background image

15

TROUBLESHOOTING

Symptom

Doesn’t operate at all:

Poor Cooling performance:

The unit operates
differently from the Remote
Control Unit’s setting:

See Page

8 - 9

6

5

CHECK ONCE

MORE

Items to check

Is the Power Supply Plug disconnected its outlet?

Has there been a power failure?

Has a fuse blown out, or a circuit breaker been tripped?

Is the timer operating?

Is the Air Filter dirty?

Air the air conditioner’s intake grille or outlet port blocked?

Did you adjust the room temperature settings (thermostat) cor-
rectly?

Is there a window or door open?

In the case of Cooling operation, is a window allowing bright sun-
light to enter? (Close the curtains.)

In the case of Cooling operation, are there heating apparatus and
computers inside the room, or are there too many people in the
room?

Is the unit set for SUPER QUIET operation?

Are the Remote Control Unit’s batteries dead?

Are the Remote Control Unit’s batteries loaded properly?

OPERATING TIPS

If the problem persists after performing these checks, or if you notice burning smells, or both the ORERATION Indicator Lamp
(Fig. 3 

5

) and the TIMER Indicator Lamp (Fig. 3 

6

) flashes, or only the TIMER Indicator Lamp (Fig. 3 

6

) flashes, immediately

stop operation, disconnect the Power Supply, and consult authorized service personnel.

AUTO Restart

In Event of Power Interruption

The air conditioner power has been interrupted by a
power failure. The air conditioner will then restart auto-
matically in its previous mode when the power is restored.

Operated by setting before the power failure.

If a power failure occurs during TIMER operation, the timer
will be reset and the unit will begin (or stop) operation at the
new time setting. In the event that this kind of timer fault
occurs the TIMER Indicator Lamp will flash (see Page. 4 ).

Use of other electrical appliances (electric shaver, etc.) or
nearby use of a wireless radio transmitter may cause the
air conditioner to malfunction. In this event, temporarily
disconnect the Power Supply Plug, reconnect it, and then
use the Remote Control Unit to resume operation.

07H093_9315345141-01_En_body

2007.08.10, 16:43

15

Summary of Contents for AOTR18JCC

Page 1: ... CONDITIONER WALL MOUNTED TYPE R410A REFRIGERANT This Air Conditioner contains and operates with refrigerant R410A and Polyol Ester oil THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL Refer to Commonwealth State Territory and local legislation regulations codes installation operation manuals before the installation maintenance and or service of this product 07H093_9315345141...

Page 2: ...ring use Do not direct air flow at fireplaces or heating apparatus Do not climb on or place objects on the air conditioner Do not hang objects from the indoor unit Do not set flower vases or water containers on top of air conditioners Do not expose the air conditioner directly to water Do not operate the air conditioner with wet hands Do not pull power supply cord Turn off power source when not us...

Page 3: ...se of both an UP DOWN air direction swing and RIGHT LEFT air direction swing Since UP DOWN air direction flaps operate automatically according to the oper ating mode of the unit it is possible to set air direction based on the operating mode REMOVABLE OPEN PANEL The indoor unit s Open Panel can be removed for easy clean ing and maintenance MILDEW RESISTANT FILTER The AIR FILTER has been treated to...

Page 4: ...explanation the accompanying illustra tion has been drawn to show all possible indicators in actral operation however the display will only show those indicators appropriate to the current op eration Fig 6 07H093_9315345141 01_En_body 2007 08 15 13 35 3 ...

Page 5: ...ed Display Temperature SET Display a SLEEP Display b SWING Display NAME OF PARTS Fig 1 Indoor Unit 1 Operating Control Panel Fig 2 2 MANUAL AUTO button When kept on pressing the MANUAL AUTO button for more than 10 seconds the forced cooling operation will start The forced cooling operation is used at the time of installation Only for authorized service personnel s use When the forced cooling opera...

Page 6: ...ile pressing the mark 2 Insert batteries Be sure to align the battery polarities correctly 3 Close the battery compartment lid Set the Current time 1 Press the CLOCK ADJUST button Fig 6 W Use the tip of a ball point pen or other small object to press the button 2 Use the TIMER SET buttons Fig 6 O to adjust the clock to the current time button Press to advance the time button Press to reverse the t...

