background image

15

TROUBLESHOOTING

Symptom

Doesn’t operate at all:

Poor Cooling performance:

The unit operates
differently from the Remote
Control Unit’s setting:

See Page

8 - 9

6

5

CHECK ONCE

MORE

Items to check

Is the Power Supply Plug disconnected its outlet?

Has there been a power failure?

Has a fuse blown out, or a circuit breaker been tripped?

Is the timer operating?

Is the Air Filter dirty?

Air the air conditioner’s intake grille or outlet port blocked?

Did you adjust the room temperature settings (thermostat) cor-
rectly?

Is there a window or door open?

In the case of Cooling operation, is a window allowing bright sun-
light to enter? (Close the curtains.)

In the case of Cooling operation, are there heating apparatus and
computers inside the room, or are there too many people in the
room?

Is the unit set for SUPER QUIET operation?

Are the Remote Control Unit’s batteries dead?

Are the Remote Control Unit’s batteries loaded properly?

OPERATING TIPS

If the problem persists after performing these checks, or if you notice burning smells, or the TIMER indicator Lamp (green)
(Fig. 3 

6

) and the OPERATION Indicator Lamp (red) (Fig. 3 

5

) flashes, immediately stop operation, disconnect the Power

Supply Plug (Fig. 1 

E

), and consult authorized service personnel.

Operation and Performance

Heating Performance

This air conditioner operates on the heat-pump princi-
ple, absorbing heat from outdoor air and transferring that
heat indoors. As a result, the operating performance is
reduced as outdoor air temperature drops. If you feel that
insufficient heating performance is being produced, we
recommend you use this air conditioner in conjunction
with another kind of heating appliance.

Heat-pump air conditioners heat your entire room by
recirculating air throughout the room, with the result that
some time may be required after first starting the air con-
ditioner until the room is heated.

Microcomputer-controlled Automatic Defrosting

When using the Heating mode under conditions of low
outdoor temperature and high humidity, frost may form
on the outdoor unit, resulting in reduced operating per-
formance.

In order to prevent this kind of reduced performance, this
unit is equipped with a Microcomputer-controlled Auto-
matic Defrosting function. If frost forms, the air condi-
tioner will temporarily stop, and the defrosting circuit will
operate briefly (for about 7-15 minutes).

During Automatic Defrosting operation, the OPERATION
indicator lamp (red) will flash.

AUTO Restart

In Event of Power Interruption

The air conditioner power has been interrupted by a
power failure. The air conditioner will then restart auto-
matically in its previous mode when the power is restored.

Operated by setting before the power failure.

If a power failure occurs during TIMER operation, the timer
will be reset and the unit will begin (or stop) operation at the
new time setting. In the event that this kind of timer fault
occurs the TIMER Indicator Lamp will flash (see Page. 4).

Use of other electrical appliances (electric shaver, etc.) or
nearby use of a wireless radio transmitter may cause the
air conditioner to malfunction. In this event, temporarily
disconnect the Power Supply Plug, reconnect it, and then
use the Remote Control Unit to resume operation.

Summary of Contents for AOTR18LCC

Page 1: ... AIR CONDITIONER WALL MOUNTED TYPE R410A REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A and Polyol Ester oil THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL Refer to Commonwealth State Territory and local legislation regulations codes installation operation manuals before the installation maintenance and or service of this product ...

Page 2: ...since special purpose tools and specified cord are required Provide occasional ventilation during use Do not direct air flow at fireplaces or heating apparatus Do not climb on or place objects on the air conditioner Do not hang objects from the indoor unit Do not set flower vases or water containers on top of air conditioners Do not expose the air conditioner directly to water Do not operate the a...

Page 3: ...OL UNIT The Wireless Remote Control Unit allows convenient con trol of air conditioner operation SWING OPERATION The Air Flow Direction Louvers swings automatically up and down so that the air speeds to every nook and corner of your room REMOVABLE OPEN PANEL The indoor unit s Open Panel can be removed for easy clean ing and maintenance MILDEW RESISTANT FILTER The AIR FILTER has been treated to res...

