1-4. Address setting by remote controller
¢
Address setting by wireless remote controller
• A wireless remote controller is required to set the infrared address setting.
• Infrared address setting function is available in all indoor units with infrared signal receiver.
• Infrared address setting for duct type and cassette type models can be performed by using the op-
tional IR receiver unit.
NOTE:
The beeping sound is emitted from the Indoor unit PCB. Since the indoor unit is installed
far away, the sound might not be heard. (The sound is not emitted from the IR receiver
unit.)
• The indoor unit address and the indoor unit refrigerant circuit address can be set by performing the
infrared address setting.
• When remote controller address setting is required, set by the rotary switch on the indoor unit
PCB.
Preparation
1.
(This step is unnecessary for newly installed and not yet set the switch.)
Set the rotary switch on the indoor unit PCB for manual address setting. (Initially set to “00” as
factory setting.)
The layout of the switches differs by the type of the indoor unit. For the details, refer to
Rotary switch
(type A)
SW601
SW602
SW604 SW605
SW606 SW607 SW608
Check the switch position is set at “0”.
(Factory setting)
IU AD x10
IU AD x1
REF AD x10
REF AD x1
2.
Before turning on the power of indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
3.
Turn on the power of indoor units.
By turning on the power, the indoor units initialize EEV.
Indoor units
Indoor units
Breaker ON
1-4. Address setting by remote controller
- (07-15) -
1. System settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...