Page 7: ... To Set the Fan Speed Press the FAN button Fig 6 P Each time the button is pressed the fan speed changes in the following order AUTO HIGH MED LOW QUIET About three seconds later the entire display will reappear When set to AUTO Cooling As the room temperature approaches that of the thermostat setting the fan speed becomes slower Fan The fan runs at the low fan speed The fan will operate at a very ...

Page 8: ... temperature to the value set in the thermostat The monitor operation range is 2 C relative to the thermostat set ting If the mode automatically selected by the unit is not what you wish select one of the mode operation COOL DRY FAN About Mode Operation Cooling Use to cool your room Dry Use for gently cooling while dehumidifying your room You cannot heat the room during Dry mode During Dry mode th...

Page 9: ...splay will reappear About the Program timer The program timer allows you to integrate OFF timer and ON timer operations in a single sequence The sequence can involve one transition from OFF timer to ON timer or from ON timer to OFF timer within a twenty four hour period The first timer function to operate will be the one set nearest to the current time The order of operation is indicated by the ar...

Page 10: ...EEP timer function automatically modifies the thermostat setting in accord ance with the set time setting When the set time has elapsed the air conditioner completely stops During Cooling Dry operation When the SLEEP timer is set the thermostat setting is automatically raised 1 C every sixty minutes When the thermostat has been raised a total of 2 C the thermostat setting at that time is maintaine...

Page 11: ...ally returned to the 3 range When used in a room with infants chil dren elderly or sick persons the air direction and room temperature should be considered carefully when making settings Vertical Air Direction Adjustment Press the SET button Vertical Fig 6 R Each time the button is pressed the air direction range will change as follows 1 2 3 4 5 6 Types of Air flow Direction Setting 1 2 3 During C...

Page 12: ...low direc tion Airflow direction is 1 4 for cooling dry With the upper airflow direction louver in the horizontal position the lower airflow direction louver moves swings to direct airflow to a wide area Left right swing The airflow direction louvers move swing in the left right airflow direction Up down left right swing The airflow direction louvers move swing in both the up down and left right a...

Page 13: ...the air filter with the panel and push in fully making sure the two lower tabs are returned properly to their holes in the panel 2 Close the Intake Grille For purposes of example the illustration shows the unit without Intake Grille installed Dust can be cleaned from the air filter either with a vacuum cleaner or by washing the filter in a solution of mild de tergent and warm water If you wash the...

Page 14: ...n not be washed and reused For storage of the Air Cleaning Filters use the filters as soon as possible after the package has been opened The air cleaning effect decreases when the filters are left in the opened package Generally the filters should be exchanged about every three months Please buy delicated air cleaning filters UTR FA13 1 Sold separately to exchange the used dirty air cleaning filte...

Page 15: ...t This smell is the result of room smells furniture tobacco etc which have been taken into the air conditioner During Cooling or Dry operation a thin mist may be seen emitted from the indoor unit This results from the sudden Cooling of room air by the air emitted from the air conditioner resulting in condensation and misting The fan may operate at very low speed during Dry operation or when the un...

Page 16: ...e problem persists after performing these checks or if you notice burning smells or both the ORERATION Indicator Lamp Fig 3 5 and the TIMER Indicator Lamp Fig 3 6 flashes or only the TIMER Indicator Lamp Fig 3 6 flashes immediately stop operation disconnect the Power Supply and consult authorized service personnel AUTO Restart In Event of Power Interruption The air conditioner power has been inter...

Page 17: ...ose listed above the heat exchanger may freeze leading to water leakage and other damage Do not use this unit for any purposes other than the Cooling Dehumidifying and air circulation of rooms in ordinary dwellings If the unit is used for long periods under high humidity conditions condensation may form on the surface of the indoor unit and drip onto the floor or other objects underneath About 80 ...

Page 18: ...07H093_9315345141 01_En_body 2007 08 10 16 43 17 ...

Page 19: ...07H093_9315345141 01_En_body 2007 08 10 16 43 18 ...

Page 20: ...07H093_9315345141 01_En_body 2007 08 10 16 43 19 ...

Reviews: