performed on the indoor
unit. For details, refer to
Function number
Setting value
Setting description
Factory setting
66
00
-4.0 °F (-20 °C)
♦
01
-0.4 °F (-18 °C)
02
3.2 °F (-16 °C)
03
6.8 °F (-14 °C)
04
10.4 °F (-12 °C)
05
14.0°F (-10 °C)
06
17.6 °F (-8 °C)
07
21.2 °F (-6 °C)
08
24.8 °F (-4 °C)
- 46 -