6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Model: AOUH09LUAS1
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5
7.5
10
15
20
ft
16
25
33
49
66
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
—
—
—
0.883
0.893
10
33
—
—
0.956
0.897
0.907
7.5
25
—
0.988
0.960
0.901
0.910
5
16
1.021
0.992
0.964
0.904
0.915
0
0
1.029
1.000
0.971
0.913
0.922
Indoor unit is lower than outdoor
unit *2
-5
-16
1.029
1.000
0.971
0.913
0.922
-7.5
-25
—
1.000
0.971
0.913
0.922
-10
-33
—
—
0.971
0.913
0.922
-15
-49
—
—
—
0.913
0.922
HEATING
Pipe length
m
5
7.5
10
15
20
ft
16
25
33
49
66
Height difference H
Indoor unit is higher than outdoor
unit *1
15
49
-
-
-
0.901
0.884
10
33
-
-
0.974
0.901
0.884
7.5
25
-
1.000
0.974
0.901
0.884
5
16
1.006
1.000
0.974
0.901
0.884
0
0
1.006
1.000
0.974
0.901
0.884
Indoor unit is lower than outdoor
unit *2
-5
-16
1.001
0.995
0.969
0.896
0.880
-7.5
-25
-
0.993
0.967
0.894
0.878
-10
-33
-
-
0.965
0.892
0.876
-15
-49
-
-
-
0.883
0.867
- 90 -
6-1. Model: AOUH09LUAS1
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOUH09-18LUAS1
OUTDOOR UNIT
AOUH09-18LUAS1