background image

OUTDOOR UNIT

 WARNING

Install  the  unit  where  it  will  not  be  tilted  by  more  than  3°.  However,  do  not  install  the  unit  with  it  tilted  to-
wards the side containing the compressor.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.

(1)  Outdoor  unit  to  be  fasten  with  bolts  at  the  four  places 

indicated by the arrows without fail.

(2)  Fix  securely  with 

b o l t s  o n  a  s o l i d 
block. (Use 4 sets of 
commercially  avail-
able  M10  bolt,  nut 
and washer.)

 CAUTION

Do not use the drain pipe and drain cap. If the drain pipe and drain 
cap  are  used,  the  drain  water  in  the  pipe  may  freeze  in  extremely 
cold weather.

Bolt

Nut 

Block

PUMP DOWN OPERATION (FORCED COOLING OPERATION)

To avoid discharging refrigerant into the atmosphere at the time of relocation or disposal, recover refrigerant by doing the cooling operation 

or forced cooling operation according to the following procedure. (When the cooling operation cannot start in winter, and so on, start the 

forced cooling operation.)
(1)  Do the air purging of the charge hose by connecting the charging hose of gauge manifold to the charging port of 3-way valve (large) and 

opening the low-pressure valve slightly.

(2)  Close the valve stem of 3-way valve (small) completely.

(3)  Start the cooling operation or following forced cooling operation.

 

When using the remote controller

 

Press the TEST RUN button after starting the cooling operation by the remote controller.

 

The operation indicator lamp and timer indicator lamp will begin to flash simultaneously during test run.

 

When using the MANUAL AUTO button of the indoor unit (The remote controller is lost, and so on.)

 

Keep on pressing the MANUAL AUTO button of the indoor unit for more than 10 seconds. 

 

(The forced cooling operation cannot start if the MANUAL AUTO button is not kept on pressing for more than 10 seconds.)

(4)  Close the valve stem of 3-way valve (large) when the reading on the compound pressure gauge becomes 0.05~0 MPa (0.5~0 kg/cm

2

).

(5)  Stop the operation.

 

• Press the START/STOP button of the remote controller to stop the operation.

 

• Press the MANUAL AUTO button when stopping the operation from indoor unit side.

 

  (It is not necessary to press on keeping for more than 10 seconds.)

CAUTION

Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.

Use heat insulation with heat resistance above  248 °F (120 °C). (Reverse cycle model only)

In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat 

insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 9/16” (15 mm) or 

thicker and if the expected humidity exceeds 80%, use heat insulation that is 13/16” (20 mm) or thicker.

If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.

In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less [at 68 °F (20 °C)].

CAUTION

During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping.

Do not remove the connection pipe while the compressor is in operation 3-way valve open. This may cause abnormal pres-

sure in the refrigeration cycle that leads to breakage and even injury.

Bottom side

Drain port

Drain port

25-9/16” 

(650 mm)

4-ø 12 hole

14-9/1

6” 

(370 mm)

ELECTRICAL WIRING (OUTDOOR UNIT)

(1)  Service cover removal

•  Remove the two mounting screws.
•  Remove the service cover by pushing downwards.

(2)  Fasten the power supply cord and the connection cord to the 

conduit holder using the lock nut. 

 

(open the knock out holes if necessary)

(3)  Connect  the  power  supply  cord  and  the  connection  cord  to 

terminal.

(4)  Fasten the power supply cord and connection cord with cord 

clamp.

1-3/1

6” (30 mm)

Keep the earth wire longer than the other wires.

 CAUTION

Be  sure  to  comply  with  local  codes  while  running  the 
wire  from  the  indoor  unit  to  the  outdoor  unit  (size  of 
wire and wiring method, etc.).

Every wire must be connected firmly.

No  wire  should  be  allowed  to  touch  refrigerant  tubing, 
the compressor or any moving part.

Loose  wiring  may  cause  the  terminal  to  overheat  or 
result  in  unit  malfunction. A  fire  hazard  may  also  exist. 
Therefore, be sure all wiring is tightly connected.

