background image

17

TROUBLESHOOTING

WARNING!

Symptom

Doesn’t operate immedi-
ately:

Noise is heard:

Smells:

Mist or steam are
emitted:

Airflow is weak or stops:

Water is produced from
the outdoor unit:

The AIR CLEAN Indicator
Lamp (orange) will begin
to slowly flash (as shown
in the figure):

The AIR CLEAN Indicator
Lamp (orange) will begin
to flash quickly (as shown
in the figure):

Problem

If the unit is stopped and then immediately started again, the com-
pressor will not operate for about 3 minutes, in order to prevent
fuse blowouts.

Whenever the Power Supply Plug is disconnected and then re-
connected to a power outlet, the protection circuit will operate for
about 3 minutes, preventing unit operation during that period.

During operation and immediately after stopping the unit, the
sound of water flowing in the air conditioner’s piping may be
heard. Also, noise may be particularly noticeable for about 2 to 3
minutes after starting operation (sound of coolant flowing).

During operation, a slight squeaking sound may be heard. This is
the result of minute expansion and contraction of the front cover
due to temperature changes.

During Heating operation, a sizzling sound may be heard occasional.
This sound is produced by the Automatic Defrosting operation.

Some smell may be emitted from the indoor unit. This smell is
the result of room smells (furniture, tobacco, etc.) which have
been taken into the air conditioner.

During Cooling or Dry operation, a thin mist may be seen emitted
from the indoor unit. This results from the sudden Cooling of
room air by the air emitted from the air conditioner, resulting in
condensation and misting.

During Heating operation, the outdoor unit’s fan may stop, and
steam may be seen rising from the unit. This is due to Automatic
Defrosting operation.

When Heating operation is started, fan speed is temporarily very
low, to allow internal parts to warm up.

During Heating operation, if the room temperature rises above
the thermostat setting, the outdoor unit will stop, and the indoor
unit will operate at very low fan speed. If you wish to warm the
room further, set the thermostat for a higher setting.

During Heating operation, the unit will temporarily stop opera-
tion (between 7 and 15 minutes) as the Automatic Defrosting mode
operates. During Automatic Defrosting operation, the OPERATION
Indicator Lamp will flash.

The fan may operate at very low speed during Dry operation or
when the unit is monitoring the room’s temperature.

During SUPER QUIET operation, the fan will operate at very low
speed.

In the monitor AUTO operation, the fan will operate at very low
speed.

During Heating operation, water may be produced from the out-
door unit due to Automatic Defrosting operation.

After approximately 400 hours of Air Cleaning Mode use, the AIR
CLEAN Indicator Lamp will begin to flash slowly (as shown in the
figure). When this occurs, please stop the system, remove the
mains socket and carry out maintenance on the dust collecting
unit's air filter.

After approximately 500 hours of Air Cleaning Mode use, the AIR
CLEAN Indicator Lamp will begin to flash quickly (as shown in
the figure). At this point, Air Cleaning will stop functioning. Please
stop the system, remove the mains socket and carry out mainte-
nance on the dust collecting unit's air filter.

See Page

18

18

18

6

6

6

18

14-15

14-15

NORMAL

FUNCTION

In the event of a malfunction (burning smell, etc.), immediately stop operation, turn off the elec-
trical breaker or disconnect the power supply plug, and consult authorized service personnel.
Merely turning off the unit’s power switch will not completely disconnect the unit from the power
source. Always be sure to turn off the electrical breaker or disconnect the power supply plug to
ensure that power is completely off.

Before requesting service, perform the following checks:

08D023_9315345196-01

2008.04.07, 17:50

17

Summary of Contents for AOTS30LDT

Page 1: ... MOUNTED TYPE R410A REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A and Polyol Ester oil THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL Refer to Commonwealth State Territory and local legislation regulations codes installation operation manuals before the installation maintenance and or service of this product 08D023_9315345196_cover 2008 04 07...

Page 2: ...s or heating apparatus Do not climb on or place objects on the air conditioner Do not hang objects from the indoor unit Do not set flower vases or water containers on top of air conditioners Do not expose the air conditioner directly to water Do not operate the air conditioner with wet hands Do not pull power supply cord Turn off power source when not using the unit for extended periods Check the ...

Page 3: ...LOW COOLING DOWNWARD AIRFLOW HEATING For cooling use horizontal airflow so the cool air does not blow directly on the occupants in the room For heating use downward airflow to send powerful warm air to the floor and create a comfortable environment OMNI DIRECTIONAL AIR FLOW SWING OPERATION Three dimensional control over air direction swing is possi ble through dual use of both an UP DOWN air direc...

Page 4: ...g 7 To facilitate explanation the accompanying illustra tion has been drawn to show all possible indicators in actral operation however the display will only show those indicators appropriate to the current op eration Fig 6 O b a R S K M N L J P Y T U V W Q X d c e f Z NAME OF PARTS 08D023_9315345196 01 2008 04 08 15 18 3 ...

