- (01 - 29) -
D
U
C
T T
YP
E
AR
C
45
-5
4LC
D
U
C
T T
YP
E
AR
C
45
-5
4LC
(5) Press the TIMER SET button to confirm the setting. Press the TIMER SET button for a few seconds until the setting value stops
flashing. If the setting value display changes or if “- -” is displayed when the flashing stops, the setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor unit.)
Setting value
SU MO TU WE TH FR SA
(6) Repeat steps 2 to 5 to perform additional settings. Press the set temperature buttons ( ) ( ) and fan control button simultaneously
again for more than 5 seconds to cancel the function setting mode. In addition, the function setting mode will be automatically canceled
after 1 minute if no operation is performed.
(7) After completing the FUNCTION SETTING, be sure to turn off the power and turn it on again.
!
CAUTION
• After turning off the power, wait 30 seconds or more before turning on it again. The FUNCTION SETTING doesn’t become
effective if it doesn’t do so.
CONTENTS FUNCTION SETTING
1. Room temperature control for cooling
• Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
(
. . .Factory setting)
Setting description
Function number
Setting value
Standard
30
00
Slightly lower control
01
Higher control
02
Lower control
03
2. Room temperature control for heating
• Depending on the installed environment, correction of the room temperature sensor may be required.
Select the appropriate control setting according to the installed environment.
(
. . .Factory setting)
Setting description
Function number
Setting value
Standard
31
00
Lower control
01
Slightly higher control
02
Higher control
03
3. Auto restart
• Enable or disable automatic restart after a power
(
. . .Factory setting)
Setting description
Function number
Setting value
Enable
40
00
Disable
01
• Auto restart is an emergency function such as for power outage etc. Do not attempt to use this function in normal operation.
Be sure to operate the unit by remote controller or external device.
4.Room temperature sensor switching
• (Only for wired remote controller)
When using the Wired remote controller temperature sensor, change the setting to "Both" (01)..
(
. . .Factory setting)
Setting description
Function number
Setting value
Indoor unit
42
00
Both
01
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
*Remote controller sensor must be turned on by using the remote controller.