CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
MODEL
: AO
G09LTCN
H
H
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HEATING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.896
0.879
10
-
-
0.968
0.890
0.879
7.5
-
0.994
0.968
0.896
0.879
5
1.000
0.994
0.968
0.896
0.879
0
1.000
0.994
0.968
0.896
0.879
Û
2
Indoor unit is
lower than
outdoor unit
-5
0.995
0.989
0.963
0.891
0.875
-7.5
-
0.987
0.961
0.889
0.873
-10
-
-
0.959
0.887
0.871
-15
-
-
-
0.878
0.862
COOLING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
Û
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.858
0.868
10
-
-
0.929
0.872
0.882
7.5
-
0.960
0.933
0.876
0.885
5
0.992
0.964
0.937
0.879
0.889
0
1.000
0.972
0.944
0.887
0.896
Û
2
Indoor unit is
lower than
outdoor unit
-5
1.000
0.972
0.944
0.887
0.896
-7.5
-
0.972
0.944
0.887
0.896
-10
-
-
0.944
0.887
0.896
-15
-
-
-
0.887
0.896
Summary of Contents for AO G09LTCN Series
Page 2: ...1 INDOOR UNIT WALL MOUNTED TYPE AS G09LTCB AS G12LTCB AS G14LTCB DTR_AS057E_03 2013 01 10 ...
Page 12: ... 01 09 WALL MOUNTED TYPE AS G09 14LT WALL MOUNTED TYPE AS G09 14LT INSTALLATION PLACE Unit mm ...
Page 36: ...2 OUTDOOR UNIT SINGLE TYPE AO G09LTCN AO G12LTCN AO G14LTCN DTR_AO092E_02 2013 01 10 ...
Page 44: ... 02 07 OUTDOOR UNIT AO G09 14LT OUTDOOR UNIT AO G09 14LT MODEL AO G14LTCN ...
Page 52: ... 02 15 OUTDOOR UNIT AO G09 14LT OUTDOOR UNIT AO G09 14LT SOUND LEVEL CHECK POINT 88888 ...