Connect wires to the matching numbers of terminals.

1
2
3

1
2
3

G

G

L1
L2

INDOOR

INDOOR UNIT

OUTDOOR UNIT

TERMINAL

DISCON-
NECT 
SWITCH
(FIELD 
SUPPLY)

Grounding
line

14AWG
(Inter-unit)
Power lines

230/208 V
230/208 V

230/208 V

TERMINAL

Power supply line

Single-phase, 230/208 

V

G

G

G

G

Control box

Terminal

Power supply cord

Connection cord 

(indoor unit and 

outdoor unit  

connection cord)

Cord clamp

 

 CAUTION

When connecting the power supply cord, make sure that 
the phase of the power supply matches with the phase of  
the  terminal  board.  If  the  phases  do  not  match,  the  
compressor will rotate in reverse and will not be able to  
compress.

 WARNING

Disconnect  switch  for  over  current  protection  given  in 
the  table  below  is  to  be  installed  between  the  indoor 
unit and the outdoor unit.

Disconnect switch

20A

Lock 
nut

Inter-unit line

Power supply

Hook
(3 places)

Direction of  
the service  
panel removal

Service cover

Power supply 
cord or connec-
tion cord

 Earth wire

1-9

/16

” (

40 

mm

or more

Power supply line

G

1

2

3

4

1

2

3 L1  L2

G

G

Earth screw

Earth screw

Earth screw

Disconnect switch

Indoor unit
terminal block

Outdoor unit
terminal block

NOTE:

Factory  installed  protective  inline  fuses  for  indoor  units’  conductors 
are installed on the Power Supply PCB.

Valve cover removal.
•  Remove the one mounting screw.
•  Remove the valve cover by sliding upward.

Valve cover

Hook (4 places)

 

 WARNING

Use ring terminals and tighten the terminal screws to the specified torques, otherwise, abnormal overheating 
may be produced and possibly cause heavy damage inside the unit.
Match the terminal block numbers and connection cord colors with those of the outdoor unit. Erroneous wir-
ing may cause burning of the electric parts.
Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.
Always  fasten  the  outside  covering  of  the  connection  cord  with  the  cord  clamp.  (If  the  insulator  is  chafed, 
electric leakage may occur.)
Securely earth the power cord plug.
Do not use the earth screw for an external connector. Only use for interconnection between two units.

(1)  Use  ring  terminals  with  insulating  sleeves  as  shown  in  the 

figure below to connect to the terminal block.

(2)  Securely  clamp  the  ring  terminals  to  the  wires  using  an 

appropriate tool so that the wires do not come loose.

(3)  Use  the  specified  wires,  connect  them  securely,  and  fasten 

them so that there is no stress placed on the terminals.

(4)  Use an appropriate screwdriver to tighten the terminal screws.
 

Do not use a screwdriver that is too small, otherwise, the screw 
heads  may  be  damaged  and  prevent  the  screws  from  being 
properly tightened.

(5)  Do  not  tighten  the  terminal  screws  too  much,  otherwise,  the 

screws may break.

(6)  See the table below for the terminal screw tightening torques.

HOW TO CONNECT THE WIRE TO THE TERMINALS

1. CONNECTION PIPES 

Outdoor unit

(1)  Detach the caps and plugs from the pipes.
(2)  Centering  the  pipe  against  port  on  the  outdoor  unit,  turn  the 

flare nut with your hand.

2. VACUUM 

(1)  Remove the cap, and connect the gauge manifold and the vacuum pump to the charging valve by the service hoses.
(2)  Vacuum the indoor unit and the connecting pipes until the pressure gauge indicates -0.1 MPa (-76 cmHg).
(3)  When -0.1 MPa (-76 cmHg) is reached, operate the vacuum pump for at least 60 minutes.
(4)  Disconnect the service hoses and fit the cap to the charging valve to the specified torque.
(5)  Remove the blank caps, and fully open the spindles of the 2-way and 3-way valves with a hexagon wrench [Torque: 6~7 N·m (60 to 70 

kgf·cm)].

