4-2. POWER SUPPLY CABLE WIRING
POWER SUPPLY CABLE SPECIFICATIONS
Use a separate power supply for the outdoor unit and indoor unit.
z
Outdoor unit
Selection of the power supply cable and breaker when connecting single outdoor unit.
Refer to the table for the breaker specifications of each installation condition.
Use
Size
Remarks
Power supply cable
8 AWG (8.4 mm²)
2 cable + Ground, ~ 208 / 230 V
Model
MCA
(A)
MAX.CKT.BKR
(A)
GFEB
AOU36RLAVM
33
40
30 mA
0.1 sec or less
AOU48RLAVM
AOU60RLAVM
37
MCA : Minimum Circuit Ampacity
MAX.CKT.BKR : Maximum Circuit Breaker
GFEB : Ground Fault Equipment Breaker
●
Select the power cable type and size in accordance with local regulations.
●
Select a wire length (Max. wire length) such that the voltage drop is less than 2%.
●
When the wire length is long and voltage drop exceeds this value, increase the wire
diameter to stay within design limits.
z
Indoor unit
Refer to the table for the breaker specifications of each installation condition. Perform the
power crossover wiring within the range of the same refrigerant system.When the crossover
wiring is done, make a connection for "indoor units" to satisfy conditions Table A and Table B
below.
Table A. Current breaker requirements
Model
MCA
(A)
MAX.CKT.BKR
(A)
All models
*1
15
MCA : Minimum Circuit Ampacity
MAX.CKT.BKR : Maximum Circuit Breaker
*1 : Refer chapter 4.2. ELECTRIC CHARACTERISTICS
When the power crossover wiring is done, make it so that the total of the MCA of the
connected "indoor units" does not exceed the 11 A.
NOTE: With Vertical air handler type, connect only one indoor unit to a MAX.CKT.BKR.
(Crossover wiring is prohibited.) Select a minimum of 7 or more multiples of rated current under
the condition time in seconds 10 ms (0.01 S) or less at the current breaker trip curves (time in
seconds/multiples of rated current).
Table B. Ground Fault Equipment Breaker requirements
Breaker capacity
Maximum connectable "Units"
30 mA, 0.1 sec or less
9 or less
- (06 - 39) -
SY
ST
EM
DE
SIGN
SY
ST
EM
DE
SIGN
Summary of Contents for Airstage AGUA12TLAV1
Page 1: ...Small VRF system for light commercial and home use DESIGN TECHNICAL MANUAL ...
Page 22: ...1 GENERAL INFORMATION DTV_J2U045E_06 CHAPTER01 2018 03 16 ...
Page 38: ...2 MODEL SELECTION DTV_J2U045E_05 CHAPTER02 2018 03 16 ...
Page 113: ...3 OUTDOOR UNITS DTV_J2U045E_02 CHAPTER03 2016 04 13 ...
Page 122: ...5 WIRING DIAGRAM MODELS AOU36RLAVM AOU48RLAVM 03 08 OUTDOOR UNITS OUTDOOR UNITS ...
Page 123: ... MODELS AOU60RLAVM 03 09 OUTDOOR UNITS OUTDOOR UNITS ...
Page 127: ... SOUND LEVEL CHECK POINT Microphone Airflow 39 3 8 in 1 m 03 13 OUTDOOR UNITS OUTDOOR UNITS ...
Page 130: ...4 INDOOR UNITS DTV_VR2U025E_10 CHAPTER04 2018 01 26 ...
Page 203: ...4 WIRING DIAGRAMS 4 1 COMPACT CASSETTE TYPE MODEL AUUA4TLAV1 04 70 INDOOR UNITS INDOOR UNITS ...
Page 207: ...4 4 MINI DUCT TYPE MODEL ARUL4TLAV1 04 74 INDOOR UNITS INDOOR UNITS ...
Page 211: ... MODELS ARUH72TLAV1 ARUH96TLAV 04 78 INDOOR UNITS INDOOR UNITS ...
Page 215: ...4 11 CEILING TYPE MODELS ABUA30TLAV ABUA36TLAV 04 82 INDOOR UNITS INDOOR UNITS ...
Page 217: ... MODELS ASUA12TLAV1 ASUA14TLAV1 04 84 INDOOR UNITS INDOOR UNITS ...
Page 218: ... MODELS ASUB18TLAV1 ASUB24TLAV1 04 85 INDOOR UNITS INDOOR UNITS ...
Page 219: ... MODELS ASUB30TLAV1 ASUB36TLAV1 04 86 INDOOR UNITS INDOOR UNITS ...
Page 220: ... MODELS ASUA7TLAV ASUA9TLAV ASUA12TLAV ASUA14TLAV 04 87 INDOOR UNITS INDOOR UNITS ...
Page 221: ... MODELS ASUB18TLAV ASUB24TLAV 04 88 INDOOR UNITS INDOOR UNITS ...
Page 361: ...5 CONTROL SYSTEM DTV_VR2U025E_14 CHAPTER05 2018 03 16 ...
Page 563: ...6 SYSTEM DESIGN DTV_J2U045E_05 CHAPTER06 2017 12 26 ...
Page 645: ...7 FUNCTION SETTING DTV_VR2U025E_12 CHAPTER07 2018 03 16 ...
Page 819: ...8 EXTERNAL INPUT OUTPUT DTV_VR2U025E_08 CHAPTER08 2017 12 26 ...
Page 878: ...9 NOTES DTV_VR2U025E_10 CHAPTER09 2017 12 26 ...
Page 894: ...10 OPTIONAL PARTS DTV_VR2U025E_12 CHAPTER10 2018 03 16 ...
Page 935: ...4 5 WIRING DIAGRAMS MODEL UTP RU01AH MODEL UTP RU01BH 10 40 OPTIONAL PARTS OPTIONAL PARTS ...
Page 936: ... MODEL UTP RU01CH 10 41 OPTIONAL PARTS OPTIONAL PARTS ...
Page 937: ... MODEL UTP RU04BH 10 42 OPTIONAL PARTS OPTIONAL PARTS ...