3-4. Function summary of indoor unit external input and output
¢
Indoor unit external input function
Dry contact/ Apply voltage
Dry contact DC 12 V
Apply voltage
Function
Operation/Stop
●
(46-00)
—
●
(46-00)
—
Emergency stop
●
(46-01)
—
●
(46-01)
—
Forced stop
●
(46-02)
—
●
(46-02)
—
Forced thermostat off
—
●
(60-00)
—
●
(60-00)
Specifications
Terminal
CNA02
(Pin1-3)
CNA02
(Ch1: Pin1-3)
(Ch2: Pin2-3)
CNA04
(Pin1-2)
CNA01
(Pin1-2)
CNA01
(Ch1: Pin1-2)
(Ch2: Pin1-3)
CNA03
(Pin1-2)
Signal type
Edge
Pulse *
Edge
Edge
Pulse *
Edge
External
power
supply
Allowable
voltage
—
DC 12 to 24 V
Allowable
current
—
10 mA or less
Wire size
22 AWG (0.33 mm
2
), Twisted
Max. cable length
492 ft (150 m)
*: Default setting is Edge signal. If you use Pulse signal, DIP switch 2-2 must be set to “On”.
¢
Indoor unit external output function
Dry contact/ Apply voltage
Dry contact
Function
Operation status
●
—
—
—
Error status
—
●
—
—
Indoor unit fan operation status
—
●
—
Auxiliary heater output
—
—
—
● *
Specifications
Terminal
CNB01
(Pin1-2)
CNB01
(Pin1-3)
CNB01
(Pin1-4)
CNB01
(Pin1-5)
Terminal output voltage
DC 12 V
Wire size
22 AWG (0.33 mm
2
), Twisted
Max. cable length
82 ft (25 m)
*: Auxiliary heater is only available for duct type indoor unit. If you use Auxiliary heater output, DIP
switch 2-3 must be set to “On”.
3-4. Function summary of indoor unit external input and output
- (08-55) -
3. Indoor unit
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...