2-14. E: 74. Outdoor temperature thermistor error (Outdoor unit)
Indicator
Indoor unit
Operation indicator
7 time flash
Timer indicator
4 time flash
Economy indicator
Continuous flash
Error code
E: 74
Detective actuator
Outdoor unit main PCB
When outdoor temperature thermistor open or short
circuit is detected at power on or while running the
compressor
Outdoor temperature thermistor
Forecast of cause
Connector failure
Thermistor failure
Main PCB failure
Check point 1. Check connection of connector
•
Check if connector is loose or removed.
•
Check erroneous connection.
•
Check if thermistor cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
↓
Check point 2. Remove connector and check thermistor resistance value
•
For the outdoor temperature thermistor resistance value, refer to
•
If thermistor is either open or shorted, replace it and reset the power.
↓
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE:
For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-14.
If the voltage does not appear, replace main PCB.
↓
End
2-14. E: 74. Outdoor temperature thermistor error (Outdoor unit)
- (03-17) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUG09LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Page 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Page 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...