Page 4: ...TS Fig 5 Fig 1 Fig 2 Fig 3 Fig 4 Fig 6 P b a S T M O L Q Y N U V W R X c d e Z Fig 7 To facilitate explanation the accompanying illustra tion has been drawn to show all possible indicators in actral operation however the display will only show those indicators appropriate to the current op eration ...

Page 5: ...ply Plug F Power Supply Cord G Air Cleaning Filter Fig 5 Outdoor Unit H Intake Port I Outlet Port J Pipe Unit K Drain port bottom Fig 6 Remote Control Unit L SLEEP button M MASTER CONTROL button N SET TEMP button O COIL DRY button P Signal Transmitter Q TIMER MODE button R TIMER SET button S FAN CONTROL button T START STOP button U SET button V SWING button W RESET button X TEST RUN button This bu...

Page 6: ... the battery compartment lid on the re verse side to open it Slide in the direction of the arrow while pressing the mark 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 6 Y Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 6 R to ...

Page 7: ...ig 6 S Each time the button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Heating Fan operates so as to optimally circulate warmed air However the fan will operate at very low speed when the temperature of the air issued from the indoor unit is low Cooling As the room temperature approache...

Page 8: ...w the indoor unit to warm up before begin full operation When the room temperature is very low frost may form on the outside unit and its performance may be reduced In order to remove such frost the unit will automatically enter the defrost cycle from time to time During Automatic Defrosting operation the OPERATION Indica tor Lamp red Fig 3 5 will flash and the heat operation will be inter rupted ...

Page 9: ...onds later the entire display will reappear About the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operatio...

Page 10: ...Timer Operation Press the START STOP button About the SLEEP Timer To prevent excessive warming or cooling during sleep the SLEEP timer function automatically modifies the thermostat setting in accordance with the set time setting When the set time has elapsed the air conditioner completely stops During Cooling Dry operation When the SLEEP timer is set the thermostat setting is auto matically raise...

Page 11: ...the heat ing range for more than 30 minutes they will automatically return to posi tion 3 When used in a room with infants chil dren elderly or sick persons the air direction and room temperature should be considered carefully when making settings Vertical Air Direction Adjustment Press the SET button Fig 6 U Each time the button is pressed the air direction range will change as follows 1 2 3 4 5 ...

Page 12: ...Fig 7 c and the COIL DRY Indicator Lamp orange Fig 3 8 will light Then it will disappear after 20 minutes To cancel COIL DRY Operation Press the START STOP button Fig 6 T during COIL DRY Operation The COIL DRY Display Fig 7 c and the COIL DRY Indicator Lamp orange Fig 3 8 will go out Then the operation stops About COIL DRY Operation Press the COIL DRY button again during COIL DRY Operation COIL DR...

Page 13: ...lle 1 Align the sides of the air filter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the panel 2 Close the Intake Grille For purposes of example the illustration shows the unit without Intake Grille installed Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of mild de tergent and w...

Page 14: ...o Air filters and close the Intake Grille In regard to the Air Cleaning Filters POLYPHENOL CATECHIN AIR CLEANING FILTER one sheet The Air Cleaning Filters are disposable filters They can not be washed and reused For storage of the Air Cleaning Filters use the filters as soon as possible after the package has been opened The air cleaning effect decreases when the filters are left in the opened pack...

Page 15: ...ner resulting in condensation and misting During Heating operation the outdoor unit s fan may stop and steam may be seen rising from the unit This is due to Automatic Defrosting operation When Heating operation is started fan speed is temporarily very low to allow internal parts to warm up During Heating operation if the room temperature rises above the thermostat setting the outdoor unit will sto...

Page 16: ...t insufficient heating performance is being produced we recommend you use this air conditioner in conjunction with another kind of heating appliance Heat pump air conditioners heat your entire room by recirculating air throughout the room with the result that some time may be required after first starting the air con ditioner until the room is heated Microcomputer controlled Automatic Defrosting W...

Page 17: ...above the heat exchanger may freeze leading to water leakage and other damage Do not use this unit for any purposes other than the Cooling Dehumidifying and air circulation of rooms in ordinary dwellings If the unit is used for long periods under high humidity conditions condensation may form on the surface of the indoor unit and drip onto the floor or other objects underneath About 80 or more Tip...

Page 18: ...17 ...

Page 19: ...18 ...

Page 20: ...19 ...

Reviews: