CAPACITY COMPENSATION RATE FOR PIPE LENGTH
5.
AND HEIGHT DIFFERENCE
MODEL
: AO G09LECAN
HEATING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.990
0.969
10
-
-
1.002 0.990 0.969
7.5
-
1.001 1.002 0.990 0.969
5
1.000 1.001 1.002 0.990 0.969
0
1.000 1.001 1.002 0.990 0.969
2
Indoor unit is
lower than
outdoor unit
-5
0.995 0.996 0.997 0.985 0.964
-7.5
-
0.994 0.995 0.983 0.962
-10
-
-
0.992 0.980 0.960
-15
-
-
-
0.970 0.950
COOLING
Pipe length (m)
5
7.5
10
15
20
Height
difference H
(m)
1
Indoor unit is
higher than
outdoor unit.
15
-
-
-
0.913 0.922
10
-
-
0.963 0.928 0.937
7.5
-
0.980 0.967 0.932 0.941
5
0.992 0.984 0.971 0.936 0.945
0
1.000 0.992 0.979 0.943 0.953
2
Indoor unit is
lower than
outdoor unit
-5
1.000 0.992 0.979 0.943 0.953
-7.5
-
0.992 0.979 0.943 0.953
-10
-
-
0.979 0.943 0.953
-15
-
-
-
0.943 0.953
Height difference H
1 Indoor unit is higher than outdoor unit.
2 Indoor unit is lower than outdoor unit.
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
H
H
Connection pipe