4-2. Power supply cable
RELATED LINKS
in Chapter 3. OUTDOOR UNITS on page 03-21
in Chapter 4. INDOOR UNITS on page 04-26
¢
Specifications
Use a separate power supply for the outdoor unit and indoor unit.
Outdoor unit
Model
MCA (A)
MAX. CKT. BKR (A)
GFEB
AOU72RLAVL
38
40
100 mA, 0.1 sec or less
AOU96RLAVL
39
AOU120RLAVL
47
50
• MCA: Minimum Circuit Ampacity
• MAX. CKT. BKR: Maximum Circuit Breaker
• GFEB: Ground Fault Equipment Breaker
• Select the power cable type and size in accordance with local regulations.
• Select a wire length (maximum wire length) so that the voltage drop is less than 2%.
• When the wire length is long and voltage drop exceeds this value, increase the wire diameter to
stay within design limits.
Indoor unit
Model
Recommended
cable size (AWG)
MAX. CKT. BKR (A)
Breaker for leakage
current
Remarks
All models
16 to 10
15
Refer to Table B
208/230 V ~ 60 Hz
2 wire + ground
Refer to the table for the breaker specifications of each installation condition.
Perform the power crossover wiring within the range of the same refrigerant system. When the pow-
er crossover wiring is done, make a connection for indoor units to satisfy conditions of Table A and B
below.
• Select the power cable type and size in accordance with local regulations.
• Include at least one breaker and one disconnect per refrigerant circuit.
• Power supply circuits should only be connected to units and the same refrigerant circuit.
• Design the power supply circuit to keep the voltage drop within 2%.
4-2. Power supply cable
- (06-50) -
4. Wiring design
SYSTEM
DESIGN
SYSTEM
DESIGN
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...