(6)  Tighten the blank caps of the 2-way valve and 3-way valve to the specified torque.

3. ADDITIONAL CHARGE

Refrigerant suitable for a piping length of 66ft(20m) is 
charged in the outdoor unit at the factory.
When the piping is longer than 66ft(20m), additional 
charging is necessary.
For the additional amount, see the table below.

4. GAS LEAKAGE INSPECTION

Tightening torque

M4 screw

1.2 to 1.8 N·m (12 to 18 kgf·cm)

M5 screw

2.0 to 3.0 N·m (20 to 30 kgf·cm)

Ring terminal

Strip
3/8” (10 mm)

Sleeve

Ring terminal

Wire

Screw with special washer

Screw with special washer

Ring terminal

Terminal block

Wire

Terminal board

(3) Tighten the flare nut of the connection pipe at the outdoor unit 

valve connector.

(4)  When the flare nut is tightened properly by your hand, use a 

torque wrench to finally tighten it.

Tightening torque

Blank  

cap

3/8” (9.52 mm)

20 to 25 N·m (200 to 250 kgf·cm)

5/8” (15.88 mm)

30 to 35 N·m (300 to 350 kgf·cm)

Charging port cap

12.5 to 16 N·m (125 to 160 kgf·cm)

CONNECTING THE PIPE

OUTDOOR UNIT INSTALLATION

 CAUTION

Do not purge the air with refrigerants, but use a vacuum pump to vacuum the installation! 
There is no extra refrigerant in the outdoor unit for air purging!
Use a vacuum pump and gauge manifold and charging hose for R410A exclusively.
Using the same vacuum for different refrigerants may damage the vacuum pump or the unit.

 CAUTION

When moving and installing the air conditioner, do not mix gas other than the specified refrigerant R410A in-
side the refrigerant cycle.

When  charging  the  refrigerant  R410A,  always  use  an  electronic  balance  for  refrigerant  charging  (to  measure 
the refrigerant by weight).

When charging the refrigerant, take into account the slight change in the composition of 
the gas and liquid phases, and always charge from the liquid phase side whose composi-
tion is stable.

Add refrigerant from the charging valve after the completion of the work.

If the units are further apart than the maximum pipe length, correct operation cannot be guaranteed.

 CAUTION

After connecting the piping, check the all joints for gas leakage with gas leak detector.
When inspecting gas leakage, always use the vacuum pump for pressure. Do not use nitrogen gas.

Piping length

66ft

(20m)

99ft

(30m)

131ft

(40m)

165ft

(50m)

Rate

Additional charge

None 14.2oz

(400g)

1lb 12oz

(800g)

2lb 10oz

(1200g)

0.43oz/ft

(40g/m)

R410A

Liquid

Gas

To prevent gas leakage, coat the flare
surface with alkylbenzene oil (HAB).
Do not use mineral oil.

3-way valve

(Liquid)

3-way valve

(Gas)

Flare nut

Flare nut

Connection pipe

(Liquid)

Connection pipe

(Gas)

Body side

90°

Torque wrench

Holding spanner

Blank cap

Charging port

Cap

Service hose

with valve core

Outdoor unit

3-way valve

Connecting pipe

Hexagon wrench

Use a 3/16” (4 mm)
hexagon wrench.

Lo

Hi

 CAUTION

Use a clean gauge mani-

fold  and  charging  hose 

for R410A exclusively.

Service hose

Gauge manifold

Vacuum pump

Flare nut tightening torque

Flare nut [in. (mm)]

Tightening torque [lbf·ft (N·m)]

3/8 (9.52) dia.

23.6 to 31.0 (32 to 42)

5/8 (15.88) dia.

46.5 to 55.3 (63 to 75)

9374995462_IM_EN.indd   2

23-Feb-16   08:45:13

Reviews: