1. System design
1-1. Refrigerant system
¢
Connectable unit within 1 refrigerant system
•
Outdoor unit
Unit
Quantity
Outdoor unit
1 unit
•
Indoor unit
Outdoor unit
Connectable indoor unit conditions
Ton
Model name
Cooling
capacity
(Btu/h)
Cooling capacity range
Connectable number
6
AOU72RLAVL
72,000
50 to 150%
of outdoor unit cooling
capacity
1 to 18 units
8
AOU96RLAVL
96,000
1 to 24 units
10
AOU120RLAVL
120,000
1 to 30 units
CAUTION
• When all indoor units are operating at maximum capacity, individual indoor unit operates at a
slightly lower capacity. (When connecting more than 100%)
• Do not exceed both of connectable cooling capacity range and maximum connectable indoor
unit quantity, otherwise it may cause hinder the return of the refrigerant oil and cause a com-
pressor breakdown.
1-1. Refrigerant system
- (06-1) -
1. System design
SYSTEM
DESIGN
SYSTEM
DESIGN
Summary of Contents for AIRSTAGE J-IIIL
Page 1: ...DESIGN TECHNICAL MANUAL ...
Page 3: ...1 GENERAL INFORMATION 2019 11 01 DV_CH01_J3LU061EF_02 ...
Page 20: ...2 5 Others 01 16 2 Optional parts GENERAL INFORMATION GENERAL INFORMATION ...
Page 21: ...2 MODEL SELECTION 2019 11 01 DV_CH02_J3LU061EF_02 ...
Page 94: ...5 1 Stand alone 02 72 5 Heating capacity table Outdoor unit MODEL SELECTION MODEL SELECTION ...
Page 95: ...3 OUTDOOR UNITS 2019 03 07 DV_CH03_J3LU061EF_01 ...
Page 120: ...11 1 Stand alone 03 24 11 Accessories OUTDOOR UNITS OUTDOOR UNITS ...
Page 121: ...4 INDOOR UNITS 2019 11 01 DV_CH04_J3LU061EF_02 ...
Page 337: ...5 CONTROL SYSTEM 2019 11 01 DV_CH05_VR2E018EF_04 ...
Page 521: ...6 SYSTEM DESIGN 2019 11 01 DV_CH06_J3LU061EF_02 ...
Page 599: ...7 FUNCTION SETTINGS 2019 11 01 DV_CH07_J3LU061EF_02 ...
Page 753: ...8 EXTERNAL INPUT AND OUTPUT 2019 11 01 DV_CH08_J3LU061EF_02 ...
Page 831: ...9 NOTES 2019 11 01 DV_CH09_J3LU061EF_04 ...
Page 850: ...4 2 Wiring connection 09 18 4 About connection between series NOTES NOTES ...
Page 851: ...10 OPTIONAL PARTS 2019 11 01 DV_CH10_VR2E018EF_05 ...