2-4. E: 18. External communication error (Indoor unit)
Indicator
Indoor unit
Operation indicator
1 time flash
Timer indicator
8 time flash
Economy indicator
Continuous flash
Error code
E: 18
Detective actuator
Indoor unit
External
communication
error
After receiving a signal from the external input and
output PCB, the same signal has not been received for
15 seconds.
Forecast of cause
Connection failure
External input and output PCB failure
Main PCB
Check point 1. Check the connection
•
Check any loose or removed connection betw een the main PCB to the external input and out-
put PCB.
-> If there is an abnormal condition, correct it by refer to the installation manual or the “DESIGN
& TECHNICAL MANUAL”.
•
Check the connection condition on the external input and output PCB and the main PCB (If
there is loose connector, open cable or mis-wiring.)
↓
Check point 2. Replace the external input and output PCB
If check point 1 do not improve the symptom, change external input and output PCB
↓
Check point 3. Replace main PCB
If check point 2 do not improve the symptom, change main PCB
↓
End
2-4. E: 18. External communication error (Indoor unit)
- (03-7) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Summary of Contents for AOUG09LMAS1
Page 4: ......
Page 5: ...1 GENERAL INFORMATION 2019 12 20 SR_CH01_AS023EF_01 ...
Page 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 01 28 SR_CH02_AS023EF_01 ...
Page 33: ...3 TROUBLESHOOTING 2020 01 30 SR_CH03_AS023EF_02 ...
Page 77: ...4 CONTROL AND FUNCTIONS 2020 03 25 SR_CH04_AS023EF_02 ...
Page 107: ...5 FILED WORKING 2020 02 03 SR_CH05_AS023EF_01 ...