Page 5: ...n Speed Display b Temperature SET Display c AIR CLEAN Display d COIL DRY Display e SLEEP Display f SWING Display NAME OF PARTS Fig 1 Indoor Unit 1 Operating Control Panel Fig 2 2 MANUAL AUTO button When kept on pressing the MANUAL AUTO button for more than 10 seconds the forced cooling operation will start The forced cooling operation is used at the time of installation Only for authorized service...

Page 6: ...w while pressing the mark 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 6 Y Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 6 Q to adjust the clock to the current time button Press to advance the time button Press to reverse t...

Page 7: ...ch time the button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Heating Fan operates so as to optimally circulate warmed air However the fan will operate at very low speed when the temperature of the air issued from the indoor unit is low Cooling As the room temperature approaches that of...

Page 8: ...er which it will switch to the selected fan setting This period of time is provided to allow the indoor unit to warm up before begin full operation When the room temperature is very low frost may form on the outside unit and its performance may be reduced In order to remove such frost the unit will automatically enter the defrost cycle from time to time During Automatic Defrosting operation the OP...

Page 9: ...the intake filter and then use the START STOP button to restart the operation Use the FAN CONTROL button to change the fan speed Refer to page 5 The plasma filter unit operates most effectively at the highest fan speed The AIR CLEAN Indicator Lamp orange will flash to inform you that the periodic cleaning of the plasma filter unit is required Refer to page 14 15 If you wish to stop Air Clean Press...

Page 10: ...e display will reappear About the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is indicated by th...

Page 11: ... operation When the SLEEP timer is set the thermostat setting is auto matically raised 1 C every sixty minutes When the thermo stat has been raised a total of 2 C the thermostat setting at that time is maintained until the set time has elapsed at which time the air conditioner automatically turns off SLEEP timer setting During Heating operation When the SLEEP timer is set the thermostat setting is...

Page 12: ...ion 3 When used in a room with infants chil dren elderly or sick persons the air direction and room temperature should be considered carefully when making settings Vertical Air Direction Adjustment Press the SET button Vertical Fig 6 T Each time the button is pressed the air direction range will change as follows 1 2 3 4 5 6 Types of Air flow Direction Setting 1 2 3 During Cooling Dry modes 4 5 6 ...

Page 13: ...ted mould or bacterium and it has no sterilization effect either Begin air conditioner operation before performing this procedure Up down swing operation Left right swing operation Swing operation stops Up down left right swing operation About Swing Operation Up down swing Swing operation begins using the following range according to the current airflow direc tion Airflow direction is 1 4 for cool...

Page 14: ... of the air filter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the panel 2 Close the Intake Grille For purposes of example the illustration shows the unit without Intake Grille installed Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of mild de tergent and warm water If you wash...

Page 15: ...minutes If the plasma filter unit is ex tremely dirty extremely dilute a mild synthetic laun dry detergent low alkalinity or isotope detergent to 15 times the standard concentration and allow the plasma filter unit to soak in it 2 Gently move up and down and to the right and left A soft sponge can also be used to wipe the surface 3 Rinse with clean water 4 Shake the plasma filter unit to drain off...

Page 16: ...s lower side as well as two center points of the lower side as shown in the figure to close it Align the two ends of the dust collection unit with the guide rail and slide in Slide in until it clicks Guide rail Click Click Please ensure that the intake grille is closed properly 1 2 WARNING Be sure the Intake Grille Fig 4 8 is installed securely If after cleaning the dust collection unit the operat...

Page 17: ...nths Please only install filters that are licensed by our company Regarding storage and care of the filter please avoid exposing it to high temperatures and high humidity Also use it as soon as possible after opening its packaging Hook Filter case Filter Case Hook Hook Hook Click When removing the filter please follow these steps backwards How to install or remove the Air cleaning and Deodorizing ...

Page 18: ...arily very low to allow internal parts to warm up During Heating operation if the room temperature rises above the thermostat setting the outdoor unit will stop and the indoor unit will operate at very low fan speed If you wish to warm the room further set the thermostat for a higher setting During Heating operation the unit will temporarily stop opera tion between 7 and 15 minutes as the Automati...

Page 19: ...sufficient heating performance is being produced we recommend you use this air conditioner in conjunction with another kind of heating appliance Heat pump air conditioners heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air con ditioner until the room is heated Microcomputer controlled Automatic Defrosting When ...

Page 20: ...of lower temperature than those listed above the heat exchanger may freeze leading to water leakage and other damage Do not use this unit for any purposes other than the Cooling Dehumidifying and air circulation of rooms in ordinary dwellings If the unit is used for long periods under high humidity conditions condensation may form on the surface of the indoor unit and drip onto the floor or other ...

Reviews: