En-19
4.10.1. SELECTING WIRING AND BREAKER
Refer to Tables 4.10-1, 4.10-2, and 4.10-3 for the wiring and breaker specifications at each installation condition.
Table 4.10-1 Breaker and wiring specifications for each model
1) Observe the following instructions pertaining to wire length.
Maximum wiring length: Keep the voltage drop within 2%.
If the wiring length is long, increase the wiring diameter.
Master unit
AJ A72LBTF
40
6
4
37
AJ A90LBTF
40
6
4
33
AJ 126LBTF
63
10
6
39
Slave unit
AJ A72UBTF
40
6
4
37
AJ A90UBTF
50
6
4
30
AJ 126UBTF
63
10
6
37
Model name
Breaker
capacity (A)
Power supply
line (mm
2
)
Ground wire
(mm
2
)
Critical wiring
length (m)
1)
Table 4.10-3 Transmission cable
Use
Size
Wire type
Remarks
LONWORKS compatible cable
22AWG LEVEL 4 (NEMA) non-polar 2 core,
twisted pair solid core diameter 0.65 mm
Transmission cable
0.33 (mm
2
)
Table 4.10-2 Main breaker and wiring specifications if multiple power supply lines are integrated
AJ A72LBTF
AJ
A72UBTF
—
100
14
5.5
49
AJ A90LBTF
AJ
A72UBTF
—
100
14
5.5
47
AJ A90LBTF
AJ
A90UBTF
—
100
14
5.5
42
AJ 126LBTF
AJ A72UBTF
—
125
22
8
55
AJ 126LBTF
AJ A90UBTF
—
125
22
8
51
AJ A90LBTF
AJ
A72UBTF
AJ
A72UBTF
150
22
8
50
AJ 126LBTF
AJ 126UBTF
—
150
38
8
72
AJ A90LBTF
AJ
A90UBTF
AJ
A90UBTF
150
38
8
76
AJ 126LBTF
AJ A90UBTF
AJ
A72UBTF
175
38
14
67
AJ 126LBTF
AJ A90UBTF
AJ
A90UBTF
175
38
14
63
AJ 126LBTF
AJ 126UBTF
AJ A72UBTF
200
60
14
90
AJ 126LBTF
AJ 126UBTF
AJ A90UBTF
200
60
14
86
AJ 126LBTF
AJ 126UBTF
AJ 126UBTF
250
60
22
75
Breaker
capacity (A)
Power supply
line (mm
2
)
Ground wire
(mm
2
)
Critical wiring
length (m)
1)
Model name
Master unit
Slave unit 1
Slave unit 2
1) Observe the following instructions pertaining to wire length.
Maximum wiring length: Keep the voltage drop within 2%.
If the wiring length is long, increase the wiring diameter.
Breaker for
leakage current
100 mA 0.1 sec
or less
CAUTION
• Pay attention to the following points while attaching wires on the terminal board.
Do not attach 2 wires on one side.
Do not twist wires.
Do not cross the wires.
Do not shorted at edge at root.
No Good
No Good
No Good
No Good
No Good
2pcs at one side
Wires twisted
Wires crossed
Shorted at edge
Shorted at root
OK
1 wire
OK
2 wires
9374241033_IM_en_p18-36.p65
26/8/2008, 